Eaton DC1 Variable frequency drive, 400 V AC, 3-phase, 4.1 A, 1.5 kW, IP20/NEMA 0, FS1 DC1-344D1NN-A20CE1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
185724
|
EAN |
4015081812233
|
Product Length/Depth |
124 mm
|
Product Height |
184 mm
|
Product Width |
81 mm
|
Product Weight |
1.2 kg
|
Certifications |
IEC/EN61800-5
RoHS, ISO 9001 CUL UL CSA-C22.2 No. 14 UL Category Control No.: NMMS, NMMS7 EAC UL report applies to both US and Canada IEC/EN61800-3 Specification for general requirements: IEC/EN 61800-2 IEC/EN 61800-3 CE UL 508C Certified by UL for use in Canada UkrSEPRO RCM Safety requirements: IEC/EN 61800-5-1 UL File No.: E172143 |
Catalog Notes |
|
Features |
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus Parameterization: Keypad |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Internal DC link
7-digital display assembly PC connection IGBT inverter Control unit Additional PCB protection |
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DX-NET-SWD3 SmartWire DT module |
Operating mode |
Sensorless vector control (SLV)
Speed control with slip compensation U/f control BLDC motors PM motors Synchronous reluctance motors |
Rated impulse withstand voltage (Uimp) |
2000 V
|
Frame size |
FS1
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m |
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Mains voltage - max |
480 V
|
Output voltage - max |
500 V
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient storage temperature - max |
60 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 400 V |
2.84 kVA
|
Apparent power at 480 V |
3.41 kVA
|
Application in industrial area permitted |
Yes
|
Heat dissipation details |
Operation (with 150 % overload)
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Voltage rating - max |
480 V
|
Mounting position |
Vertical
|
Overvoltage category |
III
|
Communication interface |
SmartWire-DT, optional
CANopen®, built in OP-Bus (RS485), built in Modbus RTU, built in |
Converter type |
U converter
|
Degree of protection |
IP20
NEMA Other |
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
2 HP
|
Equipment heat dissipation, current-dependent Pvid |
76.5 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 150% overload |
5.6 A
|
Mains current distortion |
120 %
|
Protocol |
CAN
Other bus systems MODBUS EtherNet/IP |
Overload current IL at 150% overload |
6.15 A
|
Rated frequency - max |
62 Hz
|
Rated frequency - min |
48 Hz
|
Rated operational current for specified heat dissipation (In) |
4.1 A
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
1.5 kW
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
3.6 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
3.4 A
|
System configuration type |
AC supply systems with earthed center point
|
Braking current |
≤ 0.6 A (max. 6 A for 120 ms), Actuator for external motor brake
|
Braking torque |
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
Max. 30 % MN, Standard - Main circuit |
Cable length |
50 m, screened, maximum permissible, Motor feeder
100 m, screened, with motor choke, maximum permissible, Motor feeder 75 m, unscreened, maximum permissible, Motor feeder 150 m, unscreened, with motor choke, maximum permissible, Motor feeder |
Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase |
Delay time |
< 10 ms, On-delay
< 10 ms, Off-delay |
Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
|
Number of inputs (digital) |
4 (parameterizable, 10 - 30 V DC)
|
Radio interference class |
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
|
Number of outputs (digital) |
1
|
Starting current - max |
175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Number of phases (output) |
3
|
Power consumption |
76.5 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
94.9 % (η)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
13 mA
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
4.1 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
1.5 kW
|
Output at quadratic load at rated output voltage - max |
1.5 kW
|
Output frequency - max |
500 Hz
|
Output frequency - min |
0 Hz
|
Short-circuit protection (external output circuits) |
Type 1 coordination via the power bus' feeder unit, Main circuit
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
Rated operational current (Ie) |
4.1 A at 150% overload (at an operating frequency of 16 kHz and an ambient air temperature of +50 °C)
|
Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase |
Short-circuit protection rating |
6 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Heat dissipation at current/speed |
20 W at 25% current and 0% speed
27 W at 25% current and 50% speed 27 W at 50% current and 50% speed 28 W at 50% current and 0% speed 36 W at 100% current and 0% speed 36 W at 50% current and 90% speed 46 W at 100% current and 50% speed 49 W at 100% current and 90% speed |