Eaton ESR5 Safety relays for emergency stop/protective door/light curtain monitoring, 24VDC, off-delayed, 0-300 sec.
Product Name |
Eaton ESR5 Safety relay
|
Catalog Number |
171858
|
Model Code |
ESR5-NV3-300
|
EAN |
4015081684298
|
Product Length/Depth |
114.5 mm
|
Product Height |
99 mm
|
Product Width |
45 mm
|
Product Weight |
0.472 kg
|
Certifications |
2014/30/EU
CE CSA-C22.2 No. 14-95 UL File No.: E29184 UL report applies to both US and Canada EN 50178 EN ISO 13849-1 IEC 62061 UL UL Category Control No.: NKCR; NKCR7 CSA Class No.: 3211-83; 3211-03 IEC 61508, Parts 1-7 IEC/EN 60204 Certified by UL for use in Canada UL 508 Machines 2006/42/EG |
Global Catalog |
171858
|
Type |
|
Mounting method |
Rail mounting possible
Top-hat rail fixing (according to IEC/EN 60715, 35 mm) |
Operating temperature - max |
55 °C
|
Operating temperature - min |
-20 °C
|
Features |
Safe insulation
3 Non-delayed enable current paths Monitored reset Automatic start 6 kV between the enable current paths (13/14, 23/24, 33/34) and the remaining rungs, as well as between 13/14, 23/24, 33/34 in relation to each other Manual start Reinforced insulation Basic insulation |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Electric connection type |
Screw connection
|
Fitted with: |
Feedback circuit
Start input Approval according to UL Detachable clamps Approval for TÜV |
Pollution degree |
2
|
Climatic proofing |
Cold to EN 60068-2-1
Dry heat to IEC 60068-2-2 Damp heat, constant, to IEC 60068-2-3 |
Rated impulse withstand voltage (Uimp) |
4000 V AC
|
Air pressure |
795 - 1080 hPa (operation)
|
Altitude |
Max. 2000 m
|
Category (EN 954-1) |
4
|
Degree of protection |
Installation location: ≥ IP54
Enclosure: IP20 Terminals: IP20 IP20 |
Environmental conditions |
Clearance in air and creepage distances according to EN 50178, UL 508, CSA C22.2, No. 14-95
Condensation: Non-condensing |
Number of inputs |
One- and two-channel
|
Functions |
1-channel
2-channel |
Safety performance level (EN ISO 13849-1) |
Level e
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-20 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Number of outputs (safety related, delayed) with contact |
2
|
Number of outputs (safety related, delayed, semiconductors) |
0
|
Number of outputs (safety related, undelayed) with contact |
3
|
Number of outputs (safety related, undelayed, semiconductors) |
0
|
Number of outputs (signaling function, delayed) with contact |
0
|
Number of outputs (signaling function, delayed, semiconductors) |
0
|
Number of outputs (signaling function, undelayed) with contact |
1
|
Number of outputs (signaling function, undelayed, semiconductors) |
0
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
26.4 V
|
Screwdriver size |
2, Terminal screw, Pozidriv screwdriver
0.6 x 3.5 mm, Terminal screws |
Voltage type |
DC
|
Connection type |
M3 screw terminals
|
Mounting position |
As required
|
Breaking power |
33 W max., inductive load (τ = 40 ms), at 220 V DC
1500 VA, max., resistive load (τ = 0 ms), at 250 V AC 144 W max., resistive load (τ = 0 ms), at 24 V DC 288 W max., resistive load (τ = 0 ms), at 48 V DC 40 W max., inductive load (τ = 40 ms), at 48 V DC 35 W max., inductive load (τ = 40 ms), at 110 V DC 42 W max., inductive load (τ = 40 ms), at 24 V DC 88 W max., resistive load (τ = 0 ms), at 220 V DC 77 W max., resistive load (τ = 0 ms), at 110 V DC |
Overvoltage category |
III
|
Short-circuit protection rating |
6 A (non-delayed), Output fuse, Output data
10A gL/gG, NEOZED (delayed), Output fuse, External, Output data |
Off-delay |
0.2 - 300 s (± 40 %, K3, K4 adjustable)
|
Emitted interference |
According to EN 61000-6-4
|
Current consumption |
155 mA, DC
|
Interference immunity |
According to EN 61000-6-2
|
Tightening torque |
