Kód modelu: EU2E-SWD-4DD-1

Eaton EU2E SmartWire-DT T-Connector for IP69K I/O modules, 24 V DC, four parameterizable inputs/outputs with power supply, two M12 I/O sockets EU2E-SWD-4DD-1

General specifications

Product Name
Eaton EU2E Digital module
Catalog Number
180406
EAN
4015081755592
Product Length/Depth
110 mm
Product Height
40 mm
Product Width
80 mm
Product Weight
0.08 kg
Certifications
UL
CSA
IEC/EN 61131-2
UL File No.: E170645
Catalog Notes
Plug configuration (X1: 1 I/O, X2: 3 I/O)
Model Code
EU2E-SWD-4DD-1

Vlastnosti a funkce

Electric connection type
Screw connection
Features
Overload proof (with diagnostics)
Digital inputs configurable
Fieldbus connection over separate bus coupler possible
Short-circuit protection (sensor supply)
Overload protection (sensor supply)
Digital outputs configurable
Functions
Short-circuit protection, outputs available
For connection of digital I/O signals

Obecné

Current consumption
70 mA, Max. current consumption per M12 I/O plug, Sensor supply, SmartWire-DT network
75 mA, SmartWire-DT network, 24 V, without sensor and without I/O supply
Degree of protection
IP69K
Mounting method
Screw fixing (M4)
Wall mounting/direct mounting
Mounting section (Clip M20)
DIN rail
Rail mounting possible
Overvoltage category
II
Pollution degree
3
Product category
SmartWire-DT slave
Type
Digital modules
Voltage type
DC

Okolní podmínky, mechanické

Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
As required
Shock resistance
30 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts

Klimatické podmínky a podmínky prostředí

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2
Environmental conditions
Condensation: permissible
Operating temperature - min
-25 °C
Operating temperature - max
70 °C
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)

Elektromagnetická kompatibilita

Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
1 kV, Signal cable, according to IEC/EN 61131-2, Level 3
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference class
Class A (EN 55011)
Surge rating
1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC
0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC

Jmenovité elektrické charakteristiky

Input current
4 mA (at 24 V DC, Digital inputs)
Input current at signal 1
4 mA
Output current
0.5 A
Power loss
1.8 W
Short-circuit protection
Outputs are short-circuit proof
Short-circuit tripping current
Max. 1.2 A over 3 ms, Digital semi-conductor outputs
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
0 VDC
Supply voltage at DC - max
28.8 VDC

Komunikace

Connection to SmartWire-DT
Yes
Connection type
SWD-IN : M12 plug (A-keyed), 5 pole
5-pin M12 socket (A-keyed), Supply and I/O sensor
SWD-OUT: M12 socket (A-keyed), 5 pole
Data transfer rate
2 MBit/s, SmartWire-DT
Setting automatically
LED indicator
Status indication of display outputs: Yellow LED
Status indication of SmartWire-DT network: Green LED
Status indication of input: Yellow LED
Protocol
Other bus systems
Station
SmartWire-DT slave, SmartWire-DT network

Vstup/výstup

Input
Max. 4 Freely configurable inputs/outputs
Input delay
< 0.2 ms
Lamp load
≤ 3 W (at RLL)
Limit value type 1
High: > 15 V DC
Low: < 5 V DC
Number of inputs (digital)
4
Number of outputs (digital)
4
Output
Max. 4 Transistor Outputs
Max. 4 Freely configurable inputs/outputs
Switching capacity
IEC/EN 60947-5-1, utilization category DC-13, Digital outputs

Bezpečnost

Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Input to input: no
Output to output: no
Output to input: no
Between Outputs to SmartWire-DT: no
Inputs for SmartWire-DT: no

Ověření návrhu

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.8 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.