Download document () of 20
Discontinued

134238

Eaton XC Modular PLC, 24 V DC, 8DI, 6DO, ethernet, RS232, CAN, 4MB, web Server

General specifications

Product Name
Eaton XC Modular PLC
Catalog Number
134238
EAN
4015081311088
Product Length/Depth
100 mm
Product Height
100 mm
Product Width
60 mm
Product Weight
0.25 kg
Certifications
EN 50178
IEC/EN 61131-2
EAC

Features & Functions

Features
Mains filter (power supply)
Asynchronous, cyclic, acyclic PDO types (CANopen®)
Mains overvoltage protection (power supply)
Expandable with XI/OC expansions
Short-circuit protection (power supply)
Integrated Web server
Fitted with:
Real time clock
Functions
Overvoltage protection
Additional program memory possible
Processor
ARM 532 MHz

General

Accessories
Order terminal clamps, module rack and battery separately.
Battery runtime
5 years typ.
Connection type
RJ45, Ethernet
Plug-in terminal block, CANopen®
Plug-in terminal block
Degree of protection
IP20
Model
Modular
Mounting method
Wall mounting/direct mounting
Rail mounting possible
Overvoltage category
II
Pollution degree
2
Potential isolation
Power supply of local inputs/outputs (24 V/0 V) against CPU voltage: yes
CANopen®: yes
Ethernet: no
Rated impulse withstand voltage (Uimp)
850 V (auxiliary and control circuits)
Residual ripple
≤ 5 %
Voltage type
DC

Ambient conditions, mechanical

Mounting position
Horizontal
Shock resistance
15 g, Mechanical, Shock duration 11 ms
Vibration resistance
57 - 150 Hz, ± 1.0 g
10 - 57 Hz, ± 0.075 mm

Climatic environmental conditions

Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-25 °C
Ambient storage temperature - max
70 °C
Relative humidity
10 - 95 % (non-condensing)

Electro magnetic compatibility

Emitted interference
Class A (according to IEC/EN 61000-6-4)
Interference immunity
According to EN 61000-6-2

Terminal capacities

Terminal capacity (flexible with ferrule)
0.5 - 1.5 mm²
Terminal capacity (flexible)
0.34 - 1.0 mm²
Terminal capacity (solid)
0.14 - 1.0 mm²
0.5 - 2.5 mm²

Power supply

Input power
33 W
Input voltage
24 V DC (Power supply of local inputs/outputs)
24 V DC (Power supply)
Input current
3.5 mA (per channel at nominal voltage, Digital inputs)
Output current
3.2 A
Output voltage
5 V DC (signal module)
Power loss
6 W
Normally 85 mW
Repetition rate
1 s
Residual ripple
≤ 5 %
Supply voltage
20.4 - 28.8 V DC
Supply voltage at AC, 50 Hz - min
0 VAC
Supply voltage at AC, 50 Hz - max
0 VAC
Supply voltage at DC - min
20.4 VDC
Voltage dips
10 ms
Supply voltage at DC - max
28.8 VDC
Inrush current
No limitation (limited only by upstream 24 V DC power supply unit)

Communication

Bus termination
Internal, CANopen®
Connection type
RJ45, Ethernet
Plug-in terminal block, CANopen®
Plug-in terminal block
Cycle time
< 0.025 ms, for 1 k of instructions (Bit, Byte), memory
Data transfer rate
1 MBit/s, CANopen®
10/100 MBit/s, autodetect, Ethernet
115.2 kBit/s, Serial interface (RS232) without handshake lines
Interfaces
USB Host (built-in)
USB 2.0
RS232 (built-in)
Ethernet 100Base-TX/10Base-T (built-in)
CANopen®/easyNet (built-in)
Memory
64 kByte Retain Memory
512 kByte Program memory data
4 MByte Program memory code
16 kByte Marker Memory
4 MByte (User memory)
Number of modules
Max. 126
Operating mode
Watchdog
Protocol
PROFIBUS
MODBUS
SUCONET
EtherNet/IP
Other bus systems
CANopen® (To DS 301 V4)
TCP/IP
CAN

Input/Output

Delay time
0.1 ms typ., Output delay, On -> Off
0.1 ms typ., Digital inputs, Delay time from 0 to 1, Debounce OFF
0.1 ms typ., Digital inputs 24 V DC, Delay time from 1 to 0, Debounce OFF
Duty factor
100 %, Digital outputs
Input current
3.5 mA (per channel at nominal voltage, Digital inputs)
LED indicator
Status indication of Power supply of local inputs/outputs: LED
Limit value type 1
High: > 15 V DC
Low: < 5 V DC
Making/breaking delay
0.1 ms
Number of channels
6
Number of inputs (analog)
0
Number of inputs (digital)
8
Number of outputs
6 (transistor outputs)
Number of outputs (analog)
0
Number of outputs (digital)
6
Number of relay outputs
0
Rated operational current (Ie)
0.5 A at AC-3, 230 V
Signal range
19.2 - 30 V DC (Power supply of local inputs/outputs, note polarity)
Switching capacity
IEC/EN 60947-5-1, utilization category DC-13, Digital outputs
Utilization factor
1 (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 1 ms, R = 48 Ω, L = 16 mH)

Safety

Explosion safety category for gas
None
Potential isolation
Power supply of local inputs/outputs (24 V/0 V) against CPU voltage: yes
CANopen®: yes
Ethernet: no
Protection against polarity reversal
Yes
Yes, for AS-Interface
Explosion safety category for dust
None

System

Memory
64 kByte Retain Memory
512 kByte Program memory data
4 MByte Program memory code
16 kByte Marker Memory
4 MByte (User memory)
Memory capacity
4,000 kByte

Design verification

Equipment heat dissipation, current-dependent Pvid
0.08 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
6 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Export product specification

Note: If file(s) are missing from the .zip download then the file type is not supported by bulk download.