Eaton Moeller series xPole (Style 5) - mMCT MCB. Circuit-breaker, 100 A, 3p, Type C characteristic
Product Name |
Eaton Moeller series xPole (Style 5) - mMCT MCB
|
Catalog Number |
129666
|
EAN |
5019586143976
|
Product Length/Depth |
90 mm
|
Product Height |
75 mm
|
Product Width |
81 mm
|
Product Weight |
0.706 kg
|
Compliances |
RoHS conform
|
Model Code |
mMCT-C100/3
|
Used with |
Miniature circuit breaker
mMCT |
Amperage Rating |
100 A
|
Features |
Additional equipment possible
|
Accessories required |
ZP-IHK 286052
|
Fitted with: |
Z-IS/SPE-1TE 274418
|
Frame |
45 mm
|
Pollution degree |
2
|
Mounting Method |
Quick attachment with 3 latch positions for top-hat rail IEC/EN 60715
|
Degree of protection |
IP20
|
Equipment heat dissipation, current-dependent |
27.4 W
27.3 W |
Rated impulse withstand voltage (Uimp) |
4 kV
|
Busbar material thickness |
0.8 mm - 2 mm
|
Tripping characteristic |
C
|
Ambient operating temperature - max |
55 °C
|
Ambient operating temperature - min |
-25 °C
|
Built-in depth |
75 mm
|
Connectable conductor cross section (multi-wired) - max |
50 mm²
|
Connectable conductor cross section (multi-wired) - min |
2.5 mm²
|
Connectable conductor cross section (solid-core) - max |
50 mm²
|
Connectable conductor cross section (solid-core) - min |
2.5 mm²
|
Current limiting class |
3
|
Frequency rating - max |
60 Hz
|
Frequency rating - min |
50 Hz
|
Heat dissipation capacity |
0 W
|
Heat dissipation per pole, current-dependent |
9.1 W
|
Width in number of modular spacings |
4.5
|
Voltage type |
AC
|
Lifespan, mechanical |
20000 operations
|
Overvoltage category |
III
|
Number of poles |
Three-pole
|
Lifespan, electrical |
10000 operations
|
Release characteristic |
C
|
Type |
|
Special features |
|
Application |
Switchgear for industrial and advanced commercial applications
|
Number of poles (protected) |
3
|
Number of poles (total) |
3
|
Rated insulation voltage (Ui) |
440 V
|
Rated operational current for specified heat dissipation (In) |
100 A
|
Rated operational voltage (Ue) - max |
400 V
|
Rated short-circuit breaking capacity (EN 60898) at 230 V |
0 kA
|
Rated short-circuit breaking capacity (EN 60898) at 400 V |
0 kA
|
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V |
20 kA
|
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V |
20 kA
|
Rated switching capacity (IEC/EN 60947-2) |
20 kA
|
Static heat dissipation, non-current-dependent |
0 W
|