Stáhnout dokument () z 20
Věci, na kterých záleží, díky nám fungují.

183030
Kód modelu: XNH00-FCE-A160-BT

Eaton xEffect - XNH circuit protection. NH fuse-switch 3p box terminal 1,5 - 95 mm², mounting plate, electronic fuse monitoring, NH000 & NH00

General specifications

Product Name
Eaton xEffect XNH device for mounting plate
Catalog Number
183030
EAN
4015081779574
Product Length/Depth
204 mm
Product Height
117 mm
Product Width
106 mm
Product Weight
0.771 kg
Compliances
RoHS conform
Certifications
IEC/EN 60947-3
Model Code
XNH00-FCE-A160-BT

Delivery program

Type
Fuse control - electronic
Color
Gray
Number of poles
Three-pole

Technical data - electrical

Voltage test
Yes, sliding inspection windows
Voltage inputs
400 V AC - 500 V AC (+/-10%)
Voltage rating at AC
  • 400 V (AC-23B)
  • 500 V (AC-22B)
  • 690 V (AC-21B)
Voltage rating at AC - max
250 VAC
Voltage rating at DC
  • 250 V DC at DC-22B
  • 440 V DC at DC-21B
Voltage rating at DC - max
24 VDC
Rated operating voltage (Ue) at AC - max
500 V
Rated insulation voltage (Ui)
800 VAC
Rated impulse withstand voltage (Uimp)
8 kV
Rated uninterrupted current (Iu)
160 A
Rated conditional short-circuit current (Iq)
120 kA
Rated operation current (Ie)
160 A
Rated operational current
160 A (AC-21B)
160 A
160 A (AC-23B)
160 A (AC-22B)
Switching current of electronic fuse monitoring - max
1 A
Rated short-time withstand current (Icw)
7 kA
Rated conditional short-circuit rating
100 kA (690 V)
120 kA (500 V)
Conditioned rated short-circuit current Iq
120 kA
Frequency rating
40 Hz - 60 Hz
Frequency rating of contacts
40 Hz - 60 Hz
Frequency rating (electronic fuse monitoring)
50 - 60 Hz
Creepage resistance
CTI 600
Power rating at AC-23, 400 V
0 kW
Rated operation power at AC-23, 400 V
0 kW
Permitted power loss per fuse link - max
12 W
Electronic fuse monitoring
3 LEDs (F1, F2, F3) red
> 1 kOhm/V
1.5 VA
NH with live handle straps
Self-supplied
1 LED green
Test button for relay + LEDs
1 NC
1 NO
Electrical connection type of main circuit
Frame clamp
Operating altitude without derating - max
2000 mm
Overvoltage category
III
III (230/400 V)
II (500 V)
Pollution degree
3
Direction of incoming supply
As required
Lifespan, electrical
300 operations

Technical data - mechanical

Activation type
Dependent manual activation
Actuator position
Front side
Actuator type
Cover grip
Size
NH000 / NH00 fuse
Mounting method
Mounting plate
DIN rail
Mounting position
Vertical or horizontal
Material
Polyamide
Degree of protection
IP2XC (contact protection, XNH installed)
IP10 (handle cover open, XNH installed)
IP3X
IP20 (operating status, XNH installed)
Degree of protection (front side)
Other
Terminal capacity (copper band)
9 mm x 0.8 mm (6x) at box terminal
Terminal capacity (copper busbar)
Bolt diameter at flange connection: M8
20 mm x 10 mm
Max. 25 mm cable lug width at flange connection
Terminal capacity (copper strip)
9 mm x 0.8 mm (9x) at box terminal
Terminal capacity (stranded cable)
1.5 mm² - 95 mm² at box terminal
10 mm² - 70 mm² at clamp-type terminal
1.5 mm² - 50 mm² at box terminal
Cable entry type
Other
Locking facility
Yes, optional
Suitable for fuses
NH00
Lifespan, mechanical
1400 operations

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
160 A
Equipment heat dissipation, current-dependent
9 W
Heat dissipation per pole, current-dependent
3 W
Total heat dissipation without fuses at Ith
9 W
Heat dissipation at 80% without fuses
5.8 W
Ambient operating temperature details
  • Ambient temperature range: -25 °C - 70 °C
  • Operating temperature range: -5 °C - 55 °C
Heat deflection temperature
125 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 800 V AC
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Features
Electronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-4
Electronic fuse monitoring and EMC (Electromagnetic compatibility) as of IEC 61000-4-5
Halogen free
Standard sealable
Fitted with:
Error protection
Connectors
Flammability characteristics (UL)
Self-extinguishing (UL 94)
Special features
  • Permanent operation (rated operating mode)
  • Current paths of electrolytic copper, silver-plated
  • With electronic monitoring of fuse-links
Suitable for
Ground mounting
Front mounting

Exportovat specifikaci produktu