Photo is representative
Download
Eaton Moeller series Circuit breaker BZMC1, Three-pole, 50 A, 415 V, Box terminal
Product Name |
Eaton Moeller series BZM - Molded case circuit breaker
|
Catalog Number |
131261
|
EAN |
4015081282692
|
Product Length/Depth |
130.2 mm
|
Product Height |
86 mm
|
Product Width |
75 mm
|
Product Weight |
0.83 kg
|
Compliances |
RoHS conform
|
Model Code |
BZMC1-A50-BT
|
Amperage Rating |
50 A
|
Voltage rating |
415 V - 415 V
|
Features |
Protection unit
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Pollution degree |
3
|
Mounting Method |
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique |
Equipment heat dissipation, current-dependent |
13.3 W
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Degree of protection |
IP20
|
Electrical connection type of main circuit |
Frame clamp
|
Overvoltage category |
III
|
Number of poles |
Three-pole
|
Type |
Circuit breaker
|
Position of connection for main current circuit |
Front side
|
Rated operational current for specified heat dissipation (In) |
50 A
|
Handle type |
Rocker lever
|
Short delay current setting (Isd) - max |
0 A
|
Short delay current setting (Isd) - min |
0 A
|
Instantaneous current setting (Ii) - max |
720 A
|
Instantaneous current setting (Ii) - min |
480 A
|
Overload current setting (Ir) - max |
0 A
|
Overload current setting (Ir) - min |
0 A
|
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
36 kA
|