Ismeretek keresése
Dokumentum letöltése () 20
We make what matters work*

281235
PN1-160

Eaton Moeller series NZM - Molded Case Circuit Breaker. Switch-disconnector 3p, 160A, 1

Általános jellemzők

Product Name
Eaton Moeller series NZM switch-disconnector
Catalog Number
281235
EAN
4015082812355
Product Length/Depth
88 mm
Product Height
145 mm
Product Width
90 mm
Product Weight
0.886 kg
Compliances
RoHS conform
Certifications
IEC/EN 60947
IEC
Model Code
PN1-160

Kiegészítő információk

Functions
Interlockable
Disconnectors/main switches

Fő jellemzők

Amperage Rating
160 A
Application
Use in unearthed supply systems at 690 V
Circuit breaker frame type
PN1
Features
Version as emergency stop installation
Version as maintenance-/service switch
Version as main switch
Number of poles
Three-pole
Special features
  • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
  • Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
  • Busbar tag shroud to VDE 0160 Part 100.
  • Rated current = rated uninterrupted current: 160 A
Type
Switch-disconnector
Used with
Enclosure 100 x 800 x 800 mm

Konstrukció igazolás az IEC/EN 61439 szerint

10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.

Konstrukció igazolás az IEC/EN 61439 szerint

Ambient operating temperature - max
70 °C
Ambient storage temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - min
40 °C
Equipment heat dissipation, current-dependent
29.18 W
Rated operational current for specified heat dissipation (In)
160 A

Technical data - electrical

Amperage Rating
160 A
Direction of incoming supply
As required
Electrical connection type of main circuit
Frame clamp
Handle type
Rocker lever
Isolation
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts)
Lifespan, electrical
5000 operations at 690 V AC-1
7500 operations at 415 V AC-1
1000 operations at 400 V AC-23A
1000 operations at 415 V AC-23A
1000 operations at 690 V AC-23A
7500 operations at 400 V AC-1
Number of operations per hour - max
120
Overvoltage category
III
Pollution degree
3
Rated conditional short-circuit current with back-up fuse
100 kA at 400/415 V
160 gR
80 kA at 690 V
Rated conditional short-circuit current with downstream fuse
10 kA at 690 V
160 gR
100 kA at 400/415 V
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
6000 V
Rated insulation voltage (Ui)
690 V
Rated operating frequency
50 Hz
Rated operating power at AC-23, 400 V
90 kW
Rated operating voltage (Ue) at AC - max
690 V
Rated operational current
160 A (415 V AC-22/23A, making and breaking capacity)
160 A (690 V AC-22/23A, making and breaking capacity)
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
2.8 kA
Rated short-time withstand current (Icw)
2 kA
Rated short-time withstand current (t = 0.3 s)
2 kA
Rated short-time withstand current (t = 1 s)
2 kA
Short-circuit protective device fuses - max
160 A gL
Voltage rating
690 V - 690 V

Technical data - mechanical

Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Degree of protection
IP20 (basic protection type, in the area of the HMI devices)
Other
Degree of protection (IP), front side
IP20
IP66 (with door coupling rotary handle)
IP40 (with insulating surround)
Degree of protection (terminations)
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and band terminal)
Handle color
Black
Lifespan, mechanical
20000 operations
Mounting Method
Fixed
Built-in device fixed built-in technique
Distribution board installation
Ground mounting
Intermediate mounting
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Number of switches
1
Protection against direct contact
Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Special features
  • Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
  • Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
  • Busbar tag shroud to VDE 0160 Part 100.
  • Rated current = rated uninterrupted current: 160 A
Switch positions
I, 0

Technical data - mechanical - terminals

Optional terminals
Connection on rear. Screw terminal. Tunnel terminal
Standard terminals
Box terminal
Terminal capacity (aluminum solid conductor/cable)
10 mm² - 16 mm² (1x) direct at switch rear-side connection
10 mm² - 16 mm² (2x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
Terminal capacity (aluminum stranded conductor/cable)
25 mm² - 95 mm² (1x) at 1-hole tunnel terminal
Terminal capacity (copper busbar)
M6 at rear-side screw connection
Max. 16 mm x 5 mm direct at switch rear-side connection
Min. 12 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)
10 mm² - 16 mm² (1x) direct at switch rear-side connection
10 mm² - 16 mm² (1x) at box terminal
6 mm² - 16 mm² (2x) at box terminal
6 mm² - 16 mm² (2x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
Terminal capacity (copper stranded conductor/cable)
25 mm² - 70 mm² (1x) direct at switch rear-side connection
6 mm² - 25 mm² (2x) at box terminal
25 mm² - 95 mm² (1x) at 1-hole tunnel terminal
10 mm² - 70 mm² (1x) at box terminal
25 mm² (2x) direct at switch rear-side connection
Terminal capacity hint: Up to 95 mm² can be connected depending on the cable manufacturer
Terminal capacity (copper strip)
Max. 9 segments of 9 mm x 0.8 mm at box terminal
Min. 2 segments of 9 mm x 0.8 mm at box terminal

Termékjellemzők exportja

Megjegyzés: Ha fájl(ok) hiányoznak a letöltött .zip csomagból, akkor az illető fájltípus nem támogatott tömeges letöltés esetén
Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Termék hitelesítése

Adja meg 16-17 jegyű sorozatszámát.
A megadott sorozatszám nem tartalmazhat speciális karaktereket. A megadott sorozatszám nem helyes, 16 vagy 17 számjegyből kell állnia. A megadott sorozatszám nem található. Próbálja újra. jelentse ezt a problémát további segítségért. A megadott sorozatszám nem egyezik a termékkel. Ellenőrizze a termék sorozatszámát, és próbálja meg újra. Kattintson ide hogy eljusson a megadott sorozatszámú termék oldalára Az Eaton számára a sorozatszám gyanúsnak tűnik, kérjük, próbálkozzon újra, vagy jelentse ezt a problémát további segítségért.
Gyártási szám
Visszaállítás Az Eaton számára a sorozatszám gyanúsnak tűnik, kérjük, próbálkozzon újra, vagy jelentse ezt a problémát további segítségért. A sorozatszám ismeretlen, ezért érvénytelen. Kérjük, használja ezt az űrlapot a következő célokra: jelentse ezt a problémát további segítségért.
Írja be a 6 számjegyű azonosítási kódot
A megadott termék gyanús! Próbálja újra. jelentse ezt a problémát további segítségért. A megadott hitelesítési kód nem egyezik a sorozatszámra vonatkozó adatainkkal. Próbálja újra. jelentse ezt a problémát további segítségért. Érvénytelen hitelesítési kód. A kódnak 6 karakter hosszúnak kell lennie. jelentse ezt a problémát további segítségért. Hitelesítési kód szükséges jelentse ezt a problémát további segítségért.
A hitelesítés előtt teljesítse a Captcha feladatot.
Elérhetőségek a probléma bejelentéséhez
x
Incidens jelentése
Kérjük, adja meg a teljes nevét.
x
Köszönjük, problémája bekerült a rendszerbe, termékcsapatunk hamarosan felveszi Önnel a kapcsolatot.