Eaton xEnergy Safety Ci LV systems LV switchgear. Base, HxWxD=750x375x120mm
Product Name |
Eaton xEnergy Safety Ci empty enclosure base
|
Catalog Number |
083880
|
Model Code |
U-CI48
|
EAN |
4015080838807
|
Product Length/Depth |
150 mm
|
Product Height |
750 mm
|
Product Width |
375 mm
|
Product Weight |
1.92 kg
|
Compliances |
RoHS conform
|
Certifications |
EN 62208
EN 61439-2 |
Special features |
|
Type |
Basic enclosure
|
Features |
Cover with overpressure release
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
Meets the product standard's requirements.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
960 °C
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Not relevant to indoor installations.
|
10.2.5 Lifting |
40 kg per enclosure with support frame and lifting aid met, assembled and secured as per the latest applicable instruction leaflet.
|
10.2.6 Mechanical impact |
IK10
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
IP65, with cover
|
10.4 Clearances and creepage distances |
Is the panel builder's responsibility.
|
10.5 Protection against electric shock |
Protection class 2, therefore not applicable.
|
10.6 Incorporation of switching devices and components |
Is the panel builder's responsibility.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Ui = 1000 V AC
|
10.9.3 Impulse withstand voltage |
8 kV
|
10.9.4 Testing of enclosures made of insulating material |
Meets the product standard's requirements.
|
Accessory/spare part type |
Bases for panel enclosures
|
Degree of protection |
IK10
IP65 Other |
Enclosure material |
Plastic
|
Surface protection |
Other
|
Circuit integrity |
Other
|
Base type |
Closed, with full area knockout
|
Unit type |
Modular system
|
Built-in depth |
250 mm
|
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890) |
37 W
|
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890) |
33 W
|
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890) |
35 W
|
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890) |
75 W
|
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890) |
67 W
|
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890) |
71 W
|
Color |
Gray
|
Cover/door model |
Closed
|
Cover/door type |
None
Optional |
Number of openings (flange plates) |
6
|
Plate thickness (cabinet) |
6 mm
|
Plate thickness (cover/door) |
6 mm
|
RAL-number |
7035
|
Width in number of modular spacings |
17
|
Cable entry type |
Transverse
FL4... flange Top and bottom |
Mounting method |
Surface mounted (plaster)
|
Number of rows |
0
|
Functions |
Extension possible
|
Protection class |
II
|
Number of modules |
1
|
Internal depth |
100 mm
|
Nominal current |
1600 A
|
Number of conduit inlets |
0
|
Suitable for |
Lightning protection
Outdoor use |
Enclosure material quality |
Other
|
Type of coating |
Other
|