Eaton Moeller® series ETR2 Timing relay, 1W, 0.05s-100h, 24-240VAV 50/60Hz, 24-48VDC, on-delayed
Product Name |
Eaton Moeller® series ETR2 Timing relay
|
Catalog Number |
262684
|
EAN |
4015082626846
|
Product Length/Depth |
63 mm
|
Product Height |
70 mm
|
Product Width |
17.5 mm
|
Product Weight |
0.051 kg
|
Certifications |
CSA Class No.: 3211-03
IEC/EN 60947-5-1 UL 508 UL File No.: E29184 UL UL Category Control No.: NKCR, NKCR7 CSA File No.: UL report valid Certified by UL for use in Canada CE CSA-22.2 No. 14 IEC/EN 61812-1 |
Electric connection type |
Screw connection
|
Functions |
On-delayed
Delay-on energization Fixed timing function |
Degree of protection |
IP20
|
Number of contacts (change-over contacts) |
1
|
Product category |
ETR2 timing relays
|
Suitable for |
DIN rail (top hat rail) mounting
|
Time range - min |
0.05 s
|
Time range - max |
360000 s
|
Type |
Timer relay
|
Voltage type |
AC/DC
|
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Mains voltage tolerance |
24 - 240 V AC (at 50/60 Hz)
24 - 48 V DC |
Nominal current |
3 A
|
Rated operational current (Ie) |
3 A at 230 V (NC)
4 A at AC-15, 220 V 230 V 240 V 3 A at 230 V (NO) |
Rated control supply voltage (Us) at AC, 50 Hz - min |
24 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
240 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
24 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
240 V
|
Rated control supply voltage (Us) at DC - min |
24 V
|
Rated control supply voltage (Us) at DC - max |
48 V
|
Heat dissipation capacity Pdiss |
0 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|