0.6 Nm, Screw terminals
|
Mounting width |
45 mm
|
Suitable for |
Monitoring of emergency-stop circuits
Module used to safely interrupt electrical circuits Monitoring of position switches Safety relay for monitoring emergency stop and protective door switch |
Relative humidity |
< 75 %
|
LED indicator |
Status indication of SmartWire-DT network: Green LED
|
Pick-up time |
600 ms typ. (at Uₑ in automatic mode)
70 ms typ. (at Uₑ in manual mode) 600 ms typ. (K1, K2 - for UN automatic mode) 70 ms typ. (K1, K2 - for UN manual operation) |
Lifespan, mechanical |
10,000,000 Operations
|
Input |
∞ ms, Simultaneity for inputs 1/2
|
Recovery time |
1000 ms
|
Inrush current |
0.025 - 6 A
|
Model |
Basic device
|
Safety type (IEC 61496-1) |
None
|
Vibration resistance |
10 - 150 Hz, Amplitude: 0.15 mm, Acceleration: 2 g, (IEC/EN 60068-2-6)
|
Safety parameter (EN ISO 13849-1) |
PL e, Performance level
Cat. 4, Category 300,000 switching cycles, B10d |
Terminal capacity |
1 x (0.2 – 2.5) mm², solid
2 x (0.2 – 1) mm², solid 2 x (0.25 – 1) mm², flexible with ferrule 1 x (0.25 – 2.5) mm², flexible with ferrule 24 - 12 AWG, solid or stranded |
Rated control supply voltage (Us) at AC, 60 Hz - min |
20.4 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Rated insulation voltage (Ui) |
250 V
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Release-delay - max |
300 s
|
Release-delay - min |
0.2 s
|
Static heat dissipation, non-current-dependent Pvs |
5.43 W
|
Stripping length (main cable) |
7 mm
|
Switching voltage |
250 V
|
Product category |
Electronic safety relays
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
SIL (IEC 61508) |
3
|
Permissible total cable resistance |
22 Ω (input and starting circuits for UN)
|
Power loss |
Normally 5.43 W
|
Prooftest |
240 Months (High Demand)
19 Months (Low Demand) |
Quadratic summation current |
55 A² (ITH² = I1² + I2² + I3² + I4² + I5²)
|
Rated operational voltage |
Approx. 24 V DC at input, starting and feedback circuit
230 V AC 24 V DC (power supply) |
Reset time |
20 ms (non-delayed contacts)
|
Safety parameter (IEC 62061) |
SILCL 3, Safety integrity level claim limit
3.6 x 10-10, PFHd, Probability of failure per hour Off-delay contacts, SILCL 2 as per IEC 62061 SIL 3, Safety integrity level, In accordance with IEC 61508 Cat. 4, Category Non-time-delay contacts, SILCL 3 as per IEC 62061 and SIL 3 as per IEC 61508 |
Uninterrupted current |
6 A N/C, Limiting continuous current
6 A N/O, Limiting continuous current |
Short-circuit protection |
Non-time-delay 6-A fast-blow fuse, For output circuits, External
Time-delay 10-A gL/gG Neozed fuse, For output circuits, External |
Stop category (IEC 60204) |
0 + 1
|
Switching capacity |
3 A at 3600 O/h, AC-15 at 230 V, Outputs
2.5 A at 3600 O/h, DC-13 at 24 V, Outputs 0.4 W In accordance with IEC 60947-5-1, Outputs 4 A at 360 O/h, AC-15 at 230 V, Outputs |
Switching frequency |
Max. 0.5 Hz, Input data
|
Power consumption |
5.43 W
|
Control voltage 1 - min |
24 V
|
Control voltage 1 - max |
24 V
|
Control voltage 2 - min |
24 V
|
Control voltage 2 - max |
24 V
|
Control voltage 1 type |
DC
|
Control voltage 2 type |
AC
|
Voltage type of supply voltage |
DC
|
Voltage type of operating voltage |
DC
|
Rated switch current |
4 A
|
Supply voltage at AC, 50 Hz - min |
0 V
|
Supply voltage at AC, 50 Hz - max |
0 V
|
Supply voltage at AC, 60 Hz - min |
0 V
|
Supply voltage at AC, 60 Hz - max |
0 V
|
Supply voltage at DC - min |
24 V
|
Supply voltage at DC - max |
24 V
|
Operating voltage at AC, 50 Hz - min |
0 V
|
Operating voltage at AC, 50 Hz - max |
0 V
|
Operating voltage at AC, 60 Hz - min |
0 V
|
Operating voltage at AC, 60 Hz - max |
0 V
|
Operating voltage at DC - min |
24 V
|
Operating voltage at DC - max |
24 V
|