Eaton Moeller® series DILM Contactor, 3 pole, 380 V 400 V 18.5 kW, 380 V 50 Hz, 440 V 60 Hz, AC operation, Screw terminals
Product Name |
Eaton Moeller® series DILM contactor
|
Catalog Number |
277767
|
EAN |
4015082777678
|
Product Length/Depth |
132.1 mm
|
Product Height |
115 mm
|
Product Width |
55 mm
|
Product Weight |
0.872 kg
|
Certifications |
UL
IEC/EN 60947 CSA VDE 0660 |
Catalog Notes |
Contacts according to EN 50012
|
Model Code |
DILM40(380V50HZ,440V60HZ)
|
Number of poles |
Three-pole
|
Application |
Contactors for Motors
|
Connection |
Screw terminals
|
Frame size |
FS3
|
Lifespan, mechanical |
10,000,000 Operations (AC operated)
|
Operating frequency |
5000 mechanical Operations/h (AC operated)
|
Overvoltage category |
III
|
Pollution degree |
3
|
Product category |
Contactors
|
Protection |
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
|
Rated impulse withstand voltage (Uimp) |
8000 V AC
|
Resistance per pole |
1.9 mΩ
|
Suitable for |
Also motors with efficiency class IE3
|
Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces
AC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
Voltage type |
AC
|
Shock resistance |
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27 when tabletop-mounted, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Ambient operating temperature - min |
-25 °C
|
Ambient operating temperature - max |
60 °C
|
Ambient operating temperature (enclosed) - min |
25 °C
|
Ambient operating temperature (enclosed) - max |
40 °C
|
Ambient storage temperature - min |
40 °C
|
Ambient storage temperature - max |
80 °C
|
Climatic proofing |
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78 |
Emitted interference |
According to EN 60947-1
|
Interference immunity |
According to EN 60947-1
|
Terminal capacity (copper band) |
2 x (6 x 9 x 0.8) mm (Number of segments x width x thickness), Main cables
|
Terminal capacity (flexible with ferrule) |
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 35) mm², Main cables 2 x (0.75 - 25) mm², Main cables |
Terminal capacity (solid) |
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 16) mm², Main cables 1 x (0.75 - 4) mm², Control circuit cables 1 x (0.75 - 16) mm², Main cables |
Terminal capacity (solid/stranded AWG) |
18 - 14, Control circuit cables
Single 14 - 1, double 14 - 2, Main cables |
Terminal capacity (stranded) |
2 x (16 - 35) mm², Main cables
1 x (16 - 50) mm², Main cables |
Stripping length (main cable) |
14 mm
|
Stripping length (control circuit cable) |
10 mm
|
Screw size |
M3.5, Terminal screw, Control circuit cables
M6, Terminal screw, Main cables |
Screwdriver size |
2, Terminal screw, Pozidriv screwdriver
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver |
Tightening torque |
1.2 Nm, Screw terminals, Control circuit cables
3.3 Nm, Screw terminals, Main cables |
Rated breaking capacity at 220/230 V |
400 A
|
Rated breaking capacity at 380/400 V |
400 A
|
Rated breaking capacity at 500 V |
400 A
|
Rated breaking capacity at 660/690 V |
250 A
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
60 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
40 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
40 A
|
Rated operational current (Ie) at AC-3, 440 V |
40 A
|
Rated operational current (Ie) at AC-3, 500 V |
40 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
25 A
|
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V |
18 A
|
Rated operational current (Ie) at AC-4, 400 V |
18 A
|
Rated operational current (Ie) at AC-4, 500 V |
18 A
|
Rated operational current (Ie) at AC-4, 660 V, 690 V |
14 A
|
Rated operational current (Ie) at DC-1, 60 V |
50 A
|
Rated operational current (Ie) at DC-1, 110 V |
50 A
|
Rated operational current (Ie) at DC-1, 220 V |
45 A
|
Rated insulation voltage (Ui) |
690 V
|
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V |
60 A
|
Rated operational power at AC-3, 240 V, 50 Hz |
13.5 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
18.5 kW
|
Rated operational power at AC-3, 415 V, 50 Hz |
24 kW
|
Rated operational power at AC-4, 220/230 V, 50 Hz |
5 kW
|
Rated operational power at AC-4, 240 V, 50 Hz |
5.5 kW
|
Rated operational power at AC-4, 415 V, 50 Hz |
9.5 kW
|
Rated operational power at AC-4, 440 V, 50 Hz |
10 kW
|
Rated operational power at AC-4, 500 V, 50 Hz |
11 kW
|
Rated operational power at AC-4, 660/690 V, 50 Hz |
12 kW
|
Rated operational voltage (Ue) at AC - max |
690 V
|
Short-circuit protection rating (type 1 coordination) at 400 V |
125 A gG/gL
|
Short-circuit protection rating (type 1 coordination) at 690 V |
80 A gG/gL
|
Short-circuit protection rating (type 2 coordination) at 400 V |
63 A gG/gL
|
Short-circuit protection rating (type 2 coordination) at 690 V |
50 A gG/gL
|
Conventional thermal current Ith (1-pole, enclosed) |
112 A
|
Conventional thermal current Ith (3-pole, enclosed) |
45 A
|
Conventional thermal current Ith at 55°C (3-pole, open) |
55 A
|
Conventional thermal current Ith of main contacts (1-pole, open) |
125 A
|
Arcing time |
10 ms
|
Switching time (AC operated, make contacts, closing delay) - min |
12 ms
|
Switching time (AC operated, make contacts, closing delay) - max |
18 ms
|
Switching time (AC operated, make contacts, opening delay) - min |
8 ms
|
Switching time (AC operated, make contacts, opening delay) - max |
13 ms
|
Drop-out voltage |
AC operated: 0.6 - 0.3 x UC, AC operated
|
Duty factor |
100 %
|
Pick-up voltage |
0.8 - 1.1 V AC x Uc
|
Power consumption, pick-up, 50 Hz |
149 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
|
Power consumption, pick-up, 60 Hz |
178 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
|
Power consumption, sealing, 50 Hz |
16 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
4.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz |
Power consumption, sealing, 60 Hz |
4.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
19 VA, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz |
Rated control supply voltage (Us) at AC, 50 Hz - min |
380 V
|
Rated control supply voltage (Us) at AC, 50 Hz - max |
380 V
|
Rated control supply voltage (Us) at AC, 60 Hz - min |
440 V
|
Rated control supply voltage (Us) at AC, 60 Hz - max |
440 V
|
Rated control supply voltage (Us) at DC - min |
0 V
|
Rated control supply voltage (Us) at DC - max |
0 V
|
Connection to SmartWire-DT |
No
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Number of auxiliary contacts (normally open contacts) |
0
|
Safe isolation |
440 V AC, Between the contacts, According to EN 61140
440 V AC, Between coil and contacts, According to EN 61140 |
Equipment heat dissipation, current-dependent Pvid |
6.6 W
|
Heat dissipation capacity Pdiss |
0 W
|
Rated operational current for specified heat dissipation (In) |
40 A
|
10.2.2 Corrosion resistance |
Meets the product standard's requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard's requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard's requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard's requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard's requirements.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard's requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard's requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder's responsibility.
|
10.8 Connections for external conductors |
Is the panel builder's responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder's responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder's responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder's responsibility.
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|