지식 검색
문서 다운로드 () / 20
당신의 필요한 일, 이튼이 합니다*

104480
DILMF115(RAC120)

Eaton Moeller® series DILMF Contactors for Semiconductor Industries acc. to SEMI F47, 380 V 400 V: 115 A, RAC 120: 100 - 120 V 50/60 Hz, Screw terminals

일반 규범

Product Name
Eaton Moeller® series DILMF contactor for semiconductor industries
Catalog Number
104480
Model Code
DILMF115(RAC120)
EAN
4015081042975
Product Length/Depth
160 mm
Product Height
170 mm
Product Width
90 mm
Product Weight
2.26 kg
Certifications
CSA Class No.: 2411-03, 3211-04
IEC/EN 60947-4-1
CSA-C22.2 No. 60947-4-1-14
CSA
UL Category Control No.: NLDX
UL
CSA File No.: 012528
UL 60947-4-1
UL File No.: E29096
CE
Catalog Notes
Also tested according to AC-3e.

정격 작동 전류

Fitted with:
Built-in suppressor circuit
Number of poles
Three-pole

정격 작동 전력

Application
Contactors for Semiconductor Industries acc. to SEMI F47
Overvoltage category
III
Pollution degree
3
Product category
Contactors
Resistance per pole
0.56 mΩ
Suitable for
Also motors with efficiency class IE3
SEMI F47, Magnet systems
Utilization category
AC-3: Normal AC induction motors: starting, switch off during running
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Voltage type
AC

정격 작동 전압

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient operating temperature (enclosed) - min
-25 °C
Ambient operating temperature (enclosed) - max
40 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
80 °C

할당된 모터 전력

Emitted interference
According to EN 60947-1
Interference immunity
According to EN 60947-1

전자기 호환성(EMC)

Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V
130 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V
115 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
115 A
Rated operational current (Ie) at AC-3, 440 V
115 A
Rated operational current (Ie) at AC-3, 500 V
115 A
Rated operational current (Ie) at AC-3, 660 V, 690 V
93 A
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V
55 A
Rated operational current (Ie) at AC-4, 400 V
55 A
Rated operational current (Ie) at AC-4, 500 V
55 A
Rated operational current (Ie) at AC-4, 660 V, 690 V
45 A

제품 사양 내보내기