Eaton Moeller® series Rapid Link Distribution module, 3xflat cable, 2xRound cable, for supply
| Product Name |
Eaton Rapid Link Distribution module
|
| Catalog Number |
264244
|
| EAN |
4015082642440
|
| Product Length/Depth |
175 mm
|
| Product Height |
78 mm
|
| Product Width |
83 mm
|
| Product Weight |
0.355 kg
|
| Certifications |
IEC/EN 60529
EN 60998-2-1 |
| Catalog Notes |
Order V-M25/V-M20 cable gland and RA-C1-DF bushing separately.
|
| 10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
| 10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
| 10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
| 10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
| 10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
| 10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.2.7 Inscriptions |
Meets the product standard's requirements.
|
| 10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
| 10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
| 10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
| 10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
| 10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
| 10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
| 10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
| Fitted with: |
3 flexible busbar inputs and 2 round cable inputs
|
| Connection |
Connection of round cables 4 mm²
|
| Accessory/spare part type |
Connection technique
|
| Contact type |
Screw connection double-decker terminal blocks 1.5 to 4 mm²
|
| Degree of protection |
IP65, according to IEC/EN 60529
|
| Mounting position |
As required
|
| Ambient operating temperature - max |
50 °C
|
| Ambient operating temperature - min |
-30 °C
|
| Ambient storage temperature - max |
70 °C
|
| Ambient storage temperature - min |
-40 °C
|
| Rated operational current (Ie) |
32 A
|
| Functions |
For the 400V AC feeding to the ribbon cable with a round cable
|
| Rated operational voltage (Ue) at AC - max |
500 V
|
| Rated operational voltage (Ue) at DC - max |
24 V
|
| Product category |
Accessories
|