Reset
 
                                    
                                
                                    
                                         
		
	
    
        
        
        
        
        
    
    
    Eaton Moeller® series EASY Control relays easyE4 with display (expandable, Ethernet), 12/24 V DC, 24 V AC, Inputs Digital: 8, of which can be used as analog: 4, screw terminal
| Product Name | 
                                                Eaton Moeller® series EASY Control relay
                                             | 
| Catalog Number | 
                                                197211
                                             | 
| EAN | 
                                                4015081939480
                                             | 
| Product Length/Depth | 
                                                58 mm
                                             | 
| Product Height | 
                                                90 mm
                                             | 
| Product Width | 
                                                72 mm
                                             | 
| Product Weight | 
                                                0.25 kg
                                             | 
| Compliances | 
                                                Eaton supports the product until its end of life
                                             | 
| Certifications | 
                                                IEC 60068-2-30  IEC 60068-2-6 IEC/EN 61000-4-2 CSA-C22.2 No. 61010 CULus per UL 61010 EN 61010 IEC/EN 61000-6-3 IEC/EN 61131-2 IEC/EN 61000-6-2 EN 50178 IEC 60068-2-27 UL Listed UL Category Control No.: NRAQ, NRAQ7 UL File No.: E205091 DNV GL CE UL hazardous location group B (hydrogen) UL hazardous location group C (ethylene) UL hazardous location division 2 UL hazardous location group A (acetylene) UL hazardous location class I UL hazardous location group D (propane) | 
| Catalog Notes | 
                                                Accuracy of the real-time clock depending on ambient air temperature - fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible
                                             | 
| Model Code | 
                                                EASY-E4-UC-12RC1
                                             | 
| Features | 
                                                Expandable  Display indication of 6 lines x 16 characters Networkable (Ethernet) | 
| Fitted with: | 
                                                Display  Real time clock Relay output Keypad Timer | 
| Indication | 
                                                LCD-display used as status indication of Digital inputs 24 V DC  LCD-display used as status indication of Digital inputs 12 V DC | 
| Degree of protection | 
                                                IP20
                                             | 
| Display temperature - min | 
                                                0 °C
                                             | 
| Display temperature - max | 
                                                55 °C
                                             | 
| Display type | 
                                                Monochrome
                                             | 
| Frequency counter | 
                                                Pulse shape: Square (digital inputs 24 V DC)  Cable length: ≤ 20 m (screened, Digital inputs 24 V DC) Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC) Pulse pause ratio: 1:1 (Digital inputs 24 V DC) Counter frequency: 5 kHz (Digital inputs 24 V DC) | 
| Input frequency | 
                                                50/60 Hz (Digital inputs, at 24 V DC)
                                             | 
| Insulation resistance | 
                                                According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
                                             | 
| Lifespan, electrical | 
                                                25,000 Operations (Filament bulb load at 1000 W, 230/240 V AC)  25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, uncompensated) 25,000 Operations (Fluorescent lamp load 10 x 58 W at 230/240 V AC, with upstream electrical device) 25,000 Operations (Filament bulb load at 500 W, 115/120 V AC) 25,000 Operations (Fluorescent lamp load 1 x 58 W at 230/240 V AC, conventional, compensated) | 
| Lifespan, mechanical | 
                                                10,000,000 Operations
                                             | 
| Mounting method | 
                                                Screw fixing using fixing brackets ZB4-101-GF1 (accessories)  Front build in possible Rail mounting possible Top-hat rail fixing (according to IEC/EN 60715, 35 mm) Wall mounting/direct mounting | 
| Mounting method | 
                                                Screw fixing using fixing brackets ZB4-101-GF1 (accessories)  Front build in possible Rail mounting possible Top-hat rail fixing (according to IEC/EN 60715, 35 mm) Wall mounting/direct mounting | 
| Overvoltage category | 
                                                III
                                             | 
| Pollution degree | 
                                                2
                                             | 
| Product category | 
