Eaton Moeller® series DILM Contactor, 3 pole, 380 V 400 V 55 kW, RAC 240: 190 - 240 V 50/60 Hz, AC operation, Spring-loaded terminals DILMC115-EA(RAC240)
Product Name |
Eaton Moeller® series DILM contactor
|
Catalog Number |
189969
|
EAN |
4015081879656
|
Product Length/Depth |
160 mm
|
Product Height |
170 mm
|
Product Width |
90 mm
|
Product Weight |
2.27 kg
|
Compliances |
RoHS conform
CE Marked |
Model Code |
DILMC115-EA(RAC240)
|
Connection |
Spring-loaded terminals
Screw terminals |
Voltage type |
AC
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
160 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
115 A
|
Rated operational current (Ie) at AC-4, 400 V |
55 A
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
160 A
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
55 kW
|
Short-circuit current rating (basic rating) |
10 kA, 600 A max. fuse, SCCR (UL/CSA)
10 kA, 600 A max. CB, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 480 V) |
100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA)
30 kA, 600 A max. fuse, SCCR (UL/CSA) 65 kA, 250 A max. CB, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 600 V) |
100 kA, 300 A CLASS J max. fuse, SCCR (UL/CSA)
30 kA, 600 A max. fuse, SCCR (UL/CSA) |
Rated control supply voltage (Us) at AC, 50 Hz - min |
230 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
240 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|