Eaton Moeller series NZM Undervoltage release, 208-240VAC, for NZM1
Product Name |
Eaton Moeller series NZM Undervoltage release
|
Catalog Number |
259442
|
EAN |
4015082594428
|
Product Length/Depth |
37 mm
|
Product Height |
66 mm
|
Product Width |
32 mm
|
Product Weight |
0.072 kg
|
Compliances |
IEC
UL/CSA RoHS conform |
Certifications |
UL489
CSA (File No. 22086) CE marking UL (File No. E140305) IEC60947 UL (Category Control Number DIHS) CSA-C22.2 No. 5-09 CSA (Class No. 1437-01) UL listed CSA certified |
Used with |
NZM1(-4), N(S)1(-4)
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Electric connection type |
Screw connection
|
Frame |
NZM1
|
Minimum command time - max |
15 ms
|
Minimum command time - min |
10 ms
|
Number of contacts (normally open contacts) |
0
|
Reaction time |
19 ms
|
Pick-up power consumption at AC (undervoltage release) |
1.5 VA
|
Pick-up power consumption at DC (undervoltage release) |
0.8 W
|
Voltage tolerance - max |
1.1
|
Voltage tolerance - min |
.85
|
Rated control supply voltage |
208 - 240 V 50/60 Hz
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
240 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
208 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
208 V
|
Suitable for |
Off-load switch
|
Connection type |
With terminal block on the left-hand switch side
|
Voltage type |
AC
|
Drop-out voltage of undervoltage release AC/DC - max |
0.7 x Us
|
Drop-out voltage of undervoltage release AC/DC - min |
0.35 x Us
|
Terminal capacity (solid/flexible conductor) |
0.75 mm² - 2.5 mm² (2x) at shunt release with ferrule
0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule 0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule 18 - 14 AWG (1x) at shunt release 18 - 14 AWG (2x) at shunt release 0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule 18 - 14 AWG (1x) for undervoltage releases, off-delayed 18 - 14 AWG (2x) for undervoltage releases, off-delayed |
Type |
|
Special features |
|
Power consumption |
0.8 W (sealing DC)
1.5 VA (sealing AC) |
Rated control supply voltage (Us) at DC - max |
0 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Number of contacts (normally closed contacts) |
0
|
Number of contacts (change-over contacts) |
0
|
Undelayed short-circuit release - min |
0 A
|
Undelayed short-circuit release - max |
0 A
|
Rated control voltage (relay contacts) |
240 V AC
208 V AC |