AZ-C100

Eaton Moeller series xEffect - AZ MCB. Miniature circuit breaker (MCB) AZ, 1 pole, Tripping characteristic: C, Rated current In: 100 A

일반 규범

Product Name
Eaton Moeller series xEffect - AZ MCB
Catalog Number
211804
Model Code
AZ-C100
EAN
4015082118044
Product Length/Depth
90 mm
Product Height
75 mm
Product Width
27 mm
Product Weight
0.229 kg
Compliances
RoHS compliant
Certifications
IEC/EN 60947-2
EN45545-2
IEC 61373

Delivery program

Application
  • !
  • !
  • Industrial and commercial installations, utilities, OEM control panels, renewable energy installations, IT and data centre auxiliary circuits, railway and transportation systems etc.
Number of poles
Single-pole
Number of poles (total)
1
Number of poles (protected)
1
Tripping characteristic
C
Release characteristic
C
Amperage Rating
100 A
Nominal current
100 A
Type
  • AZ
  • Miniature circuit breaker

Technical data - electrical

Voltage type
AC
Voltage rating
230 V AC
Voltage rating at DC
  • !
  • 60 V
Voltage rating (IEC/EN 60947-2)
230 V AC
Rated operational voltage (Ue) - max
230 V
Operational voltage (IEC/EN 60947-2) - max
230 VAC
Operational voltage at DC (EC/EN 60947-2) - max
60 VDC
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Frequency rating - min
50 Hz
Frequency rating - max
60 Hz
Rated switching capacity (IEC/EN 60947-2)
20 kA
Rated service short-circuit breaking capacity (IEC/EN 60947-2) - Ics
10 kA
Rated short-circuit breaking capacity (IEC 60947-2)- Icu at 230 V
20 kA
Overvoltage category
III
Pollution degree
2
3
Lifespan, electrical
10000 operations
Direction of incoming supply
Bidirectional

Technical data - mechanical

Frame
45 mm
Enclosure width
90 mm
Width in number of modular spacings
1.5
Built-in depth
65.5 mm
Mounting width per pole
27 mm
Mounting width
27 mm
Mounting Method
Two lock-in position on DIN rail (EN/IEC 60715)
Mounting position
As required
Degree of protection
IP20 (With terminal cover)
IP40 (in Enclosure)
Terminal capacity
2.5 mm² - 50 mm²
Terminals (top and bottom)
Screw-type with pressure plate
Connectable conductor cross section (solid-core) - min
2.5 mm²
Connectable conductor cross section (solid-core) - max
50 mm²
Connectable conductor cross section (multi-wired) - min
2.5 mm²
Connectable conductor cross section (multi-wired) - max
50 mm²
Contact position indicator color
Red = ON
Green = OFF

Design verification as per IEC/EN 61439 - technical data

Rated operational current for specified heat dissipation (In)
100 A
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Current limiting class
3
Features
Can be fitted with auxiliary accessories
Suitable for Isolation
Suitable for IT systems
Suitable for Rolling Stock applications
Neutral conductor switches concurrently with the phase conductors
Functional group
Overcurrent protection
Internal resistance at room temperature (single-pole, 50 Hz)
0.8 mΩ