Download document () of 20
Grid automation system solutions

GridAdvisor sensors

Eaton’s GridAdvisor sensors is a family of products that is used to monitor utility grids of all voltages, currents, overhead, padmount and vault applications. Equipped with integrated communications capabilities, the solution provides for outage management, condition-based asset management, demand profiling, waveform capture and data storage. These sensors provide utilities with valuable insights from their field assets through real-time monitoring, historical performance tracking as well as reviewable event data via Proview NXG software or exported through COMTRADE, all enabling efficient operations, strategic maintenance planning, prevention of costly failures and reduced downtime.

Reliable outage detection
Operational efficiency
Hot stick-installable
Low-cost installations
Native DNP3 protocol support
SCADA visibility

Core features

  • Self-contained, conductor-mounted with patented energy harvesting technology
  • Easy hot stick-installation virtually anywhere on the grid
  • Remote communications real-time data and device management
  • Reliable algorithms for fault detection and outage management
  • Accurate real time load flow monitoring
  • Condition-based asset management functionality

Simplified installation

Patented Energy Harvesting technology eliminates wiring to external power sources, simplifying and lowering cost of installation. Simply install with a hot stick for easy deployment on overhead and underground circuits.

Save operation and maintenance costs

Leverage the GridAdvisor Series II smart sensor as a communicating fault indicator to use standardized communications protocols to respond to disturbances on the line and more quickly restore outages. Harness the power of new, low-bandwidth IOT cellular networks to obtain critical system information – reducing drive time and maximizing energy dollars by keeping capacitors online and operating at peak efficiency.
Specifications

Electrical ratings and characteristics

Description Ratings and Characteristics
Catalog number  E0013X41G12 (LTE)
Catalog number  E0013X41G10 (CMDA/HSPA+)
Power requirements  5 amps primary current
Reset time Field configurable 1-2 hours
Trip current  100, 350 variable trip di/dt
Mode of indication Dual LEDs and DNP3
Maximum operating voltage  69 kV L-L
Fault withstand capability  25 kA for 10 cycles per IEEE Std 495-2007 standard
Temperature range  -40 °C to +85 °C
Materials  Corrosion-resistant and submersible per IEEE Std 495-2007 standard
Weight 2.42 lbs (1.1 kg)

Features

Physical features

  • Overhead and underground installable
    • Deployable on a wide variety of wire and cable sizes, anywhere from 0.25 inches to 2 inches in diameter
    • Shotgun stick-installable
  • Visual indication with dual multi-colored LEDs

Core operational features

  • Variable-trip design fault detection
  • Demand current profiling
  • Capacitor bank monitoring

Communications

  • DNP3 native device
  • Class 2, Bluetooth radio
  • Dual CAT M1 and NB/IoT cellular modem capable of supporting a wide variety of 4G/LTE networks
  • GPS location
  • Load current and fault current directionality