KnowledgeSearch
Unduh Dokumen () / 20
Kami membantu memastikan kebutuhan vital yang diperlukan oleh semua orang terpenuhi*

192543
Model code: NZMN4-AX1000-NA

Eaton Moeller series NZMN4 PXR10 circuit breaker, 1000 A, 3-pole, Screw terminal, UL/CSA

Spesifikasi umum

Product Name
Eaton Moeller series NZM molded case circuit breaker electronic
Catalog Number
192543
Model Code
NZMN4-AX1000-NA
EAN
4015081932719
Product Length/Depth
401 mm
Product Height
207 mm
Product Width
210 mm
Product Weight
21 kg
Compliances
RoHS conform
Certifications
Specially designed for North America
IEC 60947-2
UL 489
CSA (File No. 22086)
UL listed
UL (File No. E31593)
UL/CSA
CSA (Class No. 1432-01)
CE marking
CSA-C22.2 No. 5-09
CSA certified
IEC
UL (Category Control Number DIVQ)

Data teknis - elektrik

Voltage rating
690 V - 690 V
Rated operating voltage Ue (UL) - max
600 V
Rated operational current
1000 A (690 V AC -1, making and breaking capacity)
1000 A (660-690 V AC-3, making and breaking capacity)
Amperage Rating
1000 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
12 A
Overload current setting (Ir) - min
400 A
Overload current setting (Ir) - max
1000 A
Short-circuit release non-delayed setting - min
2000 A
Short-circuit release non-delayed setting - max
12000 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever

Data teknis - komunikasi

Rated operational current
1000 A (690 V AC -1, making and breaking capacity)
1000 A (660-690 V AC-3, making and breaking capacity)
Amperage Rating
1000 A
Instantaneous current setting (Ii) - min
2 A
Instantaneous current setting (Ii) - max
12 A
Overload current setting (Ir) - min
400 A
Overload current setting (Ir) - max
1000 A
Short-circuit release non-delayed setting - min
2000 A
Short-circuit release non-delayed setting - max
12000 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
Electrical connection type of main circuit
Screw connection
Handle type
Rocker lever

Data teknis - mekanis

Mounting Method
Built-in device fixed built-in technique
Fixed
Degree of protection
IP20
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Front side

dataSheetsExport