Photo is representative
Download
Eaton DS7 Soft starter, 24 A, 200 - 480 V AC, Us= 24 V AC/DC, Frame size FS2
Product Name |
Eaton DS7 Soft starter
|
Catalog Number |
134913
|
EAN |
4015081316984
|
Product Length/Depth |
118 mm
|
Product Height |
150 mm
|
Product Width |
45 mm
|
Product Weight |
0.4 kg
|
Compliances |
CE Marked
|
Certifications |
IEC 60947-4-2
UL 508 CSA Std. C22.2 No. 14-05 CSA Std. C22.2 No. 0-M91 EN 60947-4-2 C-Tick CSA-C22.2 No 0-M91 UL File No.: E251034 CSA22.2-14 CSA-C22.2 No 14-05 GB 14048.6 IEC/EN 60947-4-2 UkrSEPRO CE CSA File No.: 2511305 CSA Class No.: 321106 UL CSA |
Model Code |
DS7-340SX024N0-N
|
Fitted with: |
Internal bypass contacts
Internal bypass |
Functions |
Suppression of DC components for motors
Min. ramp time 1 s - fast switching (semiconductor contactor) Single direction Suppression of closing transients Soft start function Potential isolation between power and control sections |
Class |
Other
|
Connection to SmartWire-DT |
No
|
Degree of protection |
IP20
NEMA 1 |
Frame size |
FS2
|
Mains voltage - max |
480 V
|
Mains voltage - min |
200 V
|
Overvoltage category |
II
|
Pollution degree |
2
|
Radio interference class |
Class B (EN 55011)
|
Suitable for |
Branch circuits, (UL/CSA)
|
Type |
Soft starter for three-phase loads
|
Voltage type |
AC/DC
|
Mounting position |
Vertical
|
Shock resistance |
8 g, 11 ms, Mechanical
|
Vibration resistance |
2M2 to EN 60721-3-2
|
Altitude |
Max. 2000 m
Above 1000 m with 1 % derating per 100 m |
Ambient operating temperature - max |
40 °C
|
Ambient operating temperature - min |
-5 °C
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-30 |
Overload cycle |
AC-53a: 3 - 5: 75 - 10
|
Rated operational current (Ie) at AC-53 |
24 A
|
Rated operational voltage (Ue) - max |
480 V
|
Rated operational voltage (Ue) - min |
230 V
|
Short-circuit protection rating |
PKM0-25 (+ CL-PKZ0), Type “1” coordination, Main conducting paths
3 x 170M1365, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths |
Supply frequency |
50/60 Hz, fLN, Main circuit
|
Voltage rating - max |
480 V
|
Assigned motor power at 200/208 V, 60 Hz, 3-phase |
7.5 HP
|
Assigned motor power at 220/230 V, 60 Hz, 3-phase |
7.5 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
15 HP
|
Rated operational power at 220/230 V, 50 Hz |
5.5 kW
|
Rated operational power at 400 V, 50 Hz |
11 kW
|
Terminal capacity (flexible with ferrule) |
1 x (0.5 - 1.5) mm², Control circuit cables
2 x (0.75 - 10) mm², Main cables 1 x (0.75 - 16) mm², Main cables 2 x (0.5 - 0.75) mm², Control circuit cables |
Terminal capacity (solid) |
2 x (0.75 - 10) mm², Main cables
1 x (0.75 - 16) mm², Main cables 1 x (0.5 - 2.5) mm², Control circuit cables 2 x (0.5 - 1.0) mm², Control circuit cables |
Terminal capacity (solid/stranded AWG) |
2 x (21 - 18), Control circuit cables
18 - 6, Main cables 1 x (21 - 14), Control circuit cables |
Terminal capacity (stranded) |
1 x (0.5 - 1.5) mm², Control circuit cables
2 x (0.5 - 1.0) mm², Control circuit cables 1 x 16 mm², Main cables |
Screwdriver size |
0.6 x 3.5 mm, Terminal screws, Control circuit cables
PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver |
Tightening torque |
3.2 Nm
1.2 Nm, Screw terminals, Control circuit cables |
Current consumption |
1.6 mA, Control circuit, Digital inputs, External 24 V
50 mA, Control circuit, Regulator supply |
Drop-out time |
350 ms, Control circuit, Digital Inputs, DC operated
|
Drop-out voltage |
AC operated: 0 - 3 V, AC operated
0 - 3 V, DC operated |
Rated control supply voltage (Us) at AC, 50 Hz - min |
24 V
|
Rated control supply voltage (Us) at AC, 50 Hz - min |
24 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
24 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
24 V
|
Rated control supply voltage (Us) at DC - max |
24 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Number of outputs |
2 Relay Outputs (TOR, Ready)
|
Output voltage |
250 V AC (relay outputs)
|
Protection |
Finger and back-of-hand proof, Protection against direct contact
|
Rated control voltage (Uc) |
24 V AC
24 V AC (-15 %/+10 %) 24 V DC 24 V DC (-15 %/+10 %) |
Rated operational current (Ie) at AC-11 |
1 A
|
Application |
|
Delay time |
0 - 30 s, Soft start function, Ramp times
|
Ramp/run-up time |
1 - 30 s
|
Start voltage |
Max. 100 %, Soft start function, Start voltage = turn-off voltage
Min. 30 %, Soft start function, Start voltage = turn-off voltage |
Equipment heat dissipation, current-dependent Pvid |
1.1 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
24 A
|
Static heat dissipation, non-current-dependent Pvs |
1.1 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|