259489
Model code: NZM1-XUL220-250DC

Eaton Moeller series NZM Undervoltage release, 220-250VDC, for NZM1, L

Spesifikasi umum

Product Name
Eaton Moeller series NZM Undervoltage release
Catalog Number
259489
Model Code
NZM1-XUL220-250DC
EAN
4015082594893
Product Length/Depth
37 mm
Product Height
66 mm
Product Width
32 mm
Product Weight
0.044 kg
Compliances
UL/CSA
IEC
RoHS conform
Certifications
CE marking
CSA-C22.2 No. 5-09
UL (File No. E140305)
UL listed
CSA certified
UL (Category Control Number DIHS)
CSA (Class No. 1437-01)
UL489
CSA (File No. 22086)
IEC60947

Data teknis - elektrik

Voltage type
AC
Rated control voltage (relay contacts)
250 V DC
220 V DC
Rated control supply voltage
220 - 250 V DC
Rated control supply voltage (Us) at DC - min
220 V
Rated control supply voltage (Us) at DC - max
250 V
Voltage tolerance - min
0.85
Voltage tolerance - max
1.1
Drop-out voltage of undervoltage release AC/DC - min
0.35 x Us
Drop-out voltage of undervoltage release AC/DC - max
0.7 x Us
Power consumption
1.5 VA (AC)
0.8 W (DC)
Pick-up power consumption at AC (undervoltage release)
1.5 VA
Pick-up power consumption at DC (undervoltage release)
0.8 W
Reaction time
19 ms
Minimum command time - min
10 ms
Minimum command time - max
15 ms
Electric connection type
Screw connection

Data teknis - komunikasi

Rated control voltage (relay contacts)
250 V DC
220 V DC
Rated control supply voltage
220 - 250 V DC
Rated control supply voltage (Us) at DC - min
220 V
Rated control supply voltage (Us) at DC - max
250 V
Voltage tolerance - min
0.85
Voltage tolerance - max
1.1
Drop-out voltage of undervoltage release AC/DC - min
0.35 x Us
Drop-out voltage of undervoltage release AC/DC - max
0.7 x Us
Power consumption
1.5 VA (AC)
0.8 W (DC)
Pick-up power consumption at AC (undervoltage release)
1.5 VA
Pick-up power consumption at DC (undervoltage release)
0.8 W
Reaction time
19 ms
Minimum command time - min
10 ms
Minimum command time - max
15 ms
Electric connection type
Screw connection

Data teknis - mekanis

Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0
Connection type
With 3 m connection cable instead of screw termination

dataSheetsExport

Catatan: Jika ada file yang hilang dari unduhan .zip, artinya jenis file tersebut tidak dapat diunduh bersamaan dengan jenis file yang lain.