xPole PFIM Type AC, A, U, R residual current circuit breakers

Eaton offers a complete range of compact residual current devices for fault current/residual current and additional protection in residential and small commercial applications.

xPole PFIM Type AC, A, U, R residual current circuit breakers
Design according to
IEC/EN 61008
Rated short-circuit strength
10 kA
Available types
AC, A, U and R

Core features

  • Compatible with the other devices from the P series, which can be connected by means of a standard busbar
  • Twin-purpose terminal (lift/open-mouthed) at top and bottom
  • Can be positioned on busbar at top or bottom
  • Free terminal space despite installed busbar
  • Z-A universal tripping signal switch (also suitable for PLS and PKN) can be retrofitted
  • Z-HK auxiliary switch can be retrofitted
  • Contact position indicator red - green
  • Time-delayed types suitable for use with standard fluorescent lamps, with or without electronic ballast (30mA-RCD: 30 units per phase conductor, 100mARCD: 90 units per phase conductor)
  • The installation position does not affect the functioning of the device
  • Since tripping does not depend on the mains voltage,
    this RCD is suitable for “fault current/residual current protection” as well as “additional protection” within the meaning of the applicable standards
  • Mains connection at either side
  • The 4-pole device can also be used for 2- or 3-pole connection
The following versions of the xPole PFIM RCCB are available:
Magnet motor electricity
Type A:
Protection against special forms of residual pulsating DC currents that have not been smoothed.
   
Type R:
Prevents nuisance tripping due to X-ray devices.




 
134473914
Type G:
High level of protection against nuisance tripping. Mandatory in circuits where nuisance tripping might cause personal injury or property damage.

Type S:
Selective residual current device for AC current monitoring

Type S/A:
Additional protection against special forms of residual pulsating DC currents that have not been smoothed.

Heathcare - medical
Type G/A:
Additional protection against special forms of residual pulsating DC currents that have not been smoothed. PFIM-...-R special types for X-ray applications.
Type U:
Suitable for use with variable speed drives in household, commercial and industrial applications. This tripping characteristic has been  specifically designed for use with frequency converters to prevent nuisance tripping.

 

Reliable protection for machines

These products help maintain an optimal system and provide additional protection against residual earth leakage currents for a wide range of applications. They come with different tripping characteristics to cater for a variety of electrical systems and components. The devices offer a wide range of nominal currents and comprehensive optional accessories.

Type of protection

Since tripping does not depend on the mains voltage, this RCD is suitable for “fault current/residual current protection” as well as “additional protection” within the meaning of the applicable standards.