Eaton DA1 Variable frequency drive, 500 V AC, 3-phase, 65 A, 45 kW, IP55/NEMA 12, OLED display, DC link choke
Product Name |
Eaton DA1 Variable frequency drive
|
Catalog Number |
176970
|
Product Length/Depth |
270 mm
|
Product Height |
540 mm
|
Product Width |
235 mm
|
Product Weight |
22.5 kg
|
Certifications |
Certified by UL for use in Canada
IEC/EN61800-5 RoHS, ISO 9001 UL CE CSA-C22.2 No. 14 Specification for general requirements: IEC/EN 61800-2 EAC UL 508C DNV Safety: EN 61800-5-1: 2003 UkrSEPRO UL Category Control No.: NMMS, NMMS7 RCM UL report applies to both US and Canada IEC/EN61800-3 CUL UL File No.: E172143 IEC/EN 61800-3 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Cable length |
150 m, unscreened, maximum permissible, Motor feeder
100 m, screened, maximum permissible, Motor feeder 300 m, unscreened, with motor choke, maximum permissible, Motor feeder 200 m, screened, with motor choke, maximum permissible, Motor feeder |
Communication interface |
SmartWire-DT, optional
EtherCAT, optional CANopen®, built in DeviceNet, optional PROFIBUS, optional Modbus RTU, built in Ethernet IP, optional PROFINET, optional OP-Bus (RS485), built in Modbus-TCP, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DX-NET-SWD1 SmartWire DT module |
Degree of protection |
NEMA 12
IP55 |
Fitted with: |
OLED display
Additional PCB protection Internal DC link Brake chopper IGBT inverter DC link choke PC connection Breaking resistance Control unit |
Frame size |
FS5
|
Functions |
4-quadrant operation possible
|
Mounting position |
Vertical
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
EtherNet/IP
CAN PROFIBUS MODBUS PROFINET IO Other bus systems DeviceNet TCP/IP |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Suitable for |
Branch circuits, (UL/CSA)
|
Ambient operating temperature - min |
-10 °C
|
Altitude |
Max. 4000 m
Max. 1000 m Above 1000 m with 1 % derating per 100 m |
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
97 % (η)
|
Input current ILN at 150% overload |
70.4 A
|
Leakage current at ground IPE - max |
65 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
500 V
|
Mains voltage - max |
600 V
|
Operating mode |
Optional: Vector control with feedback (CLV)
U/f control Speed control with slip compensation Sensorless vector control (SLV) |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
500 V AC, 3-phase
600 V AC, 3-phase |
Overload current IL at 150% overload |
97.5 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) at 150% overload |
65 A
|
Rated operational power at 500 V, 50 Hz, 3-phase |
45 kW
|
Rated operational power at 525 V, 50 Hz, 3-phase |
45 kW
|
Rated operational voltage |
500 V AC, 3-phase
600 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection |
LPJ fuse used together with JM60100-3 fuse base, Power wiring, Assigned switching and protective elements
NH fuse used together with TB00-D fuse base, Power wiring, Assigned switching and protective elements |
Short-circuit protection rating |
100 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), for 4 seconds every 40 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
600 VAC
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
65 A
|
Assigned motor current IM at 525 V, 50 Hz, 150% overload |
62 A
|
Assigned motor current IM at 550 - 600 V, 60 Hz, 150% overload |
62 A
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
60 HP
|
Apparent power at 600 V |
67.55 kVA
|
Braking resistance |
12 Ω
|
Braking torque |
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie, variable, DC - Main circuit |
Switch-on threshold for the braking transistor |
975 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
5
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
2
|
Number of relay outputs |
2 (parameterizable, 1 N/O and 1 changeover contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA)
|
Equipment heat dissipation, current-dependent Pvid |
1350 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
65 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Heat dissipation details |
Operation (with 150 % overload)
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|