Reset
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB. FAZ-NA, 1-pole, tripping characteristic: C, rated current In: 5 A, Switchgear for export to North America (UL-listed)
Product Name |
Eaton Moeller series xEffect - FAZ-NA, FAZ-RT MCB
|
Catalog Number |
102083
|
EAN |
4015081019595
|
Product Length/Depth |
105 mm
|
Product Height |
75.5 mm
|
Product Width |
17.7 mm
|
Product Weight |
0.121 kg
|
Compliances |
RoHS conform
|
Certifications |
UL 489
UL (Category Control Number DIVQ) CE marking IEC/EN 60947-2 Specially designed for North America, suitable as BCPD IEC 60947-2 CSA (File No. 204453) North America (UL listed, CSA certified) UL (File No. E235139) CSA-C22.2 No. 5-09 CSA (Class No. 1432-01) UL 489, CSA C22.2 No. 5 EN45545-2 IEC 61373 |
Model Code |
FAZ-C5/1-NA
|
Used with |
Miniature circuit breaker
FAZ-NA |
Amperage Rating |
5 A
|
Voltage rating |
277 V AC / 480 V AC
|
Features |
Additional equipment possible
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
Frame |
45 mm
|
Pollution degree |
2
|
Mounting Method |
Top-hat rail IEC/EN 60715
|
Degree of protection |
UL/CSA Type: -
IP20 IP20 (IEC) IP40 (when fitted) |
Equipment heat dissipation, current-dependent |
1.9 W
|
Rated impulse withstand voltage (Uimp) |
4 kV
|
Breaking capacity |
10 kA (UL489)
|
Terminal protection |
Finger and hand touch safe, DGUV VS3, EN 50274
|
Terminals (top and bottom) |
Twin-purpose terminals
|
Tripping characteristic |
C
|
Ambient operating temperature - max |
75 °C
|
Ambient operating temperature - min |
-25 °C
|
Built-in depth |
70.5 mm
|
Connectable conductor cross section (multi-wired) - max |
25 mm²
|
Connectable conductor cross section (multi-wired) - min |
1 mm²
|
Connectable conductor cross section (solid-core) - max |
25 mm²
|
Connectable conductor cross section (solid-core) - min |
1 mm²
|
Current limiting class |
3
|
Enclosure width |
105 mm
|
Frequency rating - max |
60 Hz
|
Frequency rating - min |
50 Hz
|
Heat dissipation capacity |
0 W
|
Heat dissipation per pole, current-dependent |
0 W
|
Direction of incoming supply |
As required
|
Width in number of modular spacings |
1
|
Voltage rating (IEC/EN 60947-2) |
254 V
|
Voltage rating (UL) |
277 V
|
Voltage rating at DC |
60 V DC
|
Voltage type |
AC
|
Mounting position |
As required
|
Overvoltage category |
III
|
Number of poles |
Single-pole
|
Functions |
Current limiting circuit breaker
|
Lifespan, electrical |
20000 operations
|
Release characteristic |
C
|
Type |
|
Special features |
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
|
Application |
|
Mounting width |
17.7 mm
|
Selectivity class |
3
|
Mounting width per pole |
17.7 mm
|
Number of poles (protected) |
1
|
Number of poles (total) |
1
|
Rated insulation voltage (Ui) |
440 V
|
Rated operational current for specified heat dissipation (In) |
5 A
|
Rated operational voltage (Ue) - max |
240 V
|
Rated short-circuit breaking capacity (EN 60898) at 230 V |
0 kA
|
Rated short-circuit breaking capacity (EN 60898) at 400 V |
0 kA
|
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V |
15 kA
|
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V |
15 kA
|
Rated switching capacity (IEC/EN 60947-2) |
15 kA
|
Static heat dissipation, non-current-dependent |
0 W
|
Tightening torque |
Max. 2.4 Nm
UL: 2.8 Nm (25 lb-in) for AWG 10 - AWG 8 UL: 2.4 Nm (21 lb-in) for AWG 18 - AWG 12 UL: 4 Nm (36 lb-in) for AWG 6 |
Power loss |
1.6 W
|