The Eaton Power Distribution Rack (PDR) is designed for the evolving realities of data centers, where floor space is costly, change is inevitable and uptime is non-negotiable. A key component of any power quality system, this flexible, high density rack offers a space saving design and optional branch circuit monitoring.
Explore replacement products:
Direct connection to panelboard breakers (225A or 400A)
Single or dual 800A lugs
Single or dual 400A and 600A main breakers
Dual 600A main breakers with dual source tie breaker (main-tie-main configuration)
225A or 400A column panelboards
Front: 2 panelboards
Rear: 2 panelboards
Up to 168 pole positions
Factory-installed breakers
208Y/120 Vac
50/60Hz (45-60Hz)
Three wire + neutral + ground
Direct connection to panelboard main breakers (225A, 400A)
Connection into single or dual main lugs (800A)
Connection into single or dual main breakers (400A, 600A)-side access required
Optional Power Xpert Gateway 1000 communications card
Built-in Web and SMTP server
Support for Modbus TCP, SNMP and NTP protocols
Two (2) isolated RJ-45 Ethernet ports for redundancy
Standard system-level monitoring
Non-volatile real-time clock
Power Xpert Gateway 1000 card firmware is user-upgradeable
Input 1 V12 min/max
Input 1 V23 min/max
Input 1 V31 min/max
Input 1 ACUV total time
Input 1 I1 min/max (with optional Main CTs installed)
Input 1 I2 min/max (with optional Main CTs installed)
Input 1 I3 min/max (with optional Main CTs installed)
Input 1 V12 THD max
Input 1 V23 THD max
Input 1 V31 THD max
Input 1 frequency min/max
Input 1 kVA min/max (with optional Main CTs installed)
Input 1 power factor min/max (with optional Main CTs installed)
Input 2 V12 min/max
Input 2 V23 min/max
Input 2 V31 min/max
Input 2 AVUC total time
Input 2 I1 min/max (with optional Main CTs installed)
Input 2 I2 min/max (with optional Main CTs installed)
Input 2 I3 min/max (with optional Main CTs installed)
Input 2 V12 THD max
Input 2 V23 THD max
Input 2 V31 THD max
Input 2 frequency min/max
Input 2 kVA min/max (with optional Main CTs installed)
Input 2 power factor min/max (with optional Main CTs installed)
GND | min/max
NEU | min/max
Input 1 AC over voltage
Input 1 AC under voltage
Input 1 under or over frequency
Input 2 AC over voltage
Input 2 AC under voltage
Input 2 under or over frequency
Building alarm 1
Building alarm 2
Building alarm 3
Building alarm 4
Input 1 overload (4 levels per phase, with optional Main CTs installed)
Input 2 overload (4 levels per phase, with optional Main CTs installed)
Input 1 phase rotation error
Input 2 phase rotation error
Configuration error
Alarm, high input 1 THD (per-phase alarm), current or voltage
Alarm, high input 2 THD (per-phase alarm), current or voltage
Alarm, neutral overload warning (per panel)
Neutral overload (per panel)
Ground current warning (per panel)
Ground current overload (per panel)
Panel number
Panel name
Nominal input voltage
Nominal input frequency
System kVA
CTs present
L-L or L-N input setting
Main CT ratios
Calibration of input, output, ground and neutral CTs
Calbration of voltage
Breaker rating
Breaker warning level
Breaker type
RMS: V1, V2, V3, I1, I2, I3
Average: Vavg, kW, kVA, PF
Load: monthly kWh, yearly kWh, total kWh
Percentage: Input 1, Input 2, Input 3, Input total (percent load)
Max: Vmax, Imax
Panel or subfeed breaker overload warning
Panel or subfeed breaker overload alarm
Panel breaker overload warning
Panel breaker overload alarm
Breaker current warning
Breaker current overload
Breaker rating
Breaker warning level
Breaker overload level
Breaker type
Current: RMS and percentage
Average: kW, kVA, PF
Load: monthly kWh, yearly kWh, total kWh
Max: amperage, kW
Min: power factor
Breaker current warning
Breaker current overload
42-circuit column - rated for 225A - maximum two (2) per side
42-circuit column - rated for 400A - maximum two (2) per side
Transient voltage surge suppressor (TVSS) 50 kA/ph or 100 kA/ph
Isolated ground
Branch circuit monitoring
Plexiglas or mesh doors
0°C to 40°C (32°F to 104°F)
5-95% non-condensing
<45 dBA measured at 1.5m (5 ft) from unit under normal operating conditions
FCC 47, part 15 for Class A devices
Domestic/Canadian models: UL/CSA 60950-1
80.3x23.6x41.3
(2041x600x1050)
One side: 450 (200)
Two sides: 700 (315)