Eaton XN-322 Digital output block module XI/ON, 24 V DC, 32DO, 0.5A, pulse-switching
Product Name |
Eaton XN-322 Output block module
|
Catalog Number |
140161
|
EAN |
7640130120273
|
Product Length/Depth |
100.8 mm
|
Product Height |
55.4 mm
|
Product Width |
74.1 mm
|
Product Weight |
0.11 kg
|
Certifications |
CSA Class No.: 2252-01, 2252-81
UL File No.: E205091 IEC/EN 61000-6-4 Certified by UL for use in Canada IEC/EN 61000-6-2 IEC/EN 6113-2 UL Recognized UL report applies to both US and Canada UL 508 CSA-C22.2 No. 142 cULus CE UL Category Control No.: NRAQ, NRAQ7 IEC/EN 61131-2 |
Catalog Notes |
Max. 10 A (total module current) Utilization factor
|
Used with |
XN-B6S-SBCSBC
XN-B6T-SBCSBC |
Type |
XI/ON I/O module
|
Features |
Fieldbus connection over separate bus coupler possible
|
Air discharge |
According to EN 61100-4-2
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Electric connection type |
Screw-/spring clamp connection
|
Fitted with: |
Connectable sensors for lamp loads
Connectable sensors for resistive loads Connectable sensors for inductive loads |
Number of inputs (digital) |
0
|
Burst impulse |
According to IEC/EN 61000-4-4
|
Number of channels |
32
|
Explosion safety category for dust |
None
|
Environmental conditions |
Harmful gasses - SO2: 10 ppm (relative humidity < 75%, no condensation)
Harmful gasses - H2S: 1 ppm (relative humidity < 75%, no condensation) |
Output voltage |
23 V DC (Digital outputs)
|
Explosion safety category for gas |
None
|
Output current |
< 1 A (high level, permissible range)
0.5 A 10 A, Module total current, Digital outputs |
Mounting method |
Rail mounting possible
|
Current consumption |
30 mA, from module bus, Analog input modules
30 mA, from supply terminal |
Voltage type |
DC
|
Output |
32 Digital Outputs (24 V DC, 0.5 A)
Parallel connection of max. 2 Transistor outputs |
Contact discharge |
According to EN 61100-4-2
|
Safety performance level (EN ISO 13849-1) |
None
|
SIL (IEC 61508) |
None
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
0 °C
|
Ambient storage temperature - max |
85 °C
|
Ambient storage temperature - min |
-25 °C
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current at signal 1 |
0 mA
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
0
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Surge rating |
According to IEC/EN 61000-4-5 Level 4
|
Emitted interference |
230 - 1000 MHz (radiated, high frequency, according to EN 55016-2-3)
30 - 230 MHz (radiated, high frequency, according to EN 55016-2-3) |
Potential isolation |
Through optocoupler: yes
|
Power loss |
5 W
|
Electromagnetic fields |
According to IEC EN 61100-4-2
|
Radiated RFI |
IEC/EN 61100-4-6
|
Load resistance |
1.2 h (inductive load)
≥ 48 Ω |
Drop and topple |
According to IEC 60068-2-31, free fall according to IEC 60068-2-32
|
Protocol |
Other bus systems
|
Number of outputs (digital) |
32
|
Relative humidity |
5 - 95 % (indoor, Level RH-2, non-condensing for storage at 45°C)
|
Data transmission type |
Transistor
|
Rated operational voltage |
24 V DC (supply terminal)
|
Short-circuit release |
Automatic, Ii, Reset after short-circuit rectified, Digital outputs
|
Degree of protection |
IP20
|
Delay time |
300 µs, Digital outputs, Delay on signal change and resistive load, from High to Low signal
300 µs, Digital outputs, Delay on signal change and resistive load, from Low to High signal |
Vibration resistance |
According to IEC/EN 60068-2-6
|
Shock resistance |
Continuous according to IEC/EN 60068-2-29
Mechanical, According to IEC/EN 60068-2-27 |
Short-circuit protection |
Short-circuit proof, Short-circuit rating, Digital outputs
|
Lamp load |
≤ 6 W (at RLL)
|
Functions |
Diagnosis function
Short-circuit protection, outputs available Positive switching |
Suitable for |
Base modules with C-connection: 2-wire/3-wire
|
Number of bytes |
8 diagnostic bytes
|
Switching frequency |
100 Hz, with resistive load RLO < 1 kΩ, Digital outputs
|
System accessory |
Yes
|
Utilization factor |
100 %
|
Interfaces |
Terminating resistor: > 48 Ω
|
Voltage dips |
According to EN 61131-2 (Voltage fluctuations/voltage dips)
|
Number of HW-interfaces (wireless) |
0
|
Number of interfaces (PROFINET) |
0
|
Permitted voltage at input - max |
0 V
|
Permitted voltage at input - min |
0 V
|
Permitted voltage at output - max |
30 V
|
Permitted voltage at output - min |
0 V
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
5 W
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 60 Hz - max |
0 VAC
|
Supply voltage at AC, 60 Hz - min |
0 VAC
|
Supply voltage at DC - max |
30 VDC
|
Supply voltage at DC - min |
18 VDC
|
Time delay at signal exchange - max |
0.3 ms
|
Time delay at signal exchange - min |
0.1 ms
|
Product category |
XN Block module
|