La foto es representativa
                                
                                
                                    
                                    Download
                                
                                
                                Eaton Moeller® series MSC-R Reversing starter, 380 V 400 V 415 V: 7.5 kW, Ir= 10 - 16 A, 24 V DC, DC voltage MSC-R-16-M17(24VDC)
| Product Name | 
                                                Eaton Moeller® series MSC-R Reversing starter
                                             | 
| Catalog Number | 
                                                283204
                                             | 
| EAN | 
                                                4015082832049
                                             | 
| Product Length/Depth | 
                                                228 mm
                                             | 
| Product Height | 
                                                123.4 mm
                                             | 
| Product Width | 
                                                90 mm
                                             | 
| Product Weight | 
                                                1.66 kg
                                             | 
| Certifications | 
                                                CSA Class No.: 3211-24  CSA-C22.2 No. 14-10 IEC/EN 60947-4-1 UL CSA UL 508 (on request) UL File No.: E123500 CSA-C22.2 No. 14 (on request) UL60947-4-1A CE CSA File No.: 012528 UL Category Control No.: NKJH | 
| Fitted with: | 
                                                Short-circuit release
                                             | 
| Functions | 
                                                Temperature compensated overload protection
                                             | 
| Class | 
                                                CLASS 10 A
                                             | 
| Connection | 
                                                Screw terminals
                                             | 
| Connection to SmartWire-DT | 
                                                No
                                             | 
| Coordination type | 
                                                2
                                             | 
| Degree of protection | 
                                                IP00  NEMA Other | 
| Model | 
                                                IEC starter
                                             | 
| Mounting method | 
                                                DIN rail
                                             | 
| Number of auxiliary contacts (normally closed contacts) | 
                                                0
                                             | 
| Number of auxiliary contacts (normally open contacts) | 
                                                0
                                             | 
| Overload release current setting - min | 
                                                10 A
                                             | 
| Overload release current setting - max | 
                                                16 A
                                             | 
| Overvoltage category | 
                                                III
                                             | 
| Pollution degree | 
                                                3
                                             | 
| Rated impulse withstand voltage (Uimp) | 
                                                6000 V AC
                                             | 
| Suitable for | 
                                                Also motors with efficiency class IE3
                                             | 
| Type | 
                                                Starter with Bi-Metal release
                                             | 
| Voltage type | 
                                                DC
                                             | 
| Altitude | 
                                                Max. 2000 m
                                             | 
| Ambient operating temperature - min | 
                                                -25 °C
                                             | 
| Ambient operating temperature - max | 
                                                55 °C
                                             | 
| Rated operational current (Ie) | 
                                                15.2 A
                                             | 
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 
                                                16 A
                                             | 
| Rated operational power at AC-3, 220/230 V, 50 Hz | 
                                                4 kW
                                             | 
| Rated operational power at AC-3, 380/400 V, 50 Hz | 
                                                7.5 kW
                                             | 
| Rated operational voltage | 
                                                230 - 415 V AC
                                             | 
| Switching capacity (auxiliary contacts, general use) | 
                                                15 A, 600 V AC, (UL/CSA)  1 A, 250 V DC, (UL/CSA) | 
| Switching capacity (auxiliary contacts, pilot duty) | 
                                                P300, DC operated (UL/CSA)  A600, AC operated (UL/CSA) | 
| Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V | 
                                                50000 A
                                             | 
| Short-circuit release (Irm) - max | 
                                                248 A
                                             | 
| Power consumption (sealing) at DC | 
                                                0.5 W
                                             | 
| Rated control supply voltage (Us) at AC, 50 Hz - min | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at AC, 50 Hz - max | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at AC, 60 Hz - min | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at AC, 60 Hz - max | 
                                                0 V
                                             | 
| Rated control supply voltage (Us) at DC - min | 
                                                24 V
                                             | 
| Rated control supply voltage (Us) at DC - max | 
                                                24 V
                                             | 
| Equipment heat dissipation, current-dependent Pvid | 
                                                9.3 W
                                             | 
| Heat dissipation capacity Pdiss | 
                                                0 W
                                             | 
| Heat dissipation per pole, current-dependent Pvid | 
                                                3.1 W
                                             | 
| Rated operational current for specified heat dissipation (In) | 
                                                16 A
                                             | 
| Static heat dissipation, non-current-dependent Pvs | 
                                                0.9 W
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Meets the product standard's requirements.
                                             | 
| 10.5 Protection against electric shock | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility. The specifications for the switchgear must be observed.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             |