Arc fault protection system ARCON®
Serial Number Verified :
Authenticated:
The product is verified as being authentic; however, this does not guarantee the condition or fit for purpose of the product.

Arc fault protection system ARCON®

Arc faults still occur in electrical energy distribution systems – regardless of all the preliminary protective measures. Suitable measures must be taken to prevent the extremely serious effects and the damage caused by these events, for example the arc-fault protection system ARCON®.   

Arc fault protection system ARCON®
Rated short-time withstand current
Icw up to 150 kA/200 ms
arc mitigation time
≤ 2 ms
system integration compliant with
IEC/TR 61641:2014 Ed.3

Core features

  • ARCON® is used for LV switchgear assemblies up to 690 VAC/50 Hz
  • System arc mitigation time ≤ 2 ms
  • At lowest treshold ARCON® protects under arcing conditions at pick-up level of Ipc arc = 7.5 kA (Ipc arc max. = 100 kA)
  • Rated short-time withstand current Icw of the quenching device (at operating voltage of 415 VAC):
    - 85 kA / 1 s
    - 105 kA / 500 ms
    - 150 kA / 200 ms
  • Integrated self-monitoring function of the entire system to prevent any unexpected downtime
  • Low voltage switchgear and control gear assembly xEnergy Main/PowerXpert CX with integrated ARCON® meets criteria 1-7 acc. to IEC/TR 61641:2014 Ed.
  • Full personnel protection even with open doors e.g. during maintenance activities

 

Work Safe - Safe Solutions far beyond IEC standards

Available in Eaton's low voltage distribution systems up to 6300 A for commercial and industrial buildings, protecting personal and equipment.

ARCON® is still the fastest available arc-fault mitigation system on the market.

Eaton, Power Management Company

Electrical safety

Understanding the risk of arc-flash events in your switchgear assemblies is the first step towards protecting your people and your business. Find out how you can protect your staff, business and reputation from the risk of an arc flash.

Enhanced personnel protection

The ARCON® arc fault protection system is always used when enhanced personal protection is required that is over and above the requirements of the relevant standards.

ARCON® also protects your system

Low-voltage switchboard systems are put out of operation for several weeks due to the effects of an arc fault. If a redundant power supply is not available, this also results in unwanted production downtimes. Only an effective system protection can provide a solution here, so that the effects of the arc fault can be minimized and an immediate restoration of service is possible. Using ARCON® restricts the effects of the arc fault to its footpoints. After the cause of the fault has been rectified and the quenching device has been exchanged, the system can be made ready for operation in the shortest possible time in order to ensure the required availability.

The effects of arc faults are extremely serious

The effects of arc faults are extremely serious and range from injury to persons to massive damage to the switchgear systems and can result in standstills, which can last for weeks and may even necessitate a complete replacement of the switchgear system. Our research results indicate that the risk of injury to persons has been decisively reduced by the application of ARCON®.

Most common causes of an arc fault are:

  • Human error when working on the switchgear system
  • Bridging between conductor with conductive foreign bodies such as tools, parts or rodents
  • Dirt or condensation
  • Overvoltages
  • Incorrectly dimensioned switching devices