Eaton Moeller series NZM Circuit-breaker 3-pole 25A, motor protection, withdrawable unit
| Product Name |
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
|
| Catalog Number |
113294
|
| Model Code |
NZMS2-M25-SVE
|
| EAN |
4015081128297
|
| Product Length/Depth |
180 mm
|
| Product Height |
245 mm
|
| Product Width |
105 mm
|
| Product Weight |
2.785 kg
|
| Compliances |
RoHS conform
|
| Voltage rating |
690 V - 690 V
|
| Rated operational current |
21.7 A (400 V AC-3)
|
| Amperage Rating |
25 A
|
| Instantaneous current setting (Ii) - min |
350 A
|
| Instantaneous current setting (Ii) - max |
350 A
|
| Overload current setting (Ir) - min |
20 A
|
| Overload current setting (Ir) - max |
25 A
|
| Short-circuit release non-delayed setting - min |
350 A
|
| Short-circuit release non-delayed setting - max |
350 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
| Rated operating power at AC-3, 230 V |
5.5 kW
|
| Rated operating power at AC-3, 400 V |
11 kW
|
| Electrical connection type of main circuit |
Screw connection
|
| Handle type |
Rocker lever
|
| Rated operational current |
21.7 A (400 V AC-3)
|
| Amperage Rating |
25 A
|
| Instantaneous current setting (Ii) - min |
350 A
|
| Instantaneous current setting (Ii) - max |
350 A
|
| Overload current setting (Ir) - min |
20 A
|
| Overload current setting (Ir) - max |
25 A
|
| Short-circuit release non-delayed setting - min |
350 A
|
| Short-circuit release non-delayed setting - max |
350 A
|
| Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz |
150 kA
|
| Rated operating power at AC-3, 230 V |
5.5 kW
|
| Rated operating power at AC-3, 400 V |
11 kW
|
| Electrical connection type of main circuit |
Screw connection
|
| Handle type |
Rocker lever
|
| Mounting Method |
Built-in device plug-in technique
|
| Degree of protection |
IP20
|
| Switch off technique |
Thermomagnetic
|