Eaton DC1 Variable frequency drive, 230 V AC, 3-phase, 18 A, 4 kW, IP20/NEMA 0, Radio interference suppression filter, Brake chopper, FS3 DC1-32018FB-A20CE1
Product Name |
Eaton DC1 Variable frequency drive
|
Catalog Number |
185842
|
EAN |
4015081813414
|
Product Length/Depth |
175 mm
|
Product Height |
273 mm
|
Product Width |
129 mm
|
Product Weight |
6 kg
|
Certifications |
UL 508C
UL report applies to both US and Canada UL UL File No.: E172143 EAC IEC/EN61800-3 UkrSEPRO CE Certified by UL for use in Canada Safety requirements: IEC/EN 61800-5-1 RoHS, ISO 9001 Specification for general requirements: IEC/EN 61800-2 CSA-C22.2 No. 14 IEC/EN 61800-3 IEC/EN61800-5 RCM UL Category Control No.: NMMS, NMMS7 CUL |
Catalog Notes |
|
Features |
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus Parameterization: Keypad |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
7-digital display assembly
PC connection Control unit Radio interference suppression filter IGBT inverter Internal DC link Brake chopper Breaking resistance Additional PCB protection |
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
In conjunction with DX-NET-SWD3 SmartWire DT module
Yes |
Operating mode |
Speed control with slip compensation
U/f control Sensorless vector control (SLV) BLDC motors PM motors Synchronous reluctance motors |
Rated impulse withstand voltage (Uimp) |
2000 V
|
Frame size |
FS3
|
Altitude |
Max. 4000 m
Above 1000 m with 1 % derating per 100 m |
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Mains voltage - max |
240 V
|
Output voltage - max |
250 V
|
Rated operational power at 220/230 V, 50 Hz, 3-phase |
4 kW
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient storage temperature - max |
60 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 230 V |
7.17 kVA
|
Apparent power at 240 V |
7.48 kVA
|
Application in industrial area permitted |
Yes
|
Product category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Switch-on threshold for the braking transistor |
390 VDC
|
Voltage rating - max |
240 V
|
Mounting position |
Vertical
|
Overvoltage category |
III
|
Communication interface |
Modbus RTU, built in
OP-Bus (RS485), built in CANopen®, built in SmartWire-DT, optional |
Converter type |
U converter
|
Degree of protection |
IP20
NEMA Other |
Assigned motor power at 220/230 V, 60 Hz, 3-phase |
5 HP
|
Braking resistance |
25 Ω
|
Equipment heat dissipation, current-dependent Pvid |
160 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 150% overload |
20.9 A
|
Mains current distortion |
120 %
|
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload |
15.2 A
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
14.8 A
|
Protocol |
Other bus systems
EtherNet/IP CAN MODBUS |
Overload current IL at 150% overload |
27 A
|
Rated frequency - max |
62 Hz
|
Rated frequency - min |
48 Hz
|
Rated operational current for specified heat dissipation (In) |
18 A
|
System configuration type |
AC supply systems with earthed center point
|
Braking current |
≤ 0.6 A (max. 6 A for 120 ms), Actuator for external motor brake
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie, variable, DC - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Cable length |
C2 ≤ 5 m, Radio interference level, maximum motor cable length
200 m, screened, with motor choke, maximum permissible, Motor feeder C3 ≤ 25 m, Radio interference level, maximum motor cable length 100 m, screened, maximum permissible, Motor feeder 150 m, unscreened, maximum permissible, Motor feeder 300 m, unscreened, with motor choke, maximum permissible, Motor feeder |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
240 V AC, 3-phase
230 V AC, 3-phase |
Delay time |
< 10 ms, On-delay
< 10 ms, Off-delay |
Number of inputs (analog) |
2 (parameterizable, 0 - 10 V DC, 0/4 - 20 mA)
|
Number of inputs (digital) |
4 (parameterizable, 10 - 30 V DC)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Number of outputs (digital) |
1
|
Starting current - max |
175 %, IH, max. starting current (High Overload), For 2.5 seconds every 600 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Number of phases (output) |
3
|
Power consumption |
160W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
96 % (η)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
6.8 mA
|
Mains voltage - min |
200 V
|
Nominal output current I2N |
18 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
4 kW
|
Output at quadratic load at rated output voltage - max |
4 kW
|
Output frequency - max |
500 Hz
|
Output frequency - min |
0 Hz
|
Short-circuit protection (external output circuits) |
Type 1 coordination via the power bus' feeder unit, Main circuit
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit
|
Rated operational current (Ie) |
At a switching frequency of 8 kHz and an ambient air temperature of +50 °C
18 A at 150% overload |
Rated operational voltage |
240 V AC, 3-phase
230 V AC, 3-phase |
Short-circuit protection rating |
20 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Heat dissipation at current/speed |
100 W at 50% current and 0% speed
117 W at 50% current and 50% speed 139 W at 50% current and 90% speed 157 W at 100% current and 0% speed 186 W at 100% current and 50% speed 218 W at 100% current and 90% speed 78 W at 25% current and 0% speed 92 W at 25% current and 50% speed |