Ladda ner dokument () av 20

259591
Modellkod: NZM2/3-XUHIV208-240AC

Eaton Moeller series NZM Undervoltage release, 208-240VAC, +2early N/O, for NZM2/3, with 2 VHI

General specifications

Product Name
Eaton Moeller series NZM Undervoltage release
Catalog Number
259591
EL Number
3186291
EAN
4015082595913
Product Length/Depth
42 mm
Product Height
90 mm
Product Width
30 mm
Product Weight
0.101 kg
Compliances
UL/CSA
IEC
RoHS conform
Certifications
CSA (File No. 22086)
CSA (Class No. 1437-01)
CSA certified
UL489
CSA-C22.2 No. 5-09
UL (File No. E140305)
UL (Category Control Number DIHS)
IEC60947
UL listed
CE marking
Model Code
NZM2/3-XUHIV208-240AC

Tekniska data – elektriska

Type
  • Accessory
  • Undervoltage release with early-make auxiliary contact
Connection
Screw
Special features
  • Undervoltage release with 2 early-make auxiliary contacts, e.g., for early-make connection of undervoltage release in main switch applications, as well as for interlock and load shedding circuits.
  • For use with emergency-stop devices in connection with an emergency-stop button.
  • When the under-voltage trip is switched off, accidental contact with the circuit breaker’s primary contacts is prevented when switched on.
  • Early make of auxiliary contacts on switching on and off (manual operation): approx. 20 ms
  • Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
  • Cannot be used in conjunction with NZM...-XR... remote operator.
Frame
NZM2/3
Fitted with:
Two early-make auxiliary contacts
Suitable for
Off-load switch
Used with
NZM3(-4), N(S)3(-4)
NZM2(-4), N(S)2(-4)

Tekniska data – elektriska

Rated control supply voltage
208 - 240 V 50/60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - min
208 V
Rated control supply voltage (Us) at AC, 50 Hz - max
240 V
Rated control supply voltage (Us) at AC, 60 Hz - min
208 V
Rated control supply voltage (Us) at AC, 60 Hz - max
240 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Voltage tolerance - min
0.85
Voltage tolerance - max
1.1
Drop-out voltage of undervoltage release AC/DC - min
0.35 x Us
Drop-out voltage of undervoltage release AC/DC - max
0.7 x Us
Power consumption
0.8 W (sealing DC)
1.5 VA (sealing AC)
Pick-up power consumption at AC (undervoltage release)
1.5 VA
Pick-up power consumption at DC (undervoltage release)
0.8 W
Reaction time
19 ms
Minimum command time - min
10 ms
Minimum command time - max
15 ms
Electric connection type
Screw connection

Tekniska data – kommunikation

Voltage type
AC
Rated control voltage (relay contacts)
240 V AC
208 V AC
Rated control supply voltage
208 - 240 V 50/60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - min
208 V
Rated control supply voltage (Us) at AC, 50 Hz - max
240 V
Rated control supply voltage (Us) at AC, 60 Hz - min
208 V
Rated control supply voltage (Us) at AC, 60 Hz - max
240 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Voltage tolerance - min
0.85
Voltage tolerance - max
1.1
Drop-out voltage of undervoltage release AC/DC - min
0.35 x Us
Drop-out voltage of undervoltage release AC/DC - max
0.7 x Us
Power consumption
0.8 W (sealing DC)
1.5 VA (sealing AC)
Pick-up power consumption at AC (undervoltage release)
1.5 VA
Pick-up power consumption at DC (undervoltage release)
0.8 W
Reaction time
19 ms
Minimum command time - min
10 ms
Minimum command time - max
15 ms
Electric connection type
Screw connection

Tekniska data – mekaniska

Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
2
Connection type
With bolt connection

Exportera produktspecifikationer