Eaton 93PM G2 UPS, 120 kVA (240 kVA Frame), Network card included
| Product Name |
Eaton 93PM G2 UPS
|
| Catalog Number |
GB24A2436A03200000
|
| Product Length/Depth |
99 cm
|
| Product Height |
198.7 cm
|
| Product Width |
80 cm
|
| Product Weight |
404 kg
|
| Compliances |
CB
CE Marked RoHS Compliant |
| Certifications |
EN 62040-3
IEC/EN 62040-2 IEC/EN 62040-1 Manufactured in a plant certified to ISO 9001 and ISO 14001 management system standards |
| EAN |
6430070723501
|
| Model Code |
93PM-G2-120(240)-6
|
| Audible alarms |
Yes
|
| Auto shutdown function |
Yes
|
| Battery charger type |
ABM technology
|
| External battery connection |
Hardwired
|
| Color |
Black
|
| Construction type |
Free standing model
|
| Efficiency (eco-mode) |
99 %
|
| Improved efficiency mode |
ESS with VMMS
|
| Feed type |
AC
|
| Form factor |
Modular
|
| Hot-swappable power modules |
No
|
| Input connection |
Fixed connection
|
| Input nominal voltage |
400V default (380/400/415V)
|
| Number of output connections fixed connection |
1
|
| Output frequency |
50 Hz (50/60 Hz programmable)
|
| Output power factor |
0.9
|
| Overall efficiency |
97 %
|
| Package contents |
|
| Parallelable |
Parallel for capacity and redundancy
|
| Phase (input) |
3
|
| Phase (output) |
3
|
| Potential free switch contact |
Yes
|
| Snmp |
Yes
|
| Topology |
Online
|
| Type Of Interface |
Other
|
| Internal maintenance bypass |
No
|
| kVA rating |
120 kVA
|
| Wattage |
108000 W
|
| Application |
Data center/ facility/IT
|
| Output effective power |
108 kW
|
| Transition time for full load |
0 s
|
| Efficiency (improved efficiency mode) |
99 %
|
| Voltage distortion output (linear load) - max |
1.5 %
|
| Integrated functionality |
Network Mangement
Modular |
| Input frequency - min |
50 Hz
|
| Input frequency - max |
60 Hz
|
| Input voltage - min |
380 V
|
| Input voltage - max |
415 V
|
| Output voltage - min |
380 V
|
| Output voltage - max |
415 V
|
| Secondary Frequency Min |
50 Hz
|
| Secondary Frequency Max |
60 Hz
|
| Output apparent power |
120000 VA
|
| Primary frequency - max |
60 Hz
|
| Primary frequency - min |
50 Hz
|
| Runtime at half load |
0 min
|
| Runtime at full load |
0 min
|
| Mounting Method |
Tower
|
| Degree of Protection |
IP20
|