Eaton DA1 Frequency inverter, 500 V AC, 3-phase, 54 A, 37 kW, IP20/NEMA 0, Additional PCB protection, DC link choke, FS5
Product Name |
Eaton DA1 Variable frequency drive
|
Catalog Number |
197502
|
EAN |
4015081940776
|
Product Length/Depth |
261 mm
|
Product Height |
485 mm
|
Product Width |
234 mm
|
Product Weight |
18.2 kg
|
Certifications |
IEC/EN61800-5
Safety: EN 61800-5-1: 2003 EAC UL Certified by UL for use in Canada UL File No.: E172143 RCM RoHS, ISO 9001 IEC/EN 61800-3 IEC/EN61800-3 IEC/EN 61800-2 UkrSEPRO CE CUL UL report applies to both US and Canada UL Category Control No.: NMMS, NMMS7 UL 508C |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Model Code |
DA1-35054NB-B20C
|
Cable length |
150 m, unscreened, maximum permissible cable length
100 m, screened, maximum permissible cable length 200 m, screened, with motor choke, maximum permissible cable length 200 m, unscreened, with motor choke, maximum permissible cable length |
Communication interface |
CANopen®
Modbus RTU EtherCAT, optional OP-Bus (RS485) Modbus-TCP, optional Ethernet IP, optional SmartWire-DT, optional DeviceNet, optional PROFIBUS, optional PROFINET, optional |
Connection to SmartWire-DT |
Yes
In conjunction with DX-NET-SWD1 SmartWire DT module |
Degree of protection |
IP20
NEMA Other |
Fitted with: |
PC connection
OLED display Additional PCB protection IGBT inverter Brake chopper DC link choke Control unit Internal DC link Breaking resistance |
Frame size |
FS5
|
Functions |
4-quadrant operation possible
|
Mounting position |
Vertical
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Protocol |
PROFINET IO
EtherNet/IP DeviceNet MODBUS Other bus systems TCP/IP CAN PROFIBUS |
Safety function/level |
STO (Safe Torque Off, SIL2, PLc Cat 2)
|
Suitable for |
Branch circuits, (UL/CSA)
|
Altitude |
Above 1000 m with 1 % derating per 100 m
Max. 4000 m Max. 1000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-10 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
60 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Efficiency |
98 % (η)
|
Heat dissipation at current/speed |
280 W at 25% current and 0% speed
310 W at 25% current and 50% speed 350 W at 50% current and 0% speed 410 W at 50% current and 50% speed 590 W at 100% current and 0% speed 630 W at 50% current and 90% speed 640 W at 100% current and 50% speed 810 W at 100% current and 90% speed |
Input current ILN at 150% overload |
62.2 A
|
Leakage current at ground IPE - max |
54 mA
|
Mains switch-on frequency |
Maximum of one time every 30 seconds
|
Mains voltage - min |
500 V
|
Mains voltage - max |
600 V
|
Operating mode |
U/f control
Optional: Vector control with feedback (CLV) Speed control with slip compensation Sensorless vector control (SLV) |
Output frequency - min |
0 Hz
|
Output frequency - max |
500 Hz
|
Output voltage (U2) |
500 V AC, 3-phase
600 V AC, 3-phase |
Overload current IL at 150% overload |
81 A
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
48 Hz
|
Rated frequency - max |
62 Hz
|
Rated operational current (Ie) at 150% overload |
54 A
|
Rated operational power at 500 V, 50 Hz, 3-phase |
37 kW
|
Rated operational power at 525 V, 50 Hz, 3-phase |
37 kW
|
Rated operational voltage |
500 V AC, 3-phase
600 V AC, 3-phase |
Resolution |
0.1 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection |
NH fuse used together with TB00-D fuse base, Power wiring, Assigned switching and protective elements
LPJ fuse used together with JM60100-3 fuse base, Power wiring, Assigned switching and protective elements |
Short-circuit protection rating |
80 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), for 4 seconds every 40 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
8 kHz, 4 - 24 kHz adjustable (audible), fPWM, Power section, Main circuit
|
System configuration type |
AC supply systems with earthed center point
|
Voltage rating - max |
600 VAC
|
Assigned motor current IM at 500 V, 50 Hz, 150% overload |
64 A
|
Assigned motor current IM at 525 V, 50 Hz, 150% overload |
51.5 A
|
Assigned motor current IM at 550 - 600 V, 60 Hz, 150% overload |
52 A
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
50 HP
|
Apparent power at 600 V |
56.12 kVA
|
Braking resistance |
16 Ω
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Adjustable to 100 % (DC) Max. 100 % of rated operational current Ie with external braking resistor - Main circuit |
Switch-on threshold for the braking transistor |
975 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
5
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
2
|
Number of relay outputs |
2 (parameterizable, 1 N/O and 1 changeover contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1))
|
Rated control voltage (Uc) |
24 V DC (external, max. 100 mA)
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|