Eaton DG1 Variable frequency drive, 400 V AC, 3-phase, 170 A, 90 kW, IP54/NEMA12, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9702-5109-00P
|
Model Code |
DG1-34170FB-C54C
|
EAN |
4015081711079
|
Product Length/Depth |
340.7 mm
|
Product Height |
888.5 mm
|
Product Width |
288 mm
|
Product Weight |
75.9 kg
|
Certifications |
CE
Certified by UL for use in Canada CSA-C22.2 No. 274-13 IEC/EN 61800-3 Safety requirements: IEC/EN 61800-5 IEC/EN61800-5 UL File No.: E134360 UL508 EAC RoHS, ISO 9001 C-Tick Specification for general requirements: IEC/EN 61800-2 UL UkrSEPRO UL Category Control No.: NMMS, NMMS7 IEC/EN61800-3 CUL UL report applies to both US and Canada |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Product Category |
Variable frequency drives
|
Features |
Temperature-controlled fan
Externally accessible fan Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Fitted with: |
Control unit
Brake chopper Breaking resistance Radio interference suppression filter Additional PCB protection Multi-line graphic display IGBT inverter DC link choke Internal DC link PC connection |
Pollution degree |
2
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Connection to SmartWire-DT |
Yes
In conjunction with DXG-NET-SWD SmartWire DT module |
Operating mode |
Speed control with slip compensation
Torque regulation Sensorless vector control (SLV) U/f control |
Frame size |
FS5
|
Air volume capacity |
395 m³/h
|
Altitude |
Max. 3000 m
Max. 2000 m for Corner Grounded TN Systems Above 1000 m with 1 % derating per 100 m Max. 1000 m |
Environmental class |
3C2, 3S2 (Air quality)
|
Application in domestic and commercial area permitted |
Yes
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Application in industrial area permitted |
Yes
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient storage temperature - max |
70 °C
|
Ambient storage temperature - min |
-40 °C
|
Apparent power at 400 V |
142 kVA
|
Apparent power at 480 V |
177.5 kVA
|
Assigned motor current IM at 400 V, 50 Hz, 110% overload |
196 A
|
Assigned motor current IM at 400 V, 50 Hz, 150% overload |
161 A
|
Mounting position |
Vertical
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Relative symmetric net frequency tolerance |
10 %
|
Relative symmetric net voltage tolerance |
10 %
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload |
132 kW
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Static heat dissipation, non-current-dependent Pvs |
30.74 W
|
Switch-on threshold for the braking transistor |
850 VDC
|
Voltage rating - max |
500 VAC
|
Overvoltage category |
III
|
Communication interface |
CANopen®, optional
PROFIBUS, optional Modbus RTU, built in Ethernet IP, built in DeviceNet, optional Modbus TCP, built in SmartWire-DT, optional BACnet MS/TP, built in |
Converter type |
U converter
|
Degree of protection |
IP54
NEMA 12 |
Protocol |
DeviceNet
PROFIBUS BACnet TCP/IP MODBUS CAN PROFINET IO Other bus systems EtherNet/IP |
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload |
156 A
|
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload |
180 A
|
Assigned motor current IM at 500 V, 50 Hz, 110% overload |
184 A
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
157 A
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
125 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase, 110 % overload |
150 HP
|
Braking resistance |
3.3 Ω
|
Equipment heat dissipation, current-dependent Pvid |
2024 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Input current ILN at 110% overload |
189 A
|
Input current ILN at 150% overload |
157 A
|
Mains current distortion |
29.5 %
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Number of slots |
2 (expansion)
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit Adjustable to 150 %, DC - Main circuit |
Cable length |
C3 ≤ 50 m, Radio interference level, maximum motor cable length
C2 ≤ 10 m, Radio interference level, maximum motor cable length 200 m, screened, maximum permissible, Motor feeder |
Functions |
4-quadrant operation possible
|
Output voltage (U2) |
400 V AC, 3-phase
500 V AC, 3-phase 480 V AC, 3-phase |
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Radio interference class |
C1: with external filter, for conducted emissions only
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Number of outputs (digital) |
1
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Number of phases (input) |
3
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Number of phases (output) |
3
|
Power consumption |
2024 W
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Efficiency |
98.6 % (η)
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Supply frequency |
50/60 Hz
|
Leakage current at ground IPE - max |
7.5 mA
|
Mains voltage - max |
500 V
|
Mains voltage - min |
380 V
|
Nominal output current I2N |
170 A
|
Number of HW-interfaces (industrial ethernet) |
1
|
Number of HW-interfaces (other) |
1
|
Number of HW-interfaces (parallel) |
0
|
Number of HW-interfaces (RS-232) |
0
|
Number of HW-interfaces (RS-422) |
0
|
Number of HW-interfaces (RS-485) |
1
|
Number of HW-interfaces (serial TTY) |
0
|
Number of HW-interfaces (USB) |
0
|
Number of interfaces (PROFINET) |
0
|
Number of outputs (analog) |
2
|
Output at linear load at rated output voltage - max |
90 kW
|
Output at quadratic load at rated output voltage - max |
110 kW
|
Output frequency - max |
400 Hz
|
Output frequency - min |
0 Hz
|
Output voltage - max |
500 V
|
Overload current IL at 110% overload |
225.5 A
|
Overload current IL at 150% overload |
255 A
|
Shock resistance |
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
UPS drop test (for weights inside the UPS frame) Storage and transportation: maximum 15 g, 11 ms (inside the packaging) |
Suitable for |
Branch circuits, (UL/CSA)
|
Switching frequency |
3.6 kHz, 1 - 10 kHz adjustable, fPWM, Power section, Main circuit
|
Rated operational voltage |
400 V AC, 3-phase
500 V AC, 3-phase 480 V AC, 3-phase |
Short-circuit protection rating |
250 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Vibration |
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6 Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) |
Rated frequency - max |
66 Hz
|
Rated frequency - min |
45 Hz
|
Rated operational current (Ie) at 110% overload |
205 A
|
Rated operational current (Ie) at 150% overload |
170 A
|
Rated operational current for specified heat dissipation (In) |
170 A
|
Rated operational power at 380/400 V, 50 Hz, 3-phase |
90 kW
|
Rated operational power at 380/400 V, 50 Hz, 3-phase, 110% overload |
110 kW
|
Rated operational power at 500 V, 50 Hz, 3-phase |
110 kW
|
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Heat dissipation at current/speed |
1022 W at 50% current and 50% speed
1122 W at 50% current and 90% speed 1646 W at 100% current and 0% speed 1928 W at 50% current and 0% speed 2172 W at 100% current and 90% speed 620 W at 25% current and 0% speed 740 W at 25% current and 50% speed 861 W at 100% current and 50% speed |