Reset
Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 33A, B1-S33-CNA
| Product Name |
Eaton Moeller series NZM molded case circuit breaker magnetic
|
| Catalog Number |
103024
|
| Product Length/Depth |
88 mm
|
| Product Height |
165.5 mm
|
| Product Width |
90 mm
|
| Product Weight |
1.046 kg
|
| Compliances |
RoHS conform
|
| Certifications |
CSA-C22.2 No. 5-09
UL/CSA UL (Category Control Number DKPU2) CSA certified UL listed UL 489 CSA (Class No. 1432-01) Specially designed for North America CSA (File No. 22086) UL (File No. E31593) |
| Voltage rating |
440 V - 440 V
|
| Rated operating voltage Ue (UL) - max |
480 Y / 277 V
|
| Rated insulation voltage (Ui) |
690 V
|
| Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
| Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
| Amperage Rating |
33 A
|
| Instantaneous current setting (Ii) - min |
264 A
|
| Instantaneous current setting (Ii) - max |
462 A
|
| Overload current setting (Ir) - min |
0 A
|
| Overload current setting (Ir) - max |
0 A
|
| Short-circuit release non-delayed setting - min |
264 A
|
| Short-circuit release non-delayed setting - max |
462 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
25 kA
|
| Rated operating power at AC-3, 230 V |
7.5 kW
|
| Rated operating power at AC-3, 400 V |
15 kW
|
| Short-circuit total breaktime |
< 10 ms
|
| Electrical connection type of main circuit |
Other
|
| Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
| Number of operations per hour - max |
120
|
| Handle type |
Rocker lever
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Lifespan, electrical |
7500 operations at 415 V AC-3
|
| Direction of incoming supply |
As required
|
| Rated impulse withstand voltage (Uimp) at auxiliary contacts |
6000 V
|
| Rated impulse withstand voltage (Uimp) at main contacts |
6000 V
|
| Amperage Rating |
33 A
|
| Instantaneous current setting (Ii) - min |
264 A
|
| Instantaneous current setting (Ii) - max |
462 A
|
| Overload current setting (Ir) - min |
0 A
|
| Overload current setting (Ir) - max |
0 A
|
| Short-circuit release non-delayed setting - min |
264 A
|
| Short-circuit release non-delayed setting - max |
462 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
25 kA
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz |
25 kA
|
| Rated operating power at AC-3, 230 V |
7.5 kW
|
| Rated operating power at AC-3, 400 V |
15 kW
|
| Short-circuit total breaktime |
< 10 ms
|
| Electrical connection type of main circuit |
Other
|
| Isolation |
300 V AC (between the auxiliary contacts)
500 V AC (between auxiliary contacts and main contacts) |
| Number of operations per hour - max |
120
|
| Handle type |
Rocker lever
|
| Overvoltage category |
III
|
| Pollution degree |
3
|
| Lifespan, electrical |
7500 operations at 415 V AC-3
|
| Direction of incoming supply |
As required
|
| Mounting Method |
Built-in device fixed built-in technique
Fixed |
| Degree of protection |
IP20
IP20 (basic degree of protection, in the operating controls area) |
| Degree of protection (IP), front side |
IP66 (with door coupling rotary handle)
IP40 (with insulating surround) |
| Degree of protection (terminations) |
IP10 (tunnel terminal)
IP00 (terminations, phase isolator and strip terminal) |
| Protection against direct contact |
Finger and back-of-hand proof to VDE 0106 part 100
|
| Shock resistance |
20 g (half-sinusoidal shock 20 ms)
|
| Switch off technique |
Magnetic
|
| Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
| Lifespan, mechanical |
20000 operations
|