UPS rating (0.91 power factor) |
|
kVA |
225, 275, 450, 500, 550, 650, 750, 825, 1000, 1100 |
kW |
202, 250, 405, 450, 500, 585, 675, 750, 900, 1000 |
|
|
General characteristics |
|
Efficiency |
>94% (99% with ESS) |
Parallel capability |
4 distributed, 32 with SBM |
Max modules per size |
Up to 3 modules, 550 kVA, up to 4 modules, 825/1100 kVA |
Audible noise |
<76dBA @ 1 meter |
Altitude (max) |
2000m at 40ºC (104ºF) |
N+1 redundancy capable |
Yes |
Field upgradeable |
Yes |
System bypass module |
Included |
Control panel (LCD) |
Color touchscreen with LED panel |
Battery startup |
Standard |
Frequency conversion |
Standard |
Multi-language |
Standard |
Building alarm inputs |
5 (galvanic isolated) |
|
|
Input characteristics |
|
Voltage |
480V standard; and 400V available |
Voltage range |
+10% / -15% |
Frequency range |
45-65 Hz |
Power factor |
0.99 (minimum) |
Input current distortion |
<3.5% (no input filter required) |
Soft start capability |
Yes |
Internal backfeed protection |
Yes |
|
|
Output characteristics |
|
Voltage |
480V standard; and 400V available |
Regulation |
±1% |
Inverter |
PWM with IGBT switching |
Voltage |
THD <2% (100% linear load); <5% (non-linear load) |
Load power factor range |
Up to a .9 power factor leading without derating |
|
|
Battery |
|
Battery types |
VRLA, AGM, wet cell |
Battery voltage |
480V |
Temperature compensation |
Optional |
Charging method |
ABM technology or float, selectable |
|
|
Dimensions and weights |
|
225 kVA, 275 kVA
|
52.4”w x 32.7”d x 73.6”h (1786 lb) |
225 kVA redundant, 275 kVA redundant |
73.7”w x 32.7”d x 73.6”h (2875 lb)
|
450, 500, 550 kVA |
73.7”w x 32.7”d x 73.6”h (2977 lb) |
450, 550 kVA redundant |
103”w x 32.7”d x 73.6”h (4153 lb) |
Field upgrade module, 225 or 275 kVA |
30”w x 32.7”d x 73.6”h (1176 lb) |
650, 750, 825 kVA |
140.9"w x 32.7"d x 73.7"h (5065 lb) |
650, 750, 825 kVA +1 redundant |
170.2"w x 32.7"d x 73.7"h (6365 lb) |
1000, 1100 kVA |
170.2"w x 32.7"d x 73.7"h (6525 lb) |
|
|
Certifications |
|
Safety |
UL1778, cUL |
EMC |
IEC 62040-2, EN50091 Class A (restricted access) |
|
|
Options |
- External maintenance bypass
- PDU, RPP and STS
- Maintenance bypass module, matching cabinet, 2/3/4 breaker
- DC disconnects
- 65 or 100 kAIC input breakers
|
|
|
Communication cards |
Four communication bays standard. The following connectivity options can be installed at any time:
|
|
Remote inputs/outputs: Five building alarm inputs and one summary alarm contact (5A @ 120V) standard
Remote monitor panel: Eight backlit status indicator lamps plus an audible horn
|
|
|
Software compatibility |
Eaton Intelligence Platform:
- Automate: Make tasks simpler via advanced alerts and automated resolution
- Monitor: Make data actionable through faster, scalable interpretation and analysis
- Visualize: See beyond power consumption through 3D infrastructure visualizations
- Predict: foresee power component failure with cloud-based analytics
|