                                                Control relays easyE4
                                             | 
| Protocol | 
                                                TCP/IP  MODBUS | 
| Protection | 
                                                Miniature circuit-breaker B16 or slow-blow 8 A fuse, Protection of an output relay
                                             | 
| Rated impulse withstand voltage (Uimp) | 
                                                6 kV (contact-coil)
                                             | 
| Residual ripple | 
                                                ≤ 5 %
                                             | 
| Resolution | 
 | 
| Software | 
                                                EASYSOFT-SWLIC/easySoft
                                             | 
| Switching frequency | 
                                                10 Hz, Relay outputs  2 Hz, Resistive load/lamp load, Relay outputs 0.5 Hz, Inductive load, Relay outputs | 
| Type | 
                                                easyE4 base device
                                             | 
| Used with | 
                                                easyE4
                                             | 
| Utilization category | 
                                                B 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes AC  R 300 Light Pilot Duty, UL/CSA Control Circuit Rating Codes DC | 
| Voltage type | 
                                                AC/DC
                                             | 
| Drop and topple | 
                                                50 mm Drop height, Drop to IEC/EN 60068-2-31
                                             | 
| Height of fall (IEC/EN 60068-2-32) - max | 
                                                0.3 m
                                             | 
| Mounting position | 
                                                Vertical  Horizontal | 
| Shock resistance | 
                                                15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
                                             | 
| Vibration resistance | 
                                                10 - 57 Hz, 0.15 mm constant amplitude  According to IEC/EN 60068-2-6 57 - 150 Hz, 2 g constant acceleration | 
| Air pressure | 
                                                795 - 1080 hPa (operation)
                                             | 
| Ambient operating temperature - min | 
                                                -25 °C
                                             | 
| Ambient operating temperature - max | 
                                                55 °C
                                             | 
| Ambient storage temperature - min | 
                                                -40 °C
                                             | 
| Ambient storage temperature - max | 
                                                70 °C
                                             | 
| Environmental conditions | 
                                                Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201  Condensation: prevent with appropriate measures | 
| Relative humidity | 
                                                5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
                                             | 
| Air discharge | 
                                                8 kV
                                             | 
| Burst impulse | 
                                                2 kV, Supply cable  2 kV, Signal cable According to IEC/EN 61000-4-4 | 
| Contact discharge | 
                                                6 kV
                                             | 
| Electromagnetic fields | 
                                                10 V/m at 0.8 - 1.0 GHz (according to IEC EN 61000-4-3)  1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) | 
| Immunity to line-conducted interference | 
                                                10 V (according to IEC/EN 61000-4-6)
                                             | 
| Radio interference class | 
                                                Class B (EN 61000-6-3)
                                             | 
| Surge rating | 
                                                1 kV, Supply cables, symmetrical, power pulses (Surge), EMC  According to IEC/EN 61000-4-5, power pulses (Surge), EMC 2 kV, Supply cables, asymmetrical, power pulses (Surge), EMC | 
| Voltage dips | 
                                                ≤ 1 ms from rated voltage (12 V DC)  10 ms | 
| Terminal capacity | 
                                                0.2 - 4 mm² (AWG 22 - 12), solid  0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule | 
| Screwdriver size | 
                                                3.5 x 0.8 mm, Terminal screw
                                             | 
| Tightening torque | 
                                                0.6 Nm, Screw terminals
                                             | 
| Conventional thermal current Ith of auxiliary contacts (1-pole, open) | 
                                                8 A
                                             | 
| Power consumption | 
                                                3 W
                                             | 
