Eaton XN-322 Digital input module, 16 digital inputs 24 V DC each, pulse-switching, 5.0 ms
Product Name |
Eaton XN-322 Input module
|
Catalog Number |
183173
|
EAN |
4015081781065
|
Product Length/Depth |
104.2 mm
|
Product Height |
16.8 mm
|
Product Width |
80.3 mm
|
Product Weight |
0.055 kg
|
Certifications |
UL File No.: E135462
CE IEC/EN 61000-6-2 cULus IEC/EN 61131-2 IEC/EN 61000-6-4 |
Catalog Notes |
The max. heat dissipation is specified as the maximum power produced inside the device's housing.
|
Model Code |
XN-322-16DI-PD
|
Electric connection type |
Plug-in connection
|
Features |
Fieldbus connection over separate bus coupler possible
|
Current consumption |
None mA (typ.), for +24 V, Power supply - Input
36 mA (typ.), for +5 V power supply (internal), Power supply - Input |
Degree of protection |
IP20
|
Mounting method |
Rail mounting possible
|
Number of channels |
16
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
XN-322 digital input module
|
Type |
|
Used with |
XN-312-…
XN300 |
Voltage type |
DC
|
Height of fall (IEC/EN 60068-2-32) - max |
1 m
|
Mounting position |
Horizontal
|
Shock resistance |
15 g, Mechanical, Half-sinusoidal shock 11 ms, 18 Impacts
|
Vibration resistance |
5 - 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g
|
Air pressure |
795 - 1080 hPa (operation)
|
Ambient operating temperature - min |
0 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient storage temperature - min |
-20 °C
|
Ambient storage temperature - max |
85 °C
|
Climatic proofing |
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3 |
Environmental conditions |
Condensation: prevent with appropriate measures
|
Relative humidity |
0 - 95 % (non-condensing)
|
Air discharge |
8 kV
|
Burst impulse |
2 kV, Supply cable
1 kV, Signal cable |
Contact discharge |
4 kV
|
Electromagnetic fields |
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3) 3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3) |
Emitted interference |
47 dB (at 230 - 1000 MHz, Class A, radiated, high frequency)
40 dB (at 30 - 230 MHz, Class A, radiated, high frequency) |
Radiated RFI |
10 V
|
Surge rating |
0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC
1 kV, Signal cable, unbalanced, EMC |
Voltage dips |
Voltage dips: 10 ms/Voltage fluctuations: Yes
|
Terminal capacity |
0.2 - 1.5 mm², solid, H07V-U
0.25 - 1.5 mm², with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) 24 - 16 AWG 0.2 - 1.5 mm², flexible without ferrule, H07V-K 0.25 - 0.75 mm², with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight) |
Gauge pin |
A1 (according to IEC/EN 60947-1)
|
Stripping length (main cable) |
10 mm
|
Insulating material group |
I
|
Rated operational voltage |
160 V (terminations)
|
Supply voltage at AC, 50 Hz - min |
0 VAC
|
Supply voltage at AC, 50 Hz - max |
0 VAC
|
Supply voltage at DC - min |
18 VDC
|
Supply voltage at DC - max |
30 VDC
|
Connection type |
Push-in spring-cage terminal (plug-in connection), Connection design in TOP direction
|
Protocol |
Other bus systems
|
Input |
Digital inputs (according to EN61131-2 Type 1)
|
Input current |
3.7 mA (Digital inputs)
≥ 2.3 mA (Digital inputs, high level) ≤ 1.1 mA (Digital inputs, low level) |
Input current at signal 1 |
3.7 mA
|
Input delay |
5000 µs (falling edge)
5000 µs (rising edge) |
Input voltage |
14 - 30 V (Digital inputs, high level)
0 - 8 V (Digital inputs, low level) 24 V DC (Digital inputs) |
Load current |
Not specified by plug manufacturer
|
Number of inputs (digital) |
16
|
Number of outputs (digital) |
0
|
Output current |
0 A
|
Explosion safety category for dust |
None
|
Explosion safety category for gas |
None
|
Potential isolation |
Between Digital inputs: no
|
Equipment heat dissipation, current-dependent Pvid |
0.2 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
0 W
|
Rated operational current for specified heat dissipation (In) |
0 A
|
Static heat dissipation, non-current-dependent Pvs |
2.436 W
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Meets the product standard's requirements.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|