Delivery program

Basic function
Arc fault circuit interrupter
Number of poles
Two-pole
Tripping characteristic
C
Application
Switchgear for residential and commercial applications
Rated current
13 A
Rated Switching Cap (IEC/EN 60898-1)
10 KA
Type
AFDD+
Tripping
Non-delayed
Busbar type
ZV-SS
Product range
AFDD
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.

Technical data - electrical

Types conform to
IEC/EN 62606
IEC/EN 61009
Current test marks
As per inscription
Rated Switching Cap (IEC/EN 60898-1)
10 KA
Test circuit AC
170 - 264 Voltage AC

Technical data - mechanical

Device height
80 MM
Built-in width
54 MM
Degree of protection
IP20
Terminals (top and bottom)
Twin-purpose
Terminal protection
Busbar tag shroud as per VBG4, ÖVE-EN 6
Thickness of busbar material
0.8 - 2 Square Millimeter
Permissible Storage and Trans Temp. Min
-35 C
Permissible Storage and Trans Temp. Max
60 C
Climatic proofing
IEC/EN 61009
Contact position indicator
red / green

Design verification as per IEC/EN 61439

Rated operational current for specified heat dissipation (In)
13 A
Operating ambient temperature - min
-25 C
Operating ambient temperature - max
40 C
Thickness of busbar material
0.8 - 2 Square Millimeter
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Product application
Switchgear for residential and commercial applications
Impulse withstand current
Partly surge-proof, 250 A
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Terminal protection
Busbar tag shroud as per VBG4, ÖVE-EN 6
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.

Technical data ETIM 7.0

Number of poles
Two-pole
Rated current
13 A
Leakage current type
A
Current limiting class
3
Rated Switching Cap (IEC/EN 60898-1)
10 KA
Frequency
50 HZ
Release characteristic
C
Pollution degree
2
Built-in depth
67 MM
Additional equipment attached at delivery
Fire protection switch
Rated switch current auxiliary device
0 A
Rated voltage auxiliary device
230 V
Control voltage type auxiliary equipment
AC