Eaton DB1 Variable frequency drive, 400 V AC, 3-phase, 4.1 A, 1.5 kW, IP20/NEMA 0, Radio interference suppression filter, FS1
Product Name |
Eaton DB1 Variable frequency drive
|
Catalog Number |
197197
|
Model Code |
DB1-344D1FN-N2CC
|
EAN |
4015080896951
|
Product Length/Depth |
74 mm
|
Product Height |
130 mm
|
Product Width |
118 mm
|
Product Weight |
0.7 kg
|
Certifications |
CE
UL report applies to both US and Canada IEC/EN61800-3 UL UL File No.: E172143 IEC/EN61800-5 RCM CSA CUL IEC/EN 61800-2 Certified by UL for use in Canada UL Category Control No.: NMMS, NMMS7 IEC/EN 61800-3 CSA-C22.2 No. 14 RoHS, ISO 9001 Safety: EN 61800-5-1: 2003 UL 508C CSA-C22.2 No. 274 IEC/EN 61800-5-1 CE marking |
Features |
Parameterization: Fieldbus
Parameterization: Keypad Parameterization: drivesConnect Parameterization: drivesConnect mobile (App) |
Fitted with: |
Internal DC link
PC connection IGBT inverter Radio interference suppression filter Additional PCB protection |
Cable length |
C2 ≤ 3 m, maximum motor cable length
C3 ≤ 10 m, maximum motor cable length C1 ≤ 1 m, maximum motor cable length 10 m, screened, maximum permissible cable length |
Communication interface |
CANopen®
Modbus RTU OP-Bus (RS485) |
Connection to SmartWire-DT |
No
|
Degree of protection |
IP20
NEMA Other |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Frame size |
FS1
|
Number of slots |
1 (expansion)
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
CAN
MODBUS Other bus systems |
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: for conducted emissions only |
Suitable for |
Branch circuits, (UL/CSA)
|
Mounting position |
As required
Depending on the cooling |
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms
|
Vibration |
Resistance: According to EN 61800-5-1
|
Altitude |
Max. 2000 m
Max. 1000 m Above 1000 m with 1 % derating per 100 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
60 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
97 % (η)
|
Heat dissipation at current/speed |
27 W at 25% current and 0% speed
29 W at 25% current and 50% speed 30 W at 50% current and 0% speed 35 W at 50% current and 50% speed 36 W at 50% current and 90% speed 47 W at 100% current and 0% speed 50 W at 100% current and 50% speed 53 W at 100% current and 90% speed |
Input current ILN at 150% overload |
5.6 A
|
Leakage current at ground IPE - max |
3.5 mA (at 3 x 400 V)
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
380 V
|
Mains voltage - max |
480 V
|
Operating mode |
U/f control
Speed control with slip compensation BLDC motors PM motors Sensorless vector control (SLV) Synchronous reluctance motors |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
400 V AC, 3-phase
480 V AC, 3-phase |
Overload current IL at 150% overload |
6.15 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) at 150% overload |
4.1 A
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
1.5 kW
|
Rated operational voltage |
480 V AC, 3-phase
400 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
10 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
175 %, IH, max. starting current (High Overload), For 3.75 seconds every 600 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 32 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
480 VAC
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
4.1 A
|
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
4.1 A
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
2 HP
|
Apparent power at 400 V |
1.64 kVA
|
Apparent power at 480 V |
1.97 kVA
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
4
|
Number of outputs (analog) |
1
|
Number of outputs (digital) |
1
|
Number of relay outputs |
1 (parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA)
|
Equipment heat dissipation, current-dependent Pvid |
53 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
4.1 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|