La foto es representativa
Download
Eaton DM1 Variable frequency drive, 400 V AC, 3-phase, 1.5 A, 0.55 kW, IP20/NEMA0, Brake chopper, FS1
Product Name |
Eaton DM1 Variable frequency drive
|
Catalog Number |
3-5026-005A
|
EAN |
4015081980307
|
Product Length/Depth |
180 mm
|
Product Height |
152 mm
|
Product Width |
72 mm
|
Product Weight |
1.2 kg
|
Certifications |
UL
CE marking IEC/EN61800-5 Certified by UL for use in Canada CE IEC/EN61800-3 UL report applies to both US and Canada UL 508C UL Listed IEC/EN 61800-2 CSA-C22.2 No. 274-17 CSA-C22.2 No. 274-13 UkrSEPRO IEC/EN 61800-5-1 UL Category Control No.: NMMS, NMMS7 UL File No.: E134360 C-Tick CUL EAC IEC/EN 61800-3 RoHS, ISO 9001 |
Product Category |
Variable frequency drives
|
Features |
Temperature-controlled fan
Parameterization: Keypad Parameterization: Power Xpert inControl Parameterization: Fieldbus |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
IGBT inverter
Internal DC link Brake chopper PC connection |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Operating mode |
U/f control
|
Frame size |
FS1
|
Air volume capacity |
26 m³/h
|
Altitude |
Max. 2000 m for Corner Grounded TN Systems
Max. 1000 m Max. 3000 m Above 1000 m with 1 % derating per 100 m |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Assigned motor current IM at 230 V, 50 Hz, 150% overload |
1.4 A
|
Mains voltage tolerance |
380 - 500 V (-15%/+10%, at 50/60Hz)
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload |
1.1 kW
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Switch-on threshold for the braking transistor |
800 VDC
|
Voltage rating - max |
500 V
|
Overvoltage category |
III
|
Communication interface |
Modbus RTU, built in
CANopen®, optional SmartWire-DT, optional PROFIBUS, optional DeviceNet, optional |
Converter type |
U converter
|
Degree of protection |
IP20
NEMA Other |
Protocol |
MODBUS
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
1.1 A
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 460/480 V, 60 Hz |
0.5 HP
|
Assigned motor power at 460/480 V, 60 Hz, 110% overload |
1 HP
|
Braking resistance |
105 Ω
|
Equipment heat dissipation, current-dependent Pvid |
43 W
|
Input current ILN at 110% overload |
2.6 A
|
Input current ILN at 150% overload |
1.8 A
|
Mains current distortion |
40 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
1 (expansion)
|
Braking torque |
Adjustable to 150 %, DC - Main circuit
Max. 30 % MN, Standard - Main circuit Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
480 V AC, 3-phase
500 V AC, 3-phase 400 V AC, 3-phase |
Number of inputs (analog) |
1
|
Number of inputs (digital) |
4
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments C1: with external filter |
Number of outputs (digital) |
0
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
2 (parameterizable, 1 changeover contact and 1 N/O, 3 A (240 V AC) / 3 A (24 V DC))
|
Number of phases (output) |
3
|
Power consumption |
43 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Mains voltage - max |
500 V
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
1.5 A
|
Number of HW-interfaces (industrial ethernet) |
0
|
Number of HW-interfaces (other) |
0
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
1
|
Output at linear load at rated output voltage - max |
0.37 kW
|
Output at quadratic load at rated output voltage - max |
0.75 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
500 V
|
Overload current IL at 110% overload |
2.42 A
|
Overload current IL at 150% overload |
2.25 A
|
Shock resistance |
0.75 mm (peak) at 10 - 57 Hz, max. 1 g at 57 - 150 Hz, according to EN 61800-5-1, EN 60068-2-6: 10 - 150 Hz
|
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
4 kHz, 1 - 16 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
400 V AC, 3-phase
480 V AC, 3-phase 500 V AC, 3-phase |
Short-circuit protection rating |
4 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
2.2 A
|
Rated operational current (Ie) at 150% overload |
1.5 A
|
Rated operational current for specified heat dissipation (In) |
2.2 A
|
Rated operational power at 380/400 V, 50 Hz, 110% overload |
0.75 kW
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
0.55 kW
|
Rated operational power at 500 V, 50 Hz, 3-phase |
0.75 kW
|
Heat dissipation at current/speed |
13 W at 100% current and 50% speed
20 W at 50% current and 50% speed 22 W at 100% current and 0% speed 23 W at 50% current and 90% speed 24 W at 25% current and 0% speed 27 W at 50% current and 0% speed 28 W at 25% current and 50% speed 33 W at 100% current and 90% speed |