Tietohaku
Lataa dokumentti () / 20

113759
FAZ-C10/1-NA-DC

Eaton Moeller series xEffect - FAZ-NA-DC MCB. FAZ-DC, 1-pole, tripping characteristic: C, rated current In: 10 A, Switchgear for export to North America (UL-listed)

Yleiset tiedot

Product Name
Eaton Moeller series xEffect - FAZ-NA-DC MCB
Catalog Number
113759
EAN
4015081132942
Product Length/Depth
105 mm
Product Height
75.5 mm
Product Width
17.7 mm
Product Weight
0.121 kg
Compliances
RoHS conform
Certifications
UL 489
UL 489, CSA C22.2 No. 5
IEC 60947-2
EN45545-2
IEC 61373
Catalog Notes
Positioned for medium inrush startup currents to provide protection for small transformers and pilot devices. Single packaging of single-pole curves B, C and D for select amperages only.

Additional information

Current limiting class
3
Features
Additional equipment possible
Functional group
Overcurrent protection
Functions
Overload protection
Short Circuit protection
Internal resistance at room temperature (single-pole, 50 Hz)
16 mΩ

Delivery program

Amperage Rating
10 A
Application
DC applications in industrial and commercial installations, utilities, OEM control panels, renewable energy systems, IT and data centre auxiliary circuits, railway and transportation systems, as well as branch and feeder circuit protection in UL-listed panels for North American installations.
Nominal current
10 A
Number of poles
Single-pole
Number of poles (protected)
1
Number of poles (total)
1
Release characteristic
C
Tripping characteristic
C
Type
  • !
  • !
  • FAZ-NA-DC
  • Miniature circuit breaker

Design verification as per IEC/EN 61439

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Design verification as per IEC/EN 61439 - technical data

Ambient operating temperature - max
55 °C
Ambient operating temperature - min
-25 °C
Rated operational current for specified heat dissipation (In)
10 A

Technical data - electrical

Direction of incoming supply
Polarity dependent
Overvoltage category
III
Pollution degree
2
Rated impulse withstand voltage (Uimp)
4 kV
Rated insulation voltage (Ui)
440 V
Rated operational voltage (Ue) - max
250 V
Rated service short-circuit breaking capacity (IEC/EN 60947-2) - Ics
7.5 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V
10 kA
Rated switching capacity (IEC/EN 60947-2)
10 kA
Selectivity class
3
Voltage type
DC

Technical data - mechanical

Built-in depth
65.5 mm
Connectable conductor cross section (multi-wired) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (solid-core) - min
1 mm²
Degree of protection
IP20
Mounting position
As required
Terminals (top and bottom)
Screw-type with pressure plate
Width in number of modular spacings
1

Vientituotteen tekniset tiedot

Serial Number Verified :
Authenticated: ✓
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Todenna tuote

Syötä 16–17 numeron sarjanumerosi
Antamasi sarjanumero ei saa sisältää erikoismerkkejä. Antamasi sarjanumero on virheellinen, sillä siinä pitäisi olla 16 tai 17 numeroa. Antamaasi sarjanumeroa ei löytynyt. Yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi. Antamasi sarjanumero ei vastaa tuotetta. Tarkista tuotteesi sarjanumero ja yritä uudelleen. Napsauta täältä jotta voit siirtyä antamasi sarjanumeron tuotesivulle Eatonin mukaan sarjanumero on epäilyttävä, yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi.
Sarjanumero
Nollaus Eatonin mukaan sarjanumero on epäilyttävä, yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi. Eaton ei tunnista sarjanumeroa, ja se on virheellinen. Käytä tätä lomaketta ilmoita tästä ongelmasta lisäavun saamiseksi.
Anna 6-numeroinen todennuskoodi
Antamasi tuote on epäilyttävä! Yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi. Antamasi todennuskoodi ei vastaa tämän sarjanumeron tietoja. Yritä uudelleen tai ilmoita tästä ongelmasta lisäavun saamiseksi. Virheellinen todennuskoodi. Pituuden on oltava 6 merkkiä ilmoita tästä ongelmasta lisäavun saamiseksi. Todennuskoodi vaaditaan ilmoita tästä ongelmasta lisäavun saamiseksi.
Suorita Captcha-vahvistus ennen todennusta.
x
Ilmoita ongelmasta
Anna koko nimesi.
x
Kiitos, ongelmasi on lähetetty. Tuotetiimimme ottaa sinuun pian yhteyttä.