Eaton XC Modular PLC, 24 V DC, 8DI, 6DO, ethernet, RS232, CAN, 4MB, web Server
Product Name |
Eaton XC Modular PLC
|
Catalog Number |
134238
|
EAN |
4015081311088
|
Product Length/Depth |
100 mm
|
Product Height |
100 mm
|
Product Width |
60 mm
|
Product Weight |
0.25 kg
|
Certifications |
EN 50178
IEC/EN 61131-2 EAC |
Features |
Mains filter (power supply)
Asynchronous, cyclic, acyclic PDO types (CANopen®) Mains overvoltage protection (power supply) Expandable with XI/OC expansions Short-circuit protection (power supply) Integrated Web server |
Fitted with: |
Real time clock
|
Functions |
Overvoltage protection
Additional program memory possible |
Processor |
ARM 532 MHz
|
Accessories |
Order terminal clamps, module rack and battery separately.
|
Battery runtime |
5 years typ.
|
Connection type |
RJ45, Ethernet
Plug-in terminal block, CANopen® Plug-in terminal block |
Degree of protection |
IP20
|
Model |
Modular
|
Mounting method |
Wall mounting/direct mounting
Rail mounting possible |
Overvoltage category |
II
|
Pollution degree |
2
|
Potential isolation |
Power supply of local inputs/outputs (24 V/0 V) against CPU voltage: yes
CANopen®: yes Ethernet: no |
Rated impulse withstand voltage (Uimp) |
850 V (auxiliary and control circuits)
|
Residual ripple |
≤ 5 %
|
Voltage type |
DC
|
Mounting position |
Horizontal
|
Shock resistance |
15 g, Mechanical, Shock duration 11 ms
|
Vibration resistance |
57 - 150 Hz, ± 1.0 g
10 - 57 Hz, ± 0.075 mm |
Air pressure |
795 - 1080 hPa (operation)
|
Ambient operating temperature - min |
0 °C
|
Ambient operating temperature - max |
55 °C
|
Ambient storage temperature - min |
-25 °C
|
Ambient storage temperature - max |
70 °C
|
Relative humidity |
10 - 95 % (non-condensing)
|
Emitted interference |
Class A (according to IEC/EN 61000-6-4)
|
Interference immunity |
According to EN 61000-6-2
|
Terminal capacity (flexible with ferrule) |
0.5 - 1.5 mm²
|
Terminal capacity (flexible) |
0.34 - 1.0 mm²
|
Terminal capacity (solid) |
0.14 - 1.0 mm²
0.5 - 2.5 mm² |
Input power |
33 W
|
Input voltage |
24 V DC (Power supply of local inputs/outputs)
24 V DC (Power supply) |
Input current |
3.5 mA (per channel at nominal voltage, Digital inputs)
|
Output current |
3.2 A
|
Output voltage |
5 V DC (signal module)
|
Power loss |
6 W
Normally 85 mW |
Repetition rate |
1 s
|
Residual ripple |
≤ 5 %
|
Supply voltage |
20.4 - 28.8 V DC
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at DC - min |
20.4 VDC
|
Voltage dips |
10 ms
|
Supply voltage at DC - max |
28.8 VDC
|
Inrush current |
No limitation (limited only by upstream 24 V DC power supply unit)
|
Bus termination |
Internal, CANopen®
|
Connection type |
RJ45, Ethernet
Plug-in terminal block, CANopen® Plug-in terminal block |
Cycle time |
< 0.025 ms, for 1 k of instructions (Bit, Byte), memory
|
Data transfer rate |
1 MBit/s, CANopen®
10/100 MBit/s, autodetect, Ethernet 115.2 kBit/s, Serial interface (RS232) without handshake lines |
Interfaces |
USB Host (built-in)
USB 2.0 RS232 (built-in) Ethernet 100Base-TX/10Base-T (built-in) CANopen®/easyNet (built-in) |
Memory |
64 kByte Retain Memory
512 kByte Program memory data 4 MByte Program memory code 16 kByte Marker Memory 4 MByte (User memory) |
Number of modules |
Max. 126
|
Operating mode |
Watchdog
|
Protocol |
PROFIBUS
MODBUS SUCONET EtherNet/IP Other bus systems CANopen® (To DS 301 V4) TCP/IP CAN |
Delay time |
0.1 ms typ., Output delay, On -> Off
0.1 ms typ., Digital inputs, Delay time from 0 to 1, Debounce OFF 0.1 ms typ., Digital inputs 24 V DC, Delay time from 1 to 0, Debounce OFF |
Duty factor |
100 %, Digital outputs
|
Input current |
3.5 mA (per channel at nominal voltage, Digital inputs)
|
LED indicator |
Status indication of Power supply of local inputs/outputs: LED
|
Limit value type 1 |
High: > 15 V DC
Low: < 5 V DC |
Making/breaking delay |
0.1 ms
|
Number of channels |
6
|
Number of inputs (analog) |
0
|
Number of inputs (digital) |
8
|
Number of outputs |
6 (transistor outputs)
|
Number of outputs (analog) |
0
|
Number of outputs (digital) |
6
|
Number of relay outputs |
0
|
Rated operational current (Ie) |
0.5 A at AC-3, 230 V
|
Signal range |
19.2 - 30 V DC (Power supply of local inputs/outputs, note polarity)
|
Switching capacity |
IEC/EN 60947-5-1, utilization category DC-13, Digital outputs
|
Utilization factor |
1 (Inductive load to EN 60947-5-1, Without external suppressor circuit, T0.95 = 1 ms, R = 48 Ω, L = 16 mH)
|
Explosion safety category for gas |
None
|
Potential isolation |
Power supply of local inputs/outputs (24 V/0 V) against CPU voltage: yes
CANopen®: yes Ethernet: no |
Protection against polarity reversal |
Yes
Yes, for AS-Interface |
Explosion safety category for dust |
None
|
Memory |
64 kByte Retain Memory
512 kByte Program memory data 4 MByte Program memory code 16 kByte Marker Memory 4 MByte (User memory) |
Memory capacity |
4,000 kByte
|
Equipment heat dissipation, current-dependent Pvid |
0.08 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
6 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|