Eaton DC1 Variable frequency drive, 230 V AC, 1-phase, 7 A, 1.5 kW, IP20/NEMA 0, Radio interference suppression filter, FS1 DC1-127D0FN-A20CE1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
185809
|
EAN |
4015081813087
|
Product Length/Depth |
124 mm
|
Product Height |
184 mm
|
Product Width |
81 mm
|
Product Weight |
1.2 kg
|
Certifications |
IEC/EN61800-5
Certified by UL for use in Canada RCM RoHS, ISO 9001 UL 508C EAC Specification for general requirements: IEC/EN 61800-2 UL CUL IEC/EN 61800-3 UkrSEPRO Safety requirements: IEC/EN 61800-5-1 UL Category Control No.: NMMS, NMMS7 UL File No.: E172143 IEC/EN61800-3 UL report applies to both US and Canada CE CSA-C22.2 No. 14 |
Catalog Notes |
|
Features |
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus Parameterization: Keypad |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Control unit
IGBT inverter 7-digital display assembly Internal DC link Radio interference suppression filter PC connection Additional PCB protection |
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DX-NET-SWD3 SmartWire DT module |
Operating mode |
Sensorless vector control (SLV)
Speed control with slip compensation U/f control BLDC motors PM motors Synchronous reluctance motors |
Rated impulse withstand voltage (Uimp) |
2000 V
|
Frame size |
FS1
|
Altitude |
Max. 4000 m
Above 1000 m with 1 % derating per 100 m |
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Mains voltage - max |
240 V
|
Output voltage - max |
250 V
|
Rated operational power at 220/230 V, 50 Hz, 3-phase |
1.5 kW
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient storage temperature - max |
60 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 230 V |
2.79 kVA
|
Apparent power at 240 V |
2.91 kVA
|
Application in industrial area permitted |
Yes
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Voltage rating - max |
240 V
|
Mounting position |
Vertical
|
Overvoltage category |
III
|
Communication interface |
SmartWire-DT, optional
CANopen®, built in Modbus RTU, built in OP-Bus (RS485), built in |
Converter type |
U converter
|
Degree of protection |
IP20
NEMA Other |
Assigned motor power at 220/230 V, 60 Hz, 3-phase |
2 HP
|
Equipment heat dissipation, current-dependent Pvid |
63 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 150% overload |
12.9 A
|
Mains current distortion |
120 %
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
6.8 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
6.3 A
|
Protocol |
Other bus systems
CAN EtherNet/IP MODBUS |
Overload current IL at 150% overload |
10.5 A
|
Rated frequency - max |
62 Hz
|
Rated frequency - min |
48 Hz
|
Rated operational current for specified heat dissipation (In) |
7 A
|
System configuration type |
AC supply systems with earthed center point
|
Braking current |
≤ 0.6 A (max. 6 A for 120 ms), Actuator for external motor brake
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Braking torque |
Max. 100 % of rated operational current Ie, variable, DC - Main circuit
Max. 30 % MN, Standard - Main circuit |
Cable length |
50 m, screened, maximum permissible, Motor feeder
100 m, screened, with motor choke, maximum permissible, Motor feeder C2 ≤ 5 m, Radio interference level, maximum motor cable length C3 ≤ 25 m, Radio interference level, maximum motor cable length 75 m, unscreened, maximum permissible, Motor feeder 150 m, unscreened, with motor choke, maximum permissible, Motor feeder C1 ≤ 1 m, Radio interference level, maximum motor cable length |
Output voltage (U2) |
230 V AC, 3-phase
240 V AC, 3-phase |
Delay time |
< 10 ms, On-delay
< 10 ms, Off-delay |
Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
|
Number of inputs (digital) |
4 (parameterizable, 10 - 30 V DC)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: for conducted emissions only Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Number of outputs (digital) |
1
|
Starting current - max |
175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
|
Number of phases (input) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Number of phases (output) |
3
|
Power consumption |
63 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
95.8 % (η)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
4.8 mA
|
Mains voltage - min |
200 V
|
Nominal output current I2N |
7 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
1.5 kW
|
Output at quadratic load at rated output voltage - max |
1.5 kW
|
Output frequency - max |
500 Hz
|
Output frequency - min |
0 Hz
|
Short-circuit protection (external output circuits) |
Type 1 coordination via the power bus' feeder unit, Main circuit
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
Rated operational current (Ie) |
7 A at 150% overload (at an operating frequency of 16 kHz and an ambient air temperature of +50 °C)
|
Rated operational voltage |
240 V AC, 1-phase
230 V AC, 1-phase |
Short-circuit protection rating |
15 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Heat dissipation at current/speed |
26 W at 25% current and 0% speed
26 W at 25% current and 50% speed 31 W at 50% current and 0% speed 40 W at 50% current and 50% speed 48 W at 100% current and 0% speed 48 W at 50% current and 90% speed 68 W at 100% current and 50% speed 78 W at 100% current and 90% speed |