Eaton DG1 Variable frequency drive, 500 V AC, 3-phase, 52 A, 30 kW, IP21/NEMA1, Brake chopper, DC link choke
Product Name |
Eaton DG1 variable frequency drive
|
Catalog Number |
9703-4006-00P
|
EAN |
4015081772209
|
Product Length/Depth |
294 mm
|
Product Height |
630 mm
|
Product Width |
237.7 mm
|
Product Weight |
34.5 kg
|
Certifications |
UL report applies to both US and Canada
Specification for general requirements: IEC/EN 61800-2 Safety requirements: IEC/EN 61800-5 RoHS, ISO 9001 CE IEC/EN61800-3 EAC UL508 IEC/EN61800-5 CUL UL File No.: E134360 IEC/EN 61800-3 UkrSEPRO UL Category Control No.: NMMS, NMMS7 C-Tick UL Certified by UL for use in Canada CSA-C22.2 No. 274-13 |
Catalog Notes |
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
|
Model Code |
DG1-35052FB-C21C
|
Features |
Externally accessible fan
Parameterization: Fieldbus Parameterization: Keypad Parameterization: Power Xpert inControl |
Functions |
4-quadrant operation possible
|
Air volume capacity |
260 m³/h
|
Cable length |
C3 ≤ 10 m, Radio interference level, maximum motor cable length
200 m, screened, maximum permissible, Motor feeder |
Degree of protection |
NEMA 1
IP21 |
Electromagnetic compatibility |
1st and 2nd environments (according to EN 61800-3)
|
Environmental class |
3C2, 3S2 (Air quality)
|
Fitted with: |
Additional PCB protection
DC link choke Multi-line graphic display Control unit Radio interference suppression filter Brake chopper IGBT inverter Internal DC link PC connection Breaking resistance |
Frame size |
FS4
|
Mounting position |
Vertical
|
Number of slots |
2 (expansion)
|
Overvoltage category |
III
|
Pollution degree |
2
|
Product Category |
Variable frequency drives
|
Protection |
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
|
Radio interference class |
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
C1: with external filter, for conducted emissions only Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments |
Safety function/level |
STO (Safe Torque Off, SIL1, PLc Cat 1)
|
Shock resistance |
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
Storage and transportation: maximum 15 g, 11 ms (inside the packaging) UPS drop test (for weights inside the UPS frame) |
Suitable for |
Branch circuits, (UL/CSA)
|
Vibration |
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak) Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude |
Altitude |
Max. 2000 m
Above 1000 m with 1 % derating per 100 m Max. 1000 m |
Ambient operating temperature - min |
-10 °C
|
Ambient operating temperature - max |
50 °C
|
Ambient operating temperature at 150% overload - min |
-30 °C
|
Ambient operating temperature at 150% overload - max |
50 °C
|
Ambient storage temperature - min |
-40 °C
|
Ambient storage temperature - max |
70 °C
|
Climatic proofing |
< 95 average relative humidity (RH), no condensation, no corrosion
|
Current limitation |
0.1 - 2 x IH (CT), motor, main circuit
|
Efficiency |
98.3 % (η)
|
Input current ILN at 110% overload |
57.4 A
|
Input current ILN at 150% overload |
48.3 A
|
Leakage current at ground IPE - max |
6 mA
|
Mains current distortion |
31.2 %
|
Mains switch-on frequency |
Maximum of one time every 60 seconds
|
Mains voltage - min |
525 V
|
Mains voltage - max |
600 V
|
Operating mode |
Sensorless vector control (SLV)
U/f control Speed control with slip compensation Torque regulation |
Output frequency - min |
0 Hz
|
Output frequency - max |
400 Hz
|
Output voltage (U2) |
600 V AC, 3-phase
|
Overload current IL at 110% overload |
68.2 A
|
Overload current IL at 150% overload |
78 A
|
Rated conditional short-circuit current (Iq) |
100 kA
|
Rated control supply voltage |
10 V DC (Us, max. 10 mA)
|
Rated frequency - min |
45 Hz
|
Rated frequency - max |
66 Hz
|
Rated operational current (Ie) at 110% overload |
62 A
|
Rated operational current (Ie) at 150% overload |
52 A
|
Rated operational voltage |
600 V AC, 3-phase
|
Resolution |
0.01 Hz (Frequency resolution, setpoint value)
|
Short-circuit protection rating |
80 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
|
Starting current - max |
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
|
Supply frequency |
50/60 Hz
|
Switching frequency |
1.5 kHz, 1 - 6 kHz adjustable, fPWM, Power section, Main circuit
|
System configuration type |
TN-S, TN-C, TN-C-S, TT, IT
|
Voltage rating - max |
600 VAC
|
Assigned motor current IM at 525 V, 50 Hz, 110% overload |
54 A
|
Assigned motor current IM at 525 V, 50 Hz, 150% overload |
44 A
|
Assigned motor current IM at 600 V, 50 Hz, 110% overload |
57.1 A
|
Assigned motor current IM at 600 V, 50 Hz, 150% overload |
47.3 A
|
Apparent power at 600 V |
64.4 kVA
|
Braking resistance |
9 Ω
|
Braking torque |
Max. 30 % MN, Standard - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit Adjustable to 150 % (I/Ie), DC - Main circuit Adjustable to 150 %, DC - Main circuit |
Switch-on threshold for the braking transistor |
1050 VDC
|
Number of inputs (analog) |
2
|
Number of inputs (digital) |
8
|
Number of outputs (analog) |
2
|
Number of outputs (digital) |
1
|
Number of relay outputs |
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
|
Rated control voltage (Uc) |
24 V DC (external, max. 250 mA options incl.)
|
Communication interface |
BACnet MS/TP, built in
CANopen®, optional SmartWire-DT, optional PROFIBUS, optional Modbus RTU, built in Modbus TCP, built in Ethernet IP, built in DeviceNet, optional |
Connection to SmartWire-DT |
In conjunction with DXG-NET-SWD SmartWire DT module
Yes |
Protocol |
TCP/IP
PROFIBUS CAN DeviceNet Other bus systems MODBUS PROFINET IO BACnet EtherNet/IP |
Equipment heat dissipation, current-dependent Pvid |
884 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
52 A
|
Static heat dissipation, non-current-dependent Pvs |
24.65 W
|
Heat dissipation details |
Operation (with 150 % overload), allow for derating
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|