| Rated breaking capacity | 
                                                300000 Operations at AC-15, 250 V AC, 3 A (600 Ops./h)  200000 Operations at DC-13, 24 V DC, 1 A (500 Ops./h) | 
| Rated insulation voltage (Ui) | 
                                                240 V
                                             | 
| Rated operational voltage | 
                                                Max. 300 V DC  12 V DC (digital inputs) Max. 300 V AC 240 V AC 24 V AC (-15 %/+10 % - power supply) 24 V DC (digital inputs) 12/24 V DC (-15 %/+ 20 % - power supply) 10.2 - 28.8 V DC 24 V AC (digital inputs) 20.4 - 26.4 V AC | 
| Supply frequency | 
                                                50/60 Hz (± 5%)
                                             | 
| Supply voltage at AC, 50 Hz - min | 
                                                20.4 VAC
                                             | 
| Supply voltage at AC, 50 Hz - max | 
                                                26.4 VAC
                                             | 
| Supply voltage at DC - min | 
                                                10.2 VDC
                                             | 
| Supply voltage at DC - max | 
                                                28.8 VDC
                                             | 
| Uninterrupted current | 
                                                1 A DC, at R 300 (UL/CSA)  8 A DC, at 24 V DC (UL/CSA) 5 A AC, max. thermal continuous current cos ϕ = 1 at B 300 (UL/CSA) 10 A AC, at 240 V AC (UL/CSA) | 
| Short-circuit protection | 
                                                ≥ 1A (T), Fuse, Power supply
                                             | 
| Connection type | 
                                                Screw terminal  Ethernet: RJ45 plug, 8-pole | 
| Data transfer rate | 
                                                10/100 MBit/s
                                             | 
| Cable length | 
                                                100 m, unscreened, Digital inputs 24 V DC  100 m, unscreened, Digital inputs 24 V AC ≤ 30 m, screened, Analog inputs 100 m, unscreened, Digital inputs 12 V DC 40 m (max. per input), Digital inputs 24 V DC | 
| Cable type | 
                                                CAT5
                                             | 
| Accuracy | 
                                                ± 2 s/day, Real-time clock to inputs (± 0.2 h⁄Year)  ± 2 %, (I7, I8) ± 0.12 V, of actual value, within a single device (Analog Inputs) ± 1 %, Repetition accuracy of timing relays (of values) ± 3 %, of actual value, two easy devices (Analog Inputs) | 
| Conversions | 
                                                Each CPU cycle, Analog inputs
                                             | 
| Delay time | 
                                                0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF  0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce OFF 0.015 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF 20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON 20 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON 20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 0 to 1, Debounce ON 20 ms typ., Digital inputs 24 V DC (I1 - I8), Delay time from 1 to 0, Debounce ON 0.015 ms typ., Digital inputs 12 V DC (I1 - I8), Delay time from 0 to 1, Debounce OFF | 
| Incremental counter | 
                                                Number of counter inputs: 2 (I1 + I2, I3 + I4)  Value range: -2147483648 to +2147483647 Pulse shape: Square Pulse pause ratio: 1:1 Signal offset: 90° Counter frequency: ≤ 5 kHz | 
| Incremental encoder | 
                                                Cable length: ≤ 20 m (screened)
                                             | 
| Input | 
                                                Voltage (DC)
                                             | 
| Input current | 
                                                3.3 mA (I1 - I4, at 24 V DC, at signal 1)  2.2 mA (I5 - I8, at 24 V DC, at signal 1) 1 mA (Analog inputs) 200 mA | 
| Input impedance | 
                                                13.3 kΩ
                                             | 
| Input voltage | 
                                                At signal 1: ≥ 15 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC)  Status 0: ≤ 8 V DC (I5 - I8, Digital inputs, 24 V DC) Status 1: ≥ 8 V DC (I5 - I8, Digital inputs, 24 V DC) Signal 0: ≤ 5 V DC (I1 - I4, Digital inputs, 12 V DC) Status 0: ≤ 15 V DC (I1 - I4, Digital inputs, 24 V DC) At signal 0: ≤ 5 V (I1 - I8, sinusoidal, Digital inputs, 24 V DC) Status 1: ≥ 15 V DC (I1 - I4, Digital inputs, 24 V DC) | 
| Making/breaking capacity | 
                                                28/28 VA (DC, at R 300)  3600/360 VA (AC, at B 300) | 
| Number of inputs (analog) | 
                                                0  4 | 
| Number of inputs (digital) | 
                                                4  8 | 
| Number of outputs (analog) | 
                                                0
                                             | 
| Number of outputs (digital) | 
                                                4
                                             | 
| Output | 
                                                4 Relay Outputs  > 500 mA (Relay outputs, Recommended for load: 12 V AC/DC) Relay outputs in groups of 1 Voltage Current | 
