Photo is representative
Download
Eaton 93E UPS, Tower Online UPS, 100 kVA, 3 phase in/3 phase out, Power factor 0,9, Internal Maintenance Bypass Switch - 93E100KMBS -G2 93E G2 100kVA
Product Name |
Eaton 93E UPS
|
Catalog Number |
93E100K-G2
|
EAN |
6430070722160
|
Product Length/Depth |
800 mm
|
Product Height |
1880 mm
|
Product Width |
600 mm
|
Product Weight |
273 kg
|
Compliances |
CE Marked
RoHS Compliant CB |
Certifications |
IEC/EN 62040-2
IEC/EN 62040-1 EN 62040-3 Manufactured in a plant certified to ISO 9001 and ISO 14001 management system standards |
Audible alarms |
Yes
|
Auto shutdown function |
Yes
|
Battery charger type |
ABM technology
|
External battery connection |
Hardwired
|
Color |
Black
|
Construction type |
Free standing model
|
Efficiency (eco-mode) |
99 %
|
Improved efficiency mode |
High Efficiency
|
Feed type |
AC
|
Form factor |
Tower
|
Hot-swappable power modules |
No
|
Input connection |
Fixed connection
|
Input nominal voltage |
400V default (380/400/415V)
|
Number of output connections fixed connection |
1
|
Output frequency |
50 Hz (50/60 Hz programmable)
|
Output power factor |
.9
|
Overall efficiency |
96 %
|
Package contents |
|
Parallelable |
Parallel for capacity and redundancy
|
Phase (input) |
3
|
Phase (output) |
3
|
Potential free switch contact |
No
|
Snmp |
No
|
Topology |
Online
|
Type Of Interface |
Other
|
Internal maintenance bypass |
No
|
kVA rating |
100 kVA
|
Wattage |
90000 W
|
Application |
Data center/ facility/IT
|
Output effective power |
90 kW
|
Transition time for full load |
0 s
|
Efficiency (improved efficiency mode) |
99 %
|
Voltage distortion output (linear load) - max |
2 %
|
Integrated functionality |
Network Mangement
|
Input frequency - min |
50 Hz
|
Input frequency - max |
60 Hz
|
Input voltage - min |
380 V
|
Input voltage - max |
415 V
|
Output voltage - min |
380 V
|
Output voltage - max |
415 V
|
Secondary Frequency Min |
50 Hz
|
Secondary Frequency Max |
60 Hz
|
Output apparent power |
100000 VA
|
Primary frequency - max |
60 Hz
|
Primary frequency - min |
50 Hz
|
Runtime at half load |
0 min
|
Runtime at full load |
0 min
|
Mounting Method |
Tower
|
Degree of Protection |
IP20
|