Eaton Moeller® series B3 Three-phase busbar link, Circuit-breaker: 4, 220 mm
Product Name |
Eaton Moeller® series B3 Accessory Three-phase busbar link
|
Catalog Number |
220222
|
EAN |
4015082202224
|
Product Length/Depth |
205 mm
|
Product Height |
36 mm
|
Product Width |
33 mm
|
Product Weight |
0.322 kg
|
Certifications |
CSA Class No.: 3211-06
CSA-C22.2 No. 14 UL File No.: E36332 CE IEC/EN 60947-4-1 UL 508 UL Category Control No.: NLRV CSA CSA File No.: 165628 UL |
Color |
Black
|
Electric connection type |
Pin
|
Features |
Insulated
|
Number of phases |
3
|
Number of poles |
Three-pole
|
Mounting width |
55 mm
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Accessories
|
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Suitable for |
4 Circuit-breakers
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
55 °C
|
Rated operational voltage (Ue) - max |
690 V
|
Rated operational voltage (Ue) at AC - max |
690 V
|
Rated uninterrupted current (Iu) |
128 A
|
Rated conditional short-circuit current (Iq) |
0 kA
|
Rated short-time withstand current (Icw) |
0 kA
|
Equipment heat dissipation, current-dependent Pvid |
9.6 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
3.2 W
|
Rated operational current for specified heat dissipation (In) |
128 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|