| Parallel switching | 
                                                Not permitted
                                             | 
| Rapid counter inputs | 
                                                10 kHz, Counter frequency  -2147483648 - 2147483647 (value range) ≤ 20 m (cable length, screened) 1:1 (Pulse pause ratio) Square (pulse shape) Number: 4 (I1, I2, I3, I4 - Digital inputs 24 V DC) | 
| Signal range | 
                                                0 - 10 V DC, Analog inputs
                                             | 
| Explosion safety category for gas | 
                                                None
                                             | 
| Potential isolation | 
                                                Between Digital inputs 12 V DC and Outputs: yes  Between Analog inputs and Outputs: yes Between Digital inputs 12 V DC and expansion devices: yes Between Digital inputs 24 V DC and Outputs: yes Between Relay outputs and expansion devices: yes Between Digital inputs 24 V AC and Outputs: yes Between Relay outputs and Power supply: yes Between Digital inputs 24 V DC and expansion devices: yes Between Digital inputs 24 V DC and Ethernet: yes Basic isolation: 600 V AC (Relay outputs) Between Analog inputs and expansion devices: yes Between Relay outputs: yes Between Relay outputs and Inputs: yes Between Digital inputs 12 V DC and Ethernet: yes Between Relay outputs and Ethernet: yes Safe isolation according to EN 50178: 300 V AC (Relay outputs) Between Digital inputs 24 V AC and expansion devices: yes Between Digital inputs 24 V AC and Ethernet: yes | 
| Protection against polarity reversal | 
                                                Yes, for supply voltage (Siemens MPI optional)
                                             | 
| Explosion safety category for dust | 
                                                None
                                             | 
| Safe isolation | 
                                                300 V AC, Between coil and contact, According to EN 50178  300 V AC, Between two contacts, According to EN 50178 | 
| Equipment heat dissipation, current-dependent Pvid | 
                                                4 W
                                             | 
| Heat dissipation capacity Pdiss | 
                                                0 W
                                             | 
| Heat dissipation per pole, current-dependent Pvid | 
                                                0 W
                                             | 
| Rated operational current for specified heat dissipation (In) | 
                                                0 A
                                             | 
| Static heat dissipation, non-current-dependent Pvs | 
                                                3 W
                                             | 
| 10.2.2 Corrosion resistance | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.1 Verification of thermal stability of enclosures | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.4 Resistance to ultra-violet (UV) radiation | 
                                                Meets the product standard's requirements.
                                             | 
| 10.2.5 Lifting | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.6 Mechanical impact | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.2.7 Inscriptions | 
                                                Meets the product standard's requirements.
                                             | 
| 10.3 Degree of protection of assemblies | 
                                                Meets the product standard's requirements.
                                             | 
| 10.4 Clearances and creepage distances | 
                                                Meets the product standard's requirements.
                                             | 
| 10.5 Protection against electric shock | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.6 Incorporation of switching devices and components | 
                                                Does not apply, since the entire switchgear needs to be evaluated.
                                             | 
| 10.7 Internal electrical circuits and connections | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.8 Connections for external conductors | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.2 Power-frequency electric strength | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.3 Impulse withstand voltage | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.9.4 Testing of enclosures made of insulating material | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.10 Temperature rise | 
                                                The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
                                             | 
| 10.11 Short-circuit rating | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.12 Electromagnetic compatibility | 
                                                Is the panel builder's responsibility.
                                             | 
| 10.13 Mechanical function | 
                                                The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
                                             |