Select your location

Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.
Specifications

General specifications

Product Name
Eaton 9SX UPS
Catalog Number
9SX1000I
Product Length/Depth
160 MM
Product Height
252 MM
Product Width
387 MM
Product Weight
14.8 KG
Warranty
2 year
Compliances
CE Marked
TUV
cULus Listed
CSA 22.2
FCC part 15 Class B
CISPR22 Class B
Certifications
IEC/EN 62040-1
UL 1778
IEC/EN 62040-2
CE
cULus Listed
EAC

Product specifications

Secondary frequency - max
60 HZ
Output waveform
Sine wave
Max number of battery packs
4
Wattage
900 W
Output power factor
0.9
Form factor
Tower
Voltage distortion output (linear load) - max
3
Includes network card
No
Input connection
C14
Input voltage - min
120 V
Output voltage - max
240 V
Secondary frequency - min
50 HZ
Software compatibility
Eaton Intelligent Power Manager, Eaton Intelligent Power Protector
Battery replacement
Hot-swappable internal batteries and extended battery modules (EBMs)
Battery type
Sealed, lead-acid
Efficiency
89
Construction type
Free standing model
Output voltage - min
200 V
Color
Black
Output voltage range
200/208/220/230/240V +/- 2%
Extended battery capability
Yes
Topology
Online/Double-conversion
BTU Rating
Online: 375
Back-up time
6 min
Input nominal voltage
230V default (200/208/220/230/240/250V)
Input power factor
>.99
Input frequency range
40-70 Hz
Internal bypass
Yes
Input voltage - max
276 V
Voltage type
AC
Phase (output)
1
Battery management
ABM & Temperature compensated charging method (user selectable), Automatic battery test, deep discharge protection, automatic recognition of external battery units
Integrated functionality
Network Mangement
Auto shutdown function
Yes
Number of Outputs C13
6
VA rating
1000 VA
Potential free switch contact
Yes
Receptacle
(6) C13
Phase (input)
1
Package contents
9SX UPS
2 IEC output power cords
USB Cable
Serial Cable
Safety guide
Quickstart
Noise level
<41 dB at 1 meter
Feed type
1
Runtime graph
View runtime graph
User interface
Multilingual graphical LCD display
Battery quantity
3
Voltage
230V
Hot swap power
No
Temperature range
0° to 40°C (32° to 104°F)
Ethernet interface
No
Communication
1 USB port + 1 serial RS232 port + 1 mini-terminal block for remote power off + 1 mini-terminal block for output relay Communication slot
Relative humidity
0-96% non-condensing
Rack mounting kit
No
Efficiency (eco-mode)
94
Output frequency
50-60 Hz
Runtime at full load
6 min
Type of interface
Other
Primary frequency - min
40 HZ
Battery rating
12V/9Ah
Type
UPS
Output nominal voltage
230V default (200/208/220/230/240V)
Expansion slots
One slot for optional communication card
Input voltage range
190-276VAC without derating(up to 120-276VAC with derating)
Nominal frequency
50/60 Hz
Primary frequency - max
70 HZ
Altitude
3000 m
How to buy from Eaton