지식 검색
문서 다운로드 () / 20
당신의 필요한 일, 이튼이 합니다*

199536
PV-25A-4P-AC-I2/SVB-SW/N

Eaton PV Main switch, P1, 25 A, surface mounting, 3 pole + N, STOP function, Lockable in the 0 (Off) position PV-25A-4P-AC-I2/SVB-SW/N

일반 규범

Product Name
Eaton PV maintenance switch
Catalog Number
199536
Model Code
PV-25A-4P-AC-I2/SVB-SW/N
EAN
5027590552165
Product Length/Depth
113.4 mm
Product Height
180.3 mm
Product Width
111.4 mm
Product Weight
274 g
Compliances
CE

특징 및 기능

Features
Version as main switch
Version as maintenance-/service switch
Functions
Interlockable
Number of poles
Four-pole

일반

Degree of protection
NEMA Other
Degree of protection (front side)
IP20
Suitable for
Ground mounting

전기 정격

Rated operational power at AC-3, 380/400 V, 50 Hz
7.5 kW
Rated operational power at AC-23A, 400 V, 50 Hz
13 kW
Rated uninterrupted current (Iu)
25 A

단락 정격

Rated conditional short-circuit current (Iq)
80 kA
Rated short-time withstand current (Icw)
0.64 kA

연락처

Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0

액추에이터

Actuator color
Black
Actuator type
Door coupling rotary drive

설계 검증

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
UV resistance only in connection with protective shield.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

제품 사양 내보내기

참고: ZIP 다운로드에 파일이 없는 경우 해당 파일 형식은 대량 다운로드에서 지원되지 않습니다.