Eaton ESR5 Safety relay emergency stop/protective door/light curtain, 24 V DC, 4 enabling paths(2del.)
Product Name |
Eaton ESR5 Safety relay
|
Catalog Number |
118705
|
Model Code |
ESR5-NV3-30
|
EAN |
4015081168453
|
Product Length/Depth |
114.5 mm
|
Product Height |
99 mm
|
Product Width |
22.5 mm
|
Product Weight |
0.171 kg
|
Certifications |
EN ISO 13849-1
CE CSA Class No.: 3211-83; 3211-03 IEC 61508, Parts 1-7 UL File No.: E29184 UL 508 UL report applies to both US and Canada IEC/EN 60204 EN 50178 Certified by UL for use in Canada IEC 62061 2014/30/EU CSA-C22.2 No. 14-95 UL Category Control No.: NKCR; NKCR7 UL Machines 2006/42/EG |
Electric connection type |
Screw connection
|
Features |
Automatic start
Manual start Basic insulation 2 Non-delayed enable current paths |
Fitted with: |
Approval for TÜV
Start input Selectable cross-circuit detection Detachable clamps Feedback circuit Approval according to UL |
Functions |
1-channel
2-channel Time function |
Material |
Contacts: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au)
Enclosure: Polyamide (PA), not reinforced |
Connection type |
M3 screw terminals
|
Current consumption |
75 mA, DC
|
Degree of protection |
Terminals: IP20
IP20 Installation location: ≥ IP54 Enclosure: IP20 |
Duty factor |
100 %
|
Emitted interference |
According to EN 61000-6-4
|
Interference immunity |
According to EN-61000-6-2
According to EN 662061_x |
LED indicator |
Status indication of SmartWire-DT network: Green LED
|
Lifespan, mechanical |
10,000,000 Operations
|
Lifetime |
240 month
|
Model |
Basic device
|
Mounting method |
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Rail mounting possible |
Mounting width |
22.5 mm
|
Overvoltage category |
III
|
Pollution degree |
2
|
Power loss |
Normally 7.8 W
|
Product category |
Electronic safety relays
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated impulse withstand voltage (Uimp) |
4000 V AC
|
Recovery time |
330 ms (restart)
|
Safety performance level (EN ISO 13849-1) |
Level e
|
Safety parameter (IEC 62061) |
SIL 3 only for high demand requirements, Safety integrity level
Cat. 4, Category 18 x 10-10, PFHd, Probability of failure per hour SIL 3, Safety integrity level SILCL 3, Safety integrity level claim limit SIL 3, Safety integrity level, In accordance with IEC 61508 |
Stop category (IEC 60204) |
0
1 |
Suitable for |
Monitoring of position switches
Module used to safely interrupt electrical circuits Safety relay for monitoring emergency stop and protective door switch Monitoring of optoelectronic protection equipment Monitoring of emergency-stop circuits Safety position switch with mechanical securing action LS-S…MT-ZBZ |
Switching frequency |
Max. 0.5 Hz, Input data
|
Type |
|
Voltage type |
DC
|
Mounting position |
As required
|
Prooftest |
240 Months (High Demand)
|
Switching capacity |
3 A at 3600 O/h, DC-13 at 24 V, Outputs
5 A at 3600 O/h, AC-15 at 230 V, Outputs 0.4 W In accordance with IEC 60947-5-1, Outputs |
Vibration resistance |
10 - 150 Hz, Amplitude: 0.15 mm, Acceleration: 2 g, (IEC/EN 60068-2-6)
|
Air pressure |
795 - 1080 hPa (operation)
|
Altitude |
Max. 2000 m
|
Ambient operating temperature - min |
-20 °C
|
Ambient operating temperature - max |
45 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3 Cold to EN 60068-2-1 |
Environmental conditions |
Clearance in air and creepage distances according to EN 60947-1, UL 508, CSA C22.2, No. 14-95
Condensation: Non-condensing |
Operating temperature - min |
-20 °C
|
Operating temperature - max |
45 °C
|
Relative humidity |
< 75 %
|
Terminal capacity |
2 x (0.2 – 1) mm², solid
24 - 12 AWG, solid or stranded 1 x (0.2 – 2.5) mm², solid 2 x (0.25 – 1) mm², flexible with ferrule 1 x (0.25 – 2.5) mm², flexible with ferrule |
Stripping length (main cable) |
7 mm
|
Screwdriver size |
0.6 x 3.5 mm, Terminal screws
2, Terminal screw, Pozidriv screwdriver |
Tightening torque |
0.6 Nm, Screw terminals
|
Inrush current |
0.025 - 6 A
|
Power supply circuit |
1.8 W (DC operated)
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
0 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
26.4 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
20.4 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
26.4 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Rated insulation voltage (Ui) |
250 V
|
Rated operational voltage |
24 V DC (power supply)
Approx. 24 V DC at input, starting and feedback circuit 230 V AC |
Short-circuit current |
0.1 A, Input data
|
Short-circuit protection |
Fuse 10 A gL/gG NEOZED, For output circuits, External
|
Short-circuit protection rating |
10A gL/gG, NEOZED (N/O), Output fuse, External, Output data
6A gL/gG, NEOZED (N/C), Output fuse, External, Output data |
Breaking power |
144 W max., resistive load (τ = 0 ms), at 24 V DC
42 W max., inductive load (τ = 40 ms), at 24 V DC 88 W max., resistive load (τ = 0 ms), at 220 V DC 1500 VA, max., resistive load (τ = 0 ms), at 250 V AC 23 W max., inductive load (τ = 40 ms), at 220 V DC 288 W max., resistive load (τ = 0 ms), at 48 V DC 33 W max., inductive load (τ = 40 ms), at 48 V DC 25 W max., inductive load (τ = 40 ms), at 110 V DC 90 W max., resistive load (τ = 0 ms), at 110 V DC |
Input |
∞ ms, Simultaneity for inputs 1/2
|
Nominal current |
3.5 A
|
Number of inputs |
One- and two-channel
|
Number of outputs (safety related, delayed) with contact |
2
|
Number of outputs (safety related, undelayed) with contact |
2
|
Number of outputs (signaling function, delayed) with contact |
0
|
Number of outputs (signaling function, undelayed) with contact |
0
|
Off-delay |
0.1 - 30 s (± 40 %, K3, K4 adjustable)
|
Permissible total cable resistance |
500 Ω (input and starting circuits for UN)
|
Pick-up time |
150 ms typ. (at Uₑ in automatic mode)
150 ms typ. (controlled start, K1, K2 - for UN manual operation) 150 ms typ. (controlled start, K1, K2 - for UN automatic mode) 150 ms typ. (at Uₑ in manual mode) |
Quadratic summation current |
55 A² (ITH² = I1² + I2² + I3² + I4² + I5²)
|
Reset time |
Normally 100 ms (delayed contacts)
20 ms (non-delayed contacts) |
Resistance |
500 Ω (impedance)
|
Switching voltage |
250 V
|
Uninterrupted current |
6 A N/O, Limiting continuous current
6 A N/C, Limiting continuous current |
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
7.8 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|