Medium-voltage cable accessories

Loadbreak connectors

Eaton’s Cooper Power series 200 A 15, 25 and 35 kV loadbreak elbow connectors,  600 A 15 and 25 kV Cleer loadbreak technology, and accessories are used to connect underground cable to transformers, switchgear and sectionalizing cabinets. They are ideal for submersible, fully-shielded and insulated plug-in terminations.

Fully meets IEEE 386 Std
Interchangeable
Reliable 600 A loadbreak
Simplifies operation
Stress-relieving features
Superior switching and reliability

Core features

  • All 200 A loadbreak connectors meet the electrical, mechanical and dimensional requirements of IEEE Std 386 standard
  • Designed to be fully interchangeable with other components currently complying with IEEE Std 386 standard
  • 15 kV and 25 kV loadbreak elbows are available with integral jacket seal for use with concentric neutral and other types of shielded cable
  • Designed for use on XLPE, EPR or other solid dielectric insulated underground electrical cables
  • Molded using high-quality, peroxide-cured EPDM insulation for reliable field performance

See the loadbreak connector in action

Establish loops, taps, splices and facilitate apparatus changeouts with 200 A and 600 A, 15 and 25 kV class multi-point variable junctions

Eaton’s Cooper Power series junction bars are designed for vault or apparatus applications and can be used for looping, tapping and sectionalizing. They are fully shielded, submersible, and are designed and manufactured in accordance with IEEE Std 386-2016 standard. These junctions provide 2 to 6, 15 or 25 kV mixed inline 200 A loadbreak, 600 A deadbreak or 600 A loadbreak Cleer interfaces bussed together and encapsulated in a precision-molded, peroxide-cured EPDM insulated rubber body. Junction bars come standard with a stainless steel mounting bracket.

Designed for superior switching performance

Eaton's Cooper Power series POSI-BREAK loadbreak elbow connectors use stress-relieving features around current exchange and improved dielectrics from increased strike distance for superior switching performance and reliability.

35 kV large interface elbow bushing system

Eaton's Cooper Power series 35 kV 200 A large interface elbow bushing system is a reliable, field proven design. This system has over 25 years of field experience while being used on large 35 kV distribution systems. Features of the large interface system include increased strike distance to provide greater reliability and overall performance, reliable loadbreak switching and fault closure capability. A full line of large interface accessory products is available.
Specifications

Ratings

200 A loadbreak connector ratings in accordance with IEEE Std 386 standard
Voltage ratings 15 kV
25 kV 35 kV
Standard voltage class
15 25 35
Maximum rating phase-to-phase
14.4
26.3 36.6
Maximum rating phase to-ground 8.3
15.2 21.1
AC 60 Hz 1-minute Withstand
34
40 50
DC 15-minute wWithstand
53
78 103
BIL and full wave crest
95
125 150
Minimum corona voltage level
11
19 26
Current ratings
15 kV
25 kV 35 kV
Continuous
200 A rms
200 A rms 200 A rms
Switching
10 make/break operations at 200 A rms at 14.4 kV
10 make/break operations at 200 A rms at 26.3 kV 10 make/break operations at 200 A rms at 36.6 kV
Fault closure
10,000 A rms sym. at 14.4 kV for 0.17s after 10 switching operations
10,000 A rms sym. at 26.3 kV for 0.17s after 10 switching operations 10,000 A rms sym. at 36.6 kV for 0.17s after 10 switching operations
Short time
10,000 A rms sym. for 0.17s 
10,000 A rms sym. for 0.17s 10,000 A rms sym. for 0.17s 
3,500 A rms sym. for 3.0s
3,500 A rms sym. for 3.0s 3,500 A rms sym. for 3.0s

15 kV class 600 A Cleer loadbreak connector system ratings

600 A loadbreak interface
Continuous current
600 A rms 
Loadbreak switching
Ten make and break operations at 600 A at 14.4 kV phase-phase
Three make and break operations at 900 A at 14.4 kV phase-phase
Fault closure
16 kA rms symmetrical at 14.4 kV phase-phase after ten 600 A loadbreak switching operations for 0.17 seconds
16 kA rms symmetrical at 14.4 kV phase-phase after three 900 A loadbreak switching operations for 0.17 seconds
4-hour overload current
900 A rms
Short-time current
16 kA rms symmetrical for 0.17 seconds (limited by fault closure rating)*
10 kA rms symmetrical for 3.0 seconds
IEEE Std 386 -2006 standard 600 A, 15/25 kV feadbreak interface
Continuous current
600 A rms
4-hour overload current
900 A rms
Short-time current
16 kA rms symmetrical for 0.17 seconds* 
10 kA rms symmetrical for 3.0 seconds
Current ratings and characteristics are in accordance with applicable IEEE Std 386-2006 standard requirements
*600 A loadbreak connectors are generally capable of short-time current ratings well in excess of those listed (25 kA to 40 kA ratings for 0.17s are typical). However, ratings are limited by the fault-closure rating. Contact your Eaton representative for maximum short-time current ratings if fault-closure operations are infeasible in your application

25 kV class 600 A Cleer loadbreak connector system ratings

600 A loadbreak interface
Continuous current
600 A rms
Loadbreak switching 
Five make and break operations at 600 A at 26.3 kV phase-phase
One make and break operation at 900 A at 26.3 kV phase-phase
Fault closure
10 kA rms symmetrical at 26.3 kV phase-phase after five 600 A loadbreak switching operations for 0.17 seconds
10 kA rms symmetrical at 26.3 kV phase-phase after one 900 A loadbreak switching operations for 0.17 seconds
4-hour overload current
900 A rms
Short-time current
10 kA rms symmetrical for 0.17 seconds (limited by fault closure rating)*
10 kA rms symmetrical for 3.0 seconds
IEEE Std 386 -2006 standard 600 A, 15/25 kV deadbreak interface
Continuous current
600 A rms
4-hour overload current
900 A rms
Short-time Current
10 kA rms symmetrical for 0.17 seconds*
10 kA rms symmetrical for 3.0 seconds
Current ratings and characteristics are in accordance with applicable IEEE Std 386-2006 standard requirements
*600 A loadbreak connectors are generally capable of short-time current ratings well in excess of those listed (25 kA to 40 kA ratings for 0.17s are typical). However, ratings are limited by the fault-closure rating. Contact your Eaton representative for maximum short-time current ratings if fault-closure operations are infeasible in your application

28 kV class 600 A Cleer loadbreak connector system ratings

600 A loadbreak interface
Continuous current
600 A rms
Loadbreak switching
Five make and break operations at 600 A at 28.0 kV phase-phase
One make and break operation at 900 A at 28.0 kV phase-phase
Fault closure
10 kA rms symmetrical at 28.0 kV phase-phase after five 600 A loadbreak switching operations for 0.17 seconds
10 kA rms symmetrical at 28.0 kV phase-phase after one 900 A loadbreak switching operation for 0.17 seconds
4-hour overload current
900 A rms
Short-time current (See Important below)
25 kA rms symmetrical for 0.17 seconds (limited by fault closure rating)*
10 kA rms symmetrical for 3.0 seconds
IEEE Std 386 -2006 standard 600 A, 15/25 kV deadbreak interface
Continuous current
600 A rms
4-hour overload current
900 A rms
Short-time current (See Important below)
25 kA rms symmetrical for 0.17 seconds*
10 kA rms symmetrical for 3.0 seconds
Current ratings and characteristics are in accordance with applicable IEEE Std 386-2006 standard requirements
*600 A loadbreak connectors are generally capable of short-time current ratings well in excess of those listed (25 kA to 40 kA ratings for 0.17s are typical). However, ratings are limited by the fault-closure rating. Contact your Eaton representative for maximum short-time current ratings if fault-closure operations are infeasible in your application