Eaton Moeller® series DILL Lamp load contactor, 230 V 50 Hz, 240 V 60 Hz, 220 V 230 V: 20 A, Contactors for lighting systems
Product Name |
Eaton Moeller® series DILL lamp load contactor
|
Catalog Number |
104408
|
Model Code |
DILL20(230V50HZ,240V60HZ)
|
EAN |
4015081042258
|
Product Length/Depth |
97 mm
|
Product Height |
85 mm
|
Product Width |
45 mm
|
Product Weight |
0.426 kg
|
Compliances |
CE Marked
|
Certifications |
IEC 60947-4-1
EN 60947-4-1 CSA Std. C22.2 No. 14-05 UL 508 VDE CE CSA Class No.: 3211-04 VDE 0660 CSA-C22.2 No. 60947-4-1-14 UL Category Control No.: NLDX IEC/EN 60947 CSA File No.: 012528 CSA IEC/EN 60947-4-1 UL 60947-4-1 UL UL File No.: E29096 |
Number of poles |
Three-pole
|
Application |
Contactors for lighting systems
|
Degree of protection |
IP00
|
Lifespan, electrical |
10,000 Operations
|
Lifespan, mechanical |
1,000,000 Operations (AC operated)
|
Connection |
Screw terminals
|
Operating frequency |
60 mechanical Operations/h (AC operated)
60 electrical Operations/h |
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
DILL Lighting contactors
|
Rated impulse withstand voltage (Uimp) |
8000 V AC
|
Resistance per pole |
2.65 mΩ
|
Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
|
Voltage type |
AC
|
Shock resistance |
6.9 g, N/O main contact, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
|
Altitude |
Max. 2000 m
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
-25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Emitted interference |
According to EN 60947-1
|
Interference immunity |
According to EN 60947-1
|
Permissible compensation capacity |
470 µF
|
Rated breaking capacity at 380/400 V |
320 A
|
Rated operational current (Ie) |
23 A (Mercury blended lamps)
12 A (Low-pressure sodium lamps) 20 A (High-pressure mercury vapor lamps) 27 A at AC-3, 220/230 V 35 A (Conventional reactor starter circuit) 20 A at AC-1, 220 V 230 V 20 A (Electronic upstream devices) 20 A (High-pressure sodium lamps) 20 A at AC-1, 380 V 400 V 27 A (Filament bulbs) 35 A (Fluorescent lamp load - duo circuit) 20 A (Metal-halide lamps) |
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
20 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
0 A
|
Rated insulation voltage (Ui) |
690 V
|
Rated making capacity (cos phi to IEC/EN 60947) |
550 A
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
0 kW
|
Rated operational voltage (Ue) at AC - max |
690 V
|
Short-circuit current rating (basic rating) |
125 A, max. Fuse, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA) 125 A, max. CB, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 480 V) |
100 kA, Fuse, SCCR (UL/CSA)
32 A, max. CB, SCCR (UL/CSA) 22 kA, CB, SCCR (UL/CSA) 125 A, Class J, max. Fuse, SCCR (UL/CSA) |
Short-circuit current rating (high fault at 600 V) |
100 kA, Fuse, SCCR (UL/CSA)
32 A, max. CB, SCCR (UL/CSA) 125 A, Class J, max. Fuse, SCCR (UL/CSA) 22 kA, CB, SCCR (UL/CSA) |
Short-circuit protection rating (type 2 coordination) at 400 V |
125 A gG/gL
|
Switching capacity (main contacts, general use) |
40 A, Maximum motor rating (UL/CSA)
|
Drop-out voltage |
AC operated: 0.6 - 0.3 x UC, AC operated
|
Duty factor |
100 %
|
Pick-up voltage |
0.8 - 1.1 V AC x Uc
|
Power consumption, pick-up, 50 Hz |
52 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
|
Power consumption, pick-up, 60 Hz |
67 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
|
Power consumption, sealing, 50 Hz |
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
7.1 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
Power consumption, sealing, 60 Hz |
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
8.7 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
Rated control supply voltage (Us) at AC, 50 Hz - min |
230 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
230 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
240 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Switching time (AC operated, make contacts, closing delay) - min |
16 ms
|
Switching time (AC operated, make contacts, closing delay) - max |
22 ms
|
Switching time (AC operated, make contacts, opening delay) - min |
8 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
14 ms
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Special purpose rating of tungsten incandescent lamps |
40 A, 480 V 60 Hz 3phase, 277 V 60 Hz 1phase, (UL/CSA)
40 A, 600 V 60 Hz 3phase, 347 V 60 Hz 1phase, (UL/CSA) |
Equipment heat dissipation, current-dependent Pvid |
4.5 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
1.5 W
|
Rated operational current for specified heat dissipation (In) |
27 A
|
Static heat dissipation, non-current-dependent Pvs |
2.